IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.
CAUTION
– Connect the battery to the unit before applying A.C. power.
2.
CAUTION
– To prevent electrical shock, do not mate unit connector until installation is complete and A.C. power is
supplied to the unit.
3.
CAUTION
– This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by disconnect-
ing the unit connector. In addition, the circuit board should be mounted so that no live parts are accessible during
routine maintenance.
4.
CAUTION
– The integral, high temperature Ni-Cad battery or components of this unit are not replaceable. Replace
the entire unit when necessary and recycle or dispose of properly.
5.
CAUTION
– Installation and servicing should be performed by
qualified personnel only
. De-energize before servicing.
6.
DO NOT USE OUTDOORS.
The
ILB-CP
is for use with grounded, UL Listed, indoor fixtures. Not for use in heated
air outlets or hazardous locations. The acceptability of the combination must be determined by Underwriters Labora-
tories. Refer to the Engineering Considerations section for proper installation.
7. The
ILB-CP
requires an unswitched A.C. power source of 120 to 277 volts AC, 50/60Hz.
8.
The
ILB-CP
and A.C. driver
must
be on the same branch circuit.
9. Do not mount near gas or electric heaters.
10. The
ILB-CP
should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
11. The
ILB-CP
will supply 10-60VDC output at the individual rated specification for 90 minutes. See individual units
for output specifications.
12. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void
warranty, and result in non-compliance with UL specifications.
13. Do not use this equipment for other than intended use.
14. Install in accordance with the National Electrical Code and local regulations.
15. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before
final installation.
SAVE THESE INSTRUCTIONS
ILB-CP
“L” OPEN BOARD DESIGN
EMERGENCY LIGHTING EQUIPMENT
FOR LED
INSTRUCTION MANUAL
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 • FAX (520) 741-2837
www.iotaengineering.com
CLASS 2 OUTPUT
Patented.
See iotaengineering.com/patents for more details