Page 2

  Use

 – For use only in complete equipment or final applications where the acceptability of the combination is deter-

mined by Underwriters Laboratories, Inc.

    These components have been judged on the basis of the required spacings in the Standard for Emergency Lighting 

and Power Equipment UL 924, Sec. 29, which covers the end use product for which the component was designed.

 

CONDITIONS OF ACCEPTABILITY

 1.  Installed in a suitable ultimate enclosure.
 2.  Used with marked electrical ratings.
 3.  Provide with proper spacing between live parts and enclosure and/or adjacent devices.
 4.  Factory wired only (terminations not suitable for field wiring).
 5.  Temperature tests may have to be repeated where battery temperature exceeds 55° C.
 6.  Mounted within the end-use product such that the battery is secured and the test switch operates properly 

when the end product is fully assembled.

 7.  End-use products employing one or more of these devices are to be marked in accordance with the Standad-

for Emergency Lighting and Power Equipment, UL 924.

INSTALLATION INSTRUCTIONS

CAUTION:   Before installing, make certain the A.C. power is off and the ILB-CP unit 
connector is disconnected.

1. FIXTURE 

 

The 

ILB-CP

 can be used with most LED loads that operate at 10-60 VDC. See the 

ILB Model Specification  

 Chart

 for output specifications of the unit being installed.

2.  MOUNTING THE ILB

 Mount  the 

ILB-CP

 in the driver/lamp compartment or enclosed wireway so the wire leads are not exposed, at least 

½

 

away from the driver. Mount the 

ILB-CP 

using the mounting holes provided. The insulating barrier should be 

mounted against the fixture wall. Then the main circuit board can be mounted leaving a space between the board 

and the mounting barrier. The circuit board should be placed so that no live parts are accessible during routine 

maintenance or relamping.

    The battery should be at least 

1

/

2

″ 

from the A.C. ballast and other heat sources. Since heat rises, try to mount the 

battery as low as possible. 

CAUTION 

– Connect the battery to the unit before applying A.C. power.

 

3. WIRING

    Refer to the wiring diagram on the back page for the appropriate wiring of the LED load and driver. Install in ac-

cordance with the National Electrical Code and local regulations. For additional wiring diagrams consult Cus-

tomer Service.

4.  INSTALLING THE THREADED BODY TEST SWITCH (TBTS)

    Select a convenient location on the side of the fixture so that the 

TBTS

 can be seen after installation. Allow for 

proper clearance and drill or punch a ½

 hole. Remove the nut from the 

TBTS

. Push the 

TBTS

 housing into the 

½

 hole and secure with the nut. Connect the LED wires from the unit to the 

TBTS

 (Red/Black or Red w/tag to 

Red, and White/Red to White). For proper operation, use only the accessory components provided with the unit

See Page 1 of the Instruction Manual.

ILB-CP05

ILB-CP07

ILB-CP10

5 WATTS

7 WATTS

10 WATTS

ILB MODEL SPECIFICATION CHART

OUTPUT POWER (CONSTANT)

ILB-CP12

12 WATTS

ENGINEERING CONSIDERATIONS

INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.