Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-157-
Function
code
Name
Description
Default
value
Modify
P06.05
Output terminal
polarity selection
This function code is used to set the polarity of
output terminals.
When the bit is set to 0, input terminal polarity is
positive;
When the bit is set to 1 input terminal polarity is
negative.
BIT3
BIT2
BIT1
BIT0
RO2
RO1
HDO
Y
Setting range: 0x00
–0x0F
0x00
○
P06.06
Y switch-on
delay
This function code defines the corresponding
delay of the level variation from switch-on to
switch-off.
Y electric level
Y valid
Invalid
Switch on
delay
invalid
Valid
Switch off
delay
Setting range: 0.000
–50.000s
Note:
are valid only when
=1.
0.000s
○
P06.07
Y switch-off
delay
0.000s
○
P06.08
HDO switch-on
delay
0.000s
○
P06.09
HDO switch-off
delay
0.000s
○
P06.10
Relay RO1
switch-on delay
0.000s
○
P06.11
Relay RO1
switch-off delay
0.000s
○
P06.12
Relay RO2
switch-on delay
0.000s
○
P06.13
Relay RO2
switch-off delay
0.000s
○
P06.14
AO1 output
selection
0: Running frequency (0
–Max. output frequency)
1: Set frequency (0
–Max. output frequency)
2: Ramp reference frequency (0
–Max. output
frequency)
3: Rotational speed (0
–Speed corresponding to
max. output frequency)
4: Output current (0
–Twice the VFD rated
current)
5: Output current (0
–Twice the motor rated
current)
6: Output voltage (0
–1.5 times the VFD rated
voltage)
7: Output power (0
–Twice the motor rated
power)
8: Set torque (0
–Twice the motor rated current)
9: Output torque (Absolute value, 0
–+/- Twice
the motor rated torque)
10: AI1 input (0
–10V/0–20mA)
11: AI2 input (0
–10V)
12: AI3 input (0
–10V/0–20mA)
13: HDIA input(0.00
–50.00kHz)
14: Value 1 set through Modbus/Modbus TCP
0
○
P06.15
Reserved
0
○
P06.16
HDO high-speed
pulse output
0
○