background image

 

 

User’s Manual 

Neutron3-B+ Remote Pulse Collector 

 

 

 

 

Copyright 2020 - ionSign 

www.ionsign.fi 

15.6.2020 

– v1.4 

1  General 

Neutron3-B+ is a battery operated remote pulse collector for pulsed 
utility meters, e.g. water or gas meters. Pulses are collected auton-
omously, stored locally and sent to the server as set up by the user. 

2  Indicator lights 

Battery life is managed by only powering up the led indicators; 

  when the battery is inserted (pulses are not indicated) 

  when entering the installation mode 

  when sending the daily data package 

Yellow led OFF 

Device not configured. See SETTINGS

 

Yellow led ON 

Device has settings and is in operation

 

Yellow led blinks 

Device has settings, communicates to server

 

Green led OFF 

Device is not in a GSM network 

Green led ON 

Device is in a GSM network 

Green led blinks 

Device has a poor GSM signal quality 

GSM led blinks twice

  Device is looking for a GSM network 

GSM led blinks

 

Device is in a GSM network 

Red led toggles 

Device recorded a pulse from a meter 

3  Installation mode 

The device receives SMS message commands immediately  when 
in  installation  mode.  The  installation  mode  is  entered  by  pressing 
the button inside the device, or by placing a magnet next to the but-
ton outside of the device enclosure. 

4  Commands 

The device is controlled with SMS messages sent to the SIM 

card’s 

number. The message is delivered only at the next scheduled data 
transmission,  unless  installation mode  is  activated.  Except  for the 
STATUS  command,  the  device  doesn’t  send  replies.  In  the  mes-
sages,  commands  and  parameters  are  separated  by  one  space 
character ( 

˽

 in examples). 

SETTINGS

˽<Device  identifier>˽<Server  address>˽<Server  port>˽ 

<APN>˽<Input 

count>˽<Transmission 

delay>˽<Server 

path>[˽<Step>] 
With the SETTINGS command all required parameters for collecting 
and sending of pulse data are given and logging starts. 

Device identifier

 is a unique device ID. Range: 1-1 000 000. 

Server  address 

is  the  server

’s  IP  address  or  a  domain  name 

server name. Maximum length 50 characters. 

Server port

 is the port number where the server application waits 

for transmissions. 

APN

 is the Access Point Name for the GPRS/3G connection. Your 

operator provides this. Maximum length 30 characters. 

Input count

 is the number of connected meters. Range: 1-3. 

Transmission  delay

  helps  to  avoid  a  large  number  of  devices 

clogging the server with simultaneous transmissions. Range is 0-
1000  minutes. With  value  zero  (0)  the  data  is  sent  immediately 
when 24 readings have been collected. 

Server path

 is the path in the server where data is saved. Maxi-

mum length 50 characters. 

Step

 defines the measurement cycle length, 15, 30 or 60 min. For 

legacy server interfaces, may be omitted, defaults to 60. 

STEP

˽

<Time>

 

The measurement cycle set using the SETTINGS command can be 
changed with the STEP command. The 

Time

 parameter defines the 

cycle length in minutes. Values 15, 30 or 60. 

STATUS 

The STATUS command has no parameters. The device replies to it 
with an SMS, including the following general information: 

  Device settings validity: [Yes | No] (If Yes, also device ID) 

  Data sending to server initialized: [Yes | No] 

  Most recent device IP connection initialized: [Yes | No] 

  Most recent TCP/IP connection to server: [Yes | No] 

  Most recent server reply to device: [No | Success | Error] 

  GSM operator name 

  GSM signal strength: [dBm value | Unknown] 

Signal  strength  -113  dBm  indicates  a  value  of  -113  dBm  or  less. 
Signal strength -51 dBm indicates a value of -51 dBm or greater. 

5  Leak Guard Configuration 

The device constantly monitors for leaks, using the configured leak 
limits. The leak alarm triggers immediately when observed, regard-
less of scheduled data transmission. Leak Guard is not activated by 
default, it

’s activated with the command: 

LEAKLIMITS

˽<

Channel

>[

˽<

Pulse constant

>] 

Channel 

is the measurement channel to be configured, 1, 2 or 3. 

Pulse constant 

of the meter, in pulses/litre. Zero value, 

”0” inac-

tivates the Leak Guard. If omitted, current settings are returned. 

Limits may be changed with the below command. Prior to change, 
it

’s  a  good  idea  to  query  the  current  settings  with  LEAKLIMITS˽ 

<

Channel

>. All parameters need to be given, also the unchanged. 

