Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-84-
AI1
P05.24
P05.25
P05.26
P05.27
P05.45
P05.46
P05.47
P05.48
P05.28
P05.49
P17.19
AI2
P05.29
P05.30
P05.31
P05.32
P05.33
P05.34
P05.35
P05.36
P05.37
P17.20
AI1 input voltage
AI2 input voltage
AI1/AI2/
HDI
Analog input curve setting
Analog input filter
Related parameter list:
Function
code
Name
Description
Default
P05.24
AI1 lower limit
0.00V
–P05.26
0.00V
P05.25
Corresponding setting of AI1 lower
limit
-300.0%
–300.0%
0.0%
P05.26
AI1 upper limit
P05.24
–10.00V
10.00V
P05.27
Corresponding setting of AI1 upper
limit
-300.0%
–300.0%
100.0%
P05.28
AI1 input filter time
0.000s
–10.000s
0.100s
P05.29
AI2 lower limit
-10.00V
–P05.31
-10.00V
P05.30
Corresponding setting of AI2 lower
limit
-300.0%
–300.0%
-100.0%
P05.31
AI2 middle value 1
P05.29
–P05.33
0.00V
P05.32
Corresponding setting of AI2 middle
value 1
-300.0%
–300.0%
0.0%
P05.33
AI2 middle value 2
P05.31
–P05.35
0.00V
P05.34
Corresponding setting of AI2 middle
value 2
-300.0%
–300.0%
0.0%
P05.35
AI2 upper limit
P05.33
–10.00V
10.00V
P05.36
Corresponding setting of AI2 upper
limit
-300.0%
–300.0%
100.0%
P05.37
AI2 input filter time
0.000s
–10.000s
0.100s
P05.50
AI1 input signal type
0
–1
0: Voltage
1: Current
0
5.6.10 Analog output
The inverter unit carries one analog output terminal, of which the setting range is 0(2)
–10V/0(4)–20mA. Analog output
can be configured as voltage or current signals through setting P06.32. Analog output signals can be filtered separately,
and the proportional relation can be adjusted by setting the max. value, min. value, and the percentage of their
corresponding output. Analog output signal can output motor speed, output frequency, output current, motor torque and
motor power at a certain proportion.