Goodrive600 series high-performance multifunction VFD
Function parameter list
-253-
Function
code
Name
Description
Default Modify
considered as valid during power-on, the inverter
unit does not run and it keeps the protection
state until the running command is canceled and
enabled again.
1: The terminal running command is valid at
power-on. If the running command is considered
as valid during power-on, the inverter unit is
started automatically after the initialization.
Note: Exercise caution before using this
function. Otherwise, serious result may
follow.
P01.19
Action selected when
running frequency less
than frequency lower
limit (valid when
frequency lower limit
greater than 0)
The function code determines the running state
of the inverter unit when the set frequency is
lower than the lower-limit one.
0: Run at the frequency lower limit
1: Stop
2: Sleep
The inverter unit coasts to stop when the set
frequency is lower than the lower-limit one. If the
set frequency exceeds the lower limit one again
and it lasts for the time set by P01.20, the
inverter unit resumes the running state
automatically.
0
◎
P01.20
Wake-up-from-sleep
delay
Used to set the wake-up-from-sleep delay time.
When the running frequency of the inverter unit
is lower than the lower limit, the inverter unit
becomes standby.
When the set frequency exceeds the lower limit
once again and it lasts for the time set by
P01.20, the inverter unit runs automatically.
Sleep
Run
Set frequency curve:
Running frequency curve:
t1 < P01.20, the VFD does not run
t0=P01.34, sleep delay
Run
t2
t1
t0
Frequency lower
limit f0
Frequency f
Time t
Coast to
stop
t1+t2
≥
P01.20, the VFD runs
Setting range: 0.0
–3600.0s (Valid only when
0.0s
○
P01.21
Power-off restart
selection
Used to indicate whether the inverter unit
automatically runs after re-power on.
0: Disable
1: Enable. If the restart condition is met, the
inverter unit will run automatically after waiting
the time defined by P01.22.
0
○