4.2.3 Circuit breaker
In order to ensure safe operation of the inverter and circuits, it is recommended to configure the
miniature circuit breaker or fuse of the corresponding specification on the DC input side, AC output
side, load side and battery input side of the inverter. Recommended requirements for circuit
breakers:
Inverter
model
PV side
AC and load side
Battery side
Recommended circuit breaker specifications
3kW
DC600V, C32A, 2P
AC250V, C20A, 2P
DC100V, C100A, 2P
5kW
DC600V, C32A, 2P
AC250V, C25A, 2P
DC100V, C150A, 2P
4.3 Mechanical installation
Wall mounting procedures
(1)
Place the positioning paper card in the appropriate position on the wall, and use the electric
drill (Φ8 drill bit) to make 6 mounting holes on the wall, the depth of the holes is 70-90mm, then
install the hanging plate.