English
To avoid damaging the coil, tighten the water pipe connectors on each header
using a counter-wrench.
When installing the unit, take care not to push the coils headers towards the
inside of the unit when tightening the connections.
Caution
7KHLQVWDOODWLRQDQGRSHUDWLQJFRQGLWLRQVUHTXLUHWKH0$1'$725<ʾWWLQJRIDYDOYH21WKHXQLW
OR/AND upstream in the hydraulic circuit. This is to prevent chilled water from circulating in the
appliance when the fan is not operational (condensation issue) or to prevent the simultaneous
circulation of chilled water and hot water in a 4-pipes exchanger.
Caution
4
3
2
1
4
3
2
1
10 SysCoil 2
9.2.1. WATER COIL HEADERS
Each water coil header has 1 pipe connection for water supply and water return.
Due to the coil design and small effect on capacity, there is no preferential water supply and water return on
fan coil units. However we recommend water supply on the lower header of the coil.
9.2.2. WATER CONNECTION OF CONTROL VALVES
The use of regulation valves (supplied as an accessory or by the client) is mandatory to ensure that the
appliance operates correctly.
Size
SC10
SC20
SC30
SC40
SC50
SC60
SC70
SC80
2 pipes
L
0.41
0.61
0.89
1.17
1.45
1.73
2.19
2.60
4 pipes
L
0.41
0.61
0.89
1.17
1.45
1.73
2.19
2.60
L
0.20
0.20
0.30
0.39
0.48
0.58
0.73
0.92
Size
SC10
SC20
SC30
SC40
SC50
SC60
SC70
SC80
Headers
G ½" G ½" G ½" G ½" G ½" G ½" G ½" G ½" G ½" G ½" G ½" G ½" G ¾" G ½" G ½" G ½"
Valve
G ½" G ½" G ½" G ½" G ½" G ½" G ½" G ½" G ½" G ½" G ½" G ½" G ¾" G ½" G ¾" G ½"
9.3. COIL WATER VOLUME
2-way on/off
valves
3-way on/off
valves