Goodrive350-19 series VFD for crane
Commissioning guidelines
-47-
5.3.2 Commissioning procedure
1. Check the wiring and ensure the wiring is proper.
2. Set P00.18=1 to restore to default settings.
3. Set motor nameplate parameters in P02.
4. Set P90.00=3 to select the horizontal moving application macro.
5. Perform low-speed trial run.
5.3.3 Macro parameters (P90.00=3)
Function code
Name
Setting
Remarks
P00.01
Channel of running
commands
1
Terminal
P00.03
Max. output frequency
100.00Hz
P00.04
Upper limit of running
frequency
60.00Hz
P00.06
Setting channel of A
frequency command
6
Multi-step speed running
P00.11
ACC time 1
5.0s
P00.12
DEC time 1
4.0s
P01.01
Starting frequency of
direct start
2.00Hz
P01.15
Stop speed
1.00 Hz
P05.03
Function of S3
0
No function
P05.04
Function of S4
7
Fault reset
P06.03
RO1 output
5
VFD in fault
P06.04
RO2 output
1
Running
P10.04
Multi-step speed 1
8.0%
Corresponding to the max. frequency
P10.06
Multi-step speed 2
18.0%
Corresponding to the max. frequency
P10.08
Multi-step speed 3
32.0%
Corresponding to the max. frequency
P10.10
Multi-step speed 4
50.0%
Corresponding to the max. frequency
P11.05
Current limit mode
0x11
Enable software and hardware
current limit.
P11.26
Enabling special functions
1
P25.01
Function of S5
16
Multi-step speed 1
P25.02
Function of S6
17
Multi-step speed 2
P25.03
Function of S7
18
Multi-step speed 3
P25.04
Function of S8
6
Coast to stop
P25.10
Expansion card input
terminal polarity
0x08
Terminal polarity