Page 2
STEP 2 -
WIRING TO THE LED LOAD AND NORMAL DRIVER
Refer to the appropriate wiring diagram
to the right. Make sure all connections
are in accordance with NEC and
any other local requirements.
The
ILBDW is designed to interface
with compatible loads only.
See
Illustration 1
for output voltage ratings
per ILBDW model.
For “SLTEST” Models
(IPS test switch is secured to the ILBDW housing)
:
The IPS test switch is pre-installed by the factory. No additional connections
are needed.
For “S” Models
(IPS test switch is included in the PVC conduit): refer to the steps below for installing the IPS test switch in the luminaire.
ILBDW S AND SLTEST - CONNECTIONS TO NORMAL DRIVER AND LED LOAD
ILBDW-IPS-NORMAL-DRIVER-AND-LED-LOAD.EPS
AC (NORMAL)
DRIVER
LED
LOAD
WHITE/RED
WHITE
RED (+)
LED OUTPUT (+)
LED OUTPUT (-)
BLUE (-)
LED INPUT (-)
VIOLET/WHITE (+)
LED INPUT (+)
ILBDW
EMERGENCY DRIVER
PVC
CONDUIT
CAUTION: Before installing, make certain the IP67 Rated Test Switch (IPS) is disconnected (“S” models only) and A.C. power is off.
STEP 1 -
MOUNTING THE ILBDW
The ILBDW should be mounted nearby the fixture within suitable
reach of the PVC conduit.
IOTA provides several mounting accessories to enable suspended
or surface mounting of the
ILBDW
that can be acquired by
contacting Customer Service or your local Sales Representative.
The flex conduit should be wired into an available opening on the
luminaire. The gasket (provided) should be installed between the
PVC conduit and the luminaire opening.
The ILBDW must be oriented such that the arrow on the
unit label faces up.
INSTALLATION INSTRUCTIONS
PVC CONDUIT
IPS
(”S” models)
GASKET (PROVIDED)
LUMINAIRE
OPENING
IPS
(”SLTEST” models)
LED DRIVER AND ARRAY COMPARTMENT
STEP 3 -
INSTALLING THE IP67-RATED TEST SWITCH (IPS)
A. The IPS must be installed in a suitable
hole in the luminaire wall or wireway cover.
Insert the IPS into the hole so that the LED
test button/pilot light is located outside of
the fixture or behind the lens and the gasket
(provided) is located between the LED test
button and fixture housing or lens.
B. Secure the IPS using the
IPS nut.
C. Connect and fully engage the IPS
Connector to the IPS Socket. Ensure
the IPS Connector is properly seated
in the IPS Socket, then mark the IPS
location on the switch box plate with the
IPS Label and apply the Status Indicator
Sticker.
PVC CONDUIT
IPS
(”S” models)
GASKET (PROVIDED)
LUMINAIRE
OPENING
IPS
(”SLTEST” models)
LED DRIVER AND ARRAY COMPARTMENT
ILBDW
LUMINAIRE
HOUSING
IPS NUT
GASKET
(PROVIDED)
ILBDW
SPECIFICATIONS -
Illustration 1
Model
ILBDW CP10
ILBDW CP15
ILBDW CP20
Output Voltage (Min - Max)
15-55 VDC
20-55 VDC
40-200 VDC
Minimum Operation
90 Minutes
90 Minutes
90 Minutes
Input Voltage (Min - Max)
120-277 VAC
120-277 VAC
120-277 VAC