Goodrive350-19 series VFD for crane
Commissioning guidelines
-48-
Note: The macro parameter table does not contain some parameters that are factory default
parameters.
5.3.4 Points for attention
1. If you only want to check whether the VFD runs properly, set P90.00=0 (Common mode).
2. If you perform empty-load commissioning, set P90.00 to 3 (Horizontal moving application macro),
set P11.08 to 0x000 to disable underload protection, and set P90.12 and P90.13 to 0 to prevent
the torque verification fault reporting caused by empty load.
3. During onsite commissioning, if the VFD terminal signal upward/downward running command is
inconsistent with the hook lifting/lowering, swap any two phase wires of VFD output terminals U,
V, and W.
4. This macro can meet the requirements of most horizontal moving application cases, and the
performance parameters have been optimized and do not need to be adjusted in most cases. If
an exception occurs, see the function parameter chapter for adjustment or contact the technical
support.
5.4 Tower crane slewing with vortex
5.4.1 Wiring
Braking resistor
VFD
RO1A
RO1C
RO1B
HDO
CME
VFD fault
(+)
PB
RO2A
RO2C
RO2B
COM
M
3~
M
3~
Y1
CME
Zero-speed
running
T
S
R
T
S
R
W
V
U
S1
S2
S3
S4
FWD run
REV run
COM
+24V
PW
+24V
S5
S6
Coast to stop (NC)
S7
COM
Fault reset
EC-IO-502-00
PW
+24V
Multi-step speed giving terminal 1
IO extension card
Multi-step speed giving terminal 2
Multi-step speed giving terminal 3
Figure 5-4 Wiring for tower crane slewing
Note: If the wiring is performed according to Figure 5-4, most VFD parameters need no adjustment. If