background image

Page 2

STEP 2 - 

WIRING TO THE LED LOAD AND NORMAL DRIVER

Refer to the appropriate wiring diagram 

to the right. Make sure all connections 

are in accordance with NEC and 

any other local requirements. 

The 

ILBDW is designed to interface 

with compatible loads only. 

See 

Illustration 1

 for output voltage ratings 

per ILBDW model.

For “SLTEST” Models

(IPS test switch is secured to the ILBDW housing)

The IPS test switch is pre-installed by the factory. No additional connections 

are needed.

For “S” Models

(IPS test switch is included in the PVC conduit): refer to the steps below for installing the IPS test switch in the luminaire.

ILBDW S AND SLTEST - CONNECTIONS TO NORMAL DRIVER AND LED LOAD

ILBDW-IPS-NORMAL-DRIVER-AND-LED-LOAD.EPS

AC (NORMAL) 

DRIVER

LED

LOAD

WHITE/RED

WHITE

RED (+)

LED OUTPUT (+)

LED OUTPUT (-)

BLUE (-)

LED INPUT (-)

VIOLET/WHITE (+)

LED INPUT (+)

ILBDW

EMERGENCY DRIVER

PVC

CONDUIT

CAUTION:   Before installing, make certain the IP67 Rated Test Switch (IPS) is disconnected (“S” models only) and A.C. power is off.

STEP 1 - 

MOUNTING THE ILBDW

The ILBDW should be mounted nearby the fixture within suitable 

reach of the PVC conduit.
IOTA provides several mounting accessories to enable suspended 

or surface mounting of the 

ILBDW

 that can be acquired by 

contacting Customer Service or your local Sales Representative.

The flex conduit should be wired into an available opening on the 

luminaire. The gasket (provided) should be installed between the 

PVC conduit and the luminaire opening.

The ILBDW must be oriented such that the arrow on the 

unit label faces up.

INSTALLATION INSTRUCTIONS

PVC CONDUIT

IPS

(”S” models)

GASKET (PROVIDED)

LUMINAIRE

OPENING

IPS

(”SLTEST” models)

LED DRIVER AND ARRAY COMPARTMENT

STEP 3 - 

INSTALLING THE IP67-RATED TEST SWITCH (IPS)

A.  The IPS must be installed in a suitable 

hole in the luminaire wall or wireway cover. 

Insert the IPS into the hole so that the LED 

test button/pilot light is located outside of 

the fixture or behind the lens and the gasket 

(provided) is located between the LED test 

button and fixture housing or lens. 

B.  Secure the IPS using the 

IPS nut.

C.  Connect and fully engage the IPS 

Connector to the IPS Socket. Ensure 

the IPS Connector is properly seated 

in the IPS Socket, then mark the IPS 

location on the switch box plate with the 

IPS Label and apply the Status Indicator 

Sticker. 

PVC CONDUIT

IPS

(”S” models)

GASKET (PROVIDED)

LUMINAIRE

OPENING

IPS

(”SLTEST” models)

LED DRIVER AND ARRAY COMPARTMENT

ILBDW

LUMINAIRE

HOUSING

IPS NUT

GASKET

(PROVIDED)

ILBDW

SPECIFICATIONS - 

Illustration 1

Model

ILBDW CP10

ILBDW CP15

ILBDW CP20

Output Voltage (Min - Max)

15-55 VDC

20-55 VDC

40-200 VDC

Minimum Operation

90 Minutes

90 Minutes

90 Minutes

Input Voltage (Min - Max)

120-277 VAC

120-277 VAC

120-277 VAC