LEAKLIMITS

˽<

Channel

>

˽<

Pulse constant

>

˽<

Flow-1

>

˽<

Flow-2

>

˽ 

<

Flow-3

>

˽<

Flow-4

>

˽<

Span-1

>

˽<

Span-2

>

˽<

Span-3

>

˽<

Span-4

Flow-

1…4 

flow limit for leak guards 1-4. 

Span-

1…4

 minimum duration of this flow as pulses before alarm. 

6  Failure recovery 

For GSM network failures, the device has a built-in local buffer for 
keeping collected data stored for later transmission. The buffer ca-
pacity is 3 years for hourly data, 18 months for half-hourly data and 
9 months for quarterly data, for each channel. When the GSM net-
work resumes service, all buffered data is sent to the server without 
any need for user intervention. If the GSM signal strength is weak 
and the device often needs to buffer data, battery life will be shorter 
than expected. 

7  Neutron3-B+ technical specifications 

  Inputs: 3 inputs for pulses. 

  Replaceable battery.  

o

 One C cell Li battery: 3,6V 6Ah min 1500mA peak. Compatible 

types  e.g.  SAFT  LSH14,  ULTRALIFE  ER26500M  and  EVE 
ER26500M. Expected battery life 10 years. 

o

 Two C cell LR 14 alkaline 1,5V batteries. Expected battery life 

6 years. 

  Real-time clock. 

  Size: WxHxD 145x90x55 mm (flanged PC plastic enclosure). 

  Protection class: IP43. 

  Operating temperature: -25 °C...+55 °C. 

  RH: 5 % - 95 % non-condensing. 

  Data  communication:  Integrated  3G/GSM/GPRS  module.  Con-

forming the following directives and standards: 

-

 R&TTE Directive 1999/5/EC (Radio & Telecommunications Ter-

minal Equipment) 

-

 Low  Voltage  Directive  73/23/EEC,  Product  Safety  Directive 

89/336/EEC 

-

 GSM (Radio Spectrum): EN301 511, 3GPP 51.010-1 

-

 EMC  (Electromagnetic  Compatibility):  EN301  489-1,  EN301 

489-7 

-

 LVD (Low Voltage Directive): EN 60 950 

  Antenna: internal, SMA connector. 

8  Warranty 

ionSign grants a warranty of two (2) years for all delivered devices and software ser-
vices. The warranty starts on the date of the delivery and it covers material and man-
ufacturing defects. The warranty does not cover defects caused by improper use or 
installation nor does it cover defects caused by factors out of ionSign’s control. These 
would be for instance grid malfunction or service changes of network operators

’ ser-

vices. ionSign delivers a new device to replace the defected one, without cost. Alter-
natively, ionSign may repair the defected device. The defected device must be re-
turned to ionSign, if required, at ionSign’s cost. The warranty does not cover disman-
tling, installation, and introduction costs and the like. ionSign warrants that the pro-
vided software essentially manage with their designed tasks, at the time of delivery. 
All significant software defects are covered by the warranty. The defects will be re-
solved without unnecessary delay. The resolution may be an instruction to circum-
vent the defect. If the delivery includes third party products or services, these are only 
covered by the applicable warranty provided by that third party. Title to the delivered 
goods  transfers  to  the  client,  when  the invoiced  price is  paid in  full.  All immaterial 
rights related to devices and services remain the property of ionSign. If the service 
was a design assignment, the client assumes the right to use and further develop the 
assignment res

ults. ionSign is eligible to use the client’s name as a reference in its 

marketing. ionSign is not eligible to disclose the order details without prior consent. 
In case of a force majeure, preventing to act according to the purchase agreement, 
the affected party will start immediate negotiations to assess the effects of the obsta-
cle  on  the  scope  and  schedule  of  the  purchase  agreement.  ionSign  appropriately 
backs up client’s data residing on its servers. In spite of this, ionSign assumes no 
responsibility of possible damage due to loss of data. ionSign assumes no responsi-
bility of direct or indirect damage to property or people, nor work or travel expenses, 
caused by using its services or devices, unless due to gross negligence. ionSign’s 
financial liability is always limited to the value of the delivered goods and services, 
unless otherwise inflicted by the Finnish law.

 

Limit factory settings  Flow, l/h 

Span, pulses 

1. Seeping leak 

10 

2. Dripping leak 

10 

100 

3. Flowing leak 

200 

400 

4. Burst leak 

2000 

50 

ionSign Oy

 

P.O. Box 246 | Paananvahe 4 | FI-26100 
Rauma | Finland | t. +358 2 822 0097 
[email protected] | ionsign.fi | VAT FI21174499

 

 

 

 