background image

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

 1. 

CAUTION 

– This fixture provides more than one power supply output source. To reduce the risk of electrical 

shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit.

 2. 

CAUTION 

– This is a sealed unit. Replace the entire unit when necessary.

 3. 

DO NOT USE OUTDOORS.

 The 

ETS-STEP 

is for use with grounded, UL Listed, indoor fixtures. Not for use in 

heated air outlets or hazardous locations.

 4.  The 

ETS-STEP

 requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the 

unused A.C. lead.

  5.  Do not mount near gas or electric heaters.

 6.  The 

ETS-STEP

 should be mounted in locations and at heights where it will not readily be subjected to tamper-

ing by unauthorized personnel.

 7. The 

ETS-STEP

 is compatible with all A.C. magnetic and electronic ballasts and drivers.

  8.  The 

ETS-STEP 

is for use in step-dimming applications and not designed for use with 0-10 volt dimming 

controls.  May be suitable for use in some 3-wire dimming applications. Contact Customer Service for more 
information.

  9.  The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.

 10.  Do not use this equipment for other than intended use.

 11.  Install in accordance with the National Electrical Code and local regulations.

 12.  Installation and servicing should be performed by qualified personnel.

13.  Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before 

final installation.

 

SAVE THESE  INSTRUCTIONS

ETS-STEP

EMERGENCY LIGHTING

CONTROL DEVICE

FOR STEP DIMMING

SERIES ALCR for 3A CIRCUIT

INSTRUCTION MANUAL

P.O. BOX 11846  TUCSON, AZ 85734 

(520) 294-3292   •  FAX (520) 741-2837

www.iotaengineering.com

Summary of Contents for ETS-STEP

Page 1: ...adily be subjected to tamper ing by unauthorized personnel 7 The ETS STEP is compatible with all A C magnetic and electronic ballasts and drivers 8 The ETS STEP is for use in step dimming applications and not designed for use with 0 10 volt dimming controls May be suitable for use in some 3 wire dimming applications Contact Customer Service for more information 9 The use of accessory equipment not...

Page 2: ...entire assembly back into the tube until the lens collar rests against the plastic tube The plastic tube should be adjusted so that the A C Indicator is within of the fixture lens The A C Indicator must be visible after installation Refer to Illustration 1 Strip Fixture Select a convenient location on the side of the fixture so the A C Indicator can be seen after installation Allow for proper clea...

Page 3: ...rcing the luminaire to operate at full lumen output All lamps in the fixture are illuminated at full light output for as long as auxiliary power is avail able When the A C power is restored the ETS STEP switches the system back to the Normal Mode See page 1 of the Instruction Manual TESTING MAINTENANCE The ETS STEP is a maintenance free unit however periodic inspection and testing is required NFPA...

Page 4: ...s illustration shows a separately derived system switched neutral When the generator is not a separately derived system the neutral conductors are solidly interconnected TYPICAL FIXTURE WIRING ETS STEP_fixture_wiring REV 020118 YELLOW YELLOW WHITE ETS STEP EMERGENCY CONTROL DEVICE AC DRIVER BALLAST RED LED NORMAL POWER INDICATOR OPTIONAL BLACK 120V RED BROWN L2 ORANGE 277V BLK YEL 120 277V BLK ORG...