HT33 Series User Manual
Chapter 2 Installation Guidance
2.1 Introduction
This
chapter introduces UPS installation, it provide normal installation steps and ideas. Please
installation engineers operate according to difference for each place,
Warning-Installation can only be done by authorized engineers
1. Do not apply electrical power to the UPS equipment before the approval of commissioning
engineer.
2. The UPS should be installed by a qualified engineer in accordance with the information contained
in this chapter.
Note: 3-Phase 4-Wire Input Power is required
The standard UPS can be connected to TN, TT and IT AC distribution system (IEC60364-3) of
3-phase 5-wire
WARNING: battery hazards
SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED
WITH THIS EQUIPMENT. When connecting the battery, the battery terminal voltage will exceed
400Vdc and is potentially lethal.
Eye protection should be worn to prevent injury from accidental electrical arcs.
Remove rings, watches and all metal objects.
Only use tools with insulated handles.
Wear rubber gloves.
If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a
container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin, the affected area should be washed immediately
with water.
2.2.1 Distribution Room
The UPS is designed for indoor installation, which shall be located in a clean environment with
adequate ventilation to keep the environmental temperature within the required specification. The UPS
uses forced convection cooling by internal fans. Cooling air enters the module through ventilation grills
located at the front part of the cabinet and exhausted through grills located in the rear part of the cabinet.
Please do not block the ventilation holes.
If necessary, a system of extractor fans should be installed to aid cooling-air flow. An air filter should
be used when the UPS is to operate in a dirty environment and should be regularly cleaned to maintain
airflow.
Note: The UPS should be installed on a cement surface or other surface that is not
combustible.