HT33 Series User Manual
Chapter 8 Product Specification
This chapter describes the product specification of UPS
8.1 Applicable Standards
UPS design meets the European and national standards given in Table 8-1.
Table 8-1 Compliance with European and International Standards
Item
Normative reference
General safety requirements for UPS
used in operator access areas
EN50091-1-1/IEC62040-1-1/AS 62040-1:2009
Electromagnetic compatibility (EMC)
requirements for UPS
EN50091-2/IEC62040-2/AS 62040-2
Method of specifying the performance
and test requirements of UPS
EN50091-3/IEC62040-3/AS 62040-3(VFI SS 111)
Note: The above mentioned product standards incorporate relevant compliance clauses with generic
IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity
(IEC/EN/ AS61000 series) and construction (IEC/EN/AS60146 series and 60950)
8.2 Environmental Characteristics
Table 8-2 Environmental Properties
Items
Unit
Requirements
Acoustic noise level at 1 meter
dB
55.0
Altitude of Operation
m
≤1000m above sea level, derate power by 1% per
100m between 1000m and 2000m
Relative Humidity
%
RH
0 to 95% non condensing
Operating Temperature
℃
0 to 40 deg , Battery life is halved for every 10°C
increase above 20°C
UPS Storage-Transport Temperature
℃
-
20-70
Recommended Battery Storage
Temperature
℃
-
20-30 (20°C for optimum battery storage)
8.3 Mechanical Characteristics
Table 8-3 Mechanical Properties
Cabinet
Specification
Unit
HT33010, HT33015, HT33020,
HT33030
Mechanical
Dimension,
W×D×H
mm
540*690*1100
(with built-in battery)
280*730*668
320*781*788
Weight
kg
68
(with built-in battery)
80
(with built-in battery)
46
60
Color
N/A
Black
Protection Level,
IEC(60529)
N/A
IP20