TYPICAL WIRING DIAGRAMS

For wiring diagrams of ballast/drivers not shown, consult our Customer Service.

Rev. 1700
68014-104

TYPICAL SEPARATELY DERIVED SYSTEM (SWITCHED NEUTRAL) APPLICATION

ETS-STEP_application_illustration

REV 020118

YELLOW (+) 

YELLOW/WHITE

ETS-STEP

 

EMERGENCY

CONTROL 

DEVICE

AC DRIVER
/ BALLAST

RED LED 
NORMAL POWER 
INDICATOR
(OPTIONAL)

EMERGENCY

POWER

(GENERATOR)

NORMAL
SUPPLY

G

N

÷

HOT

HOT

NEUTRAL

NEUTRAL

BLACK (120V)

RED

BROWN (L2)

ORANGE (277V)

BLK/YEL (120/277V)

BLK/ORG (120/277V)

NORMAL POWER SENSE.
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.

NORMAL

PANEL

UL 1008 DEVICE

EMERGENCY PANEL

TRANSFER SWITCH

CONTROL DEVICES

(WALL SWITCHES)

MONITOR

/ SENSE

NEUTRAL

WHITE

BLACK

BLACK

L1 L2

L1

L2

WHITE

HOT

HOT

NEUTRAL

BLUE (L1)

Note: This illustration shows a separately derived system (switched neutral). When the generator
is not a separately derived system, the neutral conductors are solidly interconnected.

TYPICAL FIXTURE WIRING

ETS-STEP_fixture_wiring

REV 020118

YELLOW (+) 

YELLOW/WHITE

ETS-STEP

 

EMERGENCY

CONTROL 

DEVICE

AC DRIVER
/ BALLAST

RED LED 
NORMAL POWER 
INDICATOR
(OPTIONAL)

÷

BLACK (120V)

RED

BROWN (L2)

ORANGE (277V)

BLK/YEL (120/277V)

BLK/ORG (120/277V)

NORMAL POWER SENSE.
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.

CONTROL DEVICES

(WALL SWITCHES)

MONITOR

/ SENSE

L1 L2

L1

L2

WHITE

BLUE (L1)

EMERGENCY PANEL

HOT

EMERGENCY PANEL

NEUTRAL

NORMAL PANEL HOT

(NORMAL SUPPLY SENSE)

WHITE

BLACK

BLACK

SEPARATELY DERIVED SYSTEM (SWITCHED NEUTRAL)

FIXTURE WIRING DETAIL

TYPICAL CIRCUIT DIAGRAM

Note: This illustration shows a separately derived system 
(switched neutral). When the generator is not a separately de-
rived system, the neutral conductors are solidly interconnected.

FIXTURE WIRING
DETAIL

Summary of Contents for ETS-STEP

Page 1: ...adily be subjected to tamper ing by unauthorized personnel 7 The ETS STEP is compatible with all A C magnetic and electronic ballasts and drivers 8 The ETS STEP is for use in step dimming applications and not designed for use with 0 10 volt dimming controls May be suitable for use in some 3 wire dimming applications Contact Customer Service for more information 9 The use of accessory equipment not...

Page 2: ...entire assembly back into the tube until the lens collar rests against the plastic tube The plastic tube should be adjusted so that the A C Indicator is within of the fixture lens The A C Indicator must be visible after installation Refer to Illustration 1 Strip Fixture Select a convenient location on the side of the fixture so the A C Indicator can be seen after installation Allow for proper clea...

Page 3: ...rcing the luminaire to operate at full lumen output All lamps in the fixture are illuminated at full light output for as long as auxiliary power is avail able When the A C power is restored the ETS STEP switches the system back to the Normal Mode See page 1 of the Instruction Manual TESTING MAINTENANCE The ETS STEP is a maintenance free unit however periodic inspection and testing is required NFPA...

Page 4: ...s illustration shows a separately derived system switched neutral When the generator is not a separately derived system the neutral conductors are solidly interconnected TYPICAL FIXTURE WIRING ETS STEP_fixture_wiring REV 020118 YELLOW YELLOW WHITE ETS STEP EMERGENCY CONTROL DEVICE AC DRIVER BALLAST RED LED NORMAL POWER INDICATOR OPTIONAL BLACK 120V RED BROWN L2 ORANGE 277V BLK YEL 120 277V BLK ORG...

Reviews: