PAGE 8
INVICTA
ONSEN INSTALLATION AND USER MANUAL
3.3 Protecting the floor
• Any combustible floor beneath a fireplace must have a floor protector that extends minimum 300mm at the front.
• If installed directly on combustible material, the floor protector must be made of a minimum 6mm thick cement sheet.
Non-combustible finishes can be applied to the floor protector (tiles, steel sheet, light concrete, etc).
• If the combustible floor is installed on concrete, you can replace the combustible material with non-combustible
material laid directly onto the concrete.
200mm
300mm
Combustible floor
(eg: Timber)
Floor protector
200mm
825mm
705mm
Joist
Insulative board (8mm)
+ non combustible finish
Non combustible finish
(eg.tiles)
Concrete
Combustible
floor (eg. timber)
Joist
Insulative board (8mm)
+ non combustible finish
Combustible
floor (eg. timber)
Combustible
floor (eg. timber)
FLOOR PROTECTOR LAID ON TIMBER FLOOR
3. INSTALLATION
(CONTINUED)
200mm
300mm
Combustible floor
(eg: Timber)
Floor protector
200mm
825mm
705mm
Joist
Insulative board (8mm)
+ non combustible finish
Non combustible finish
(eg.tiles)
Concrete
Combustible
floor (eg. timber)
Joist
Insulative board (8mm)
+ non combustible finish
Combustible
floor (eg. timber)
Combustible
floor (eg. timber)
FLOOR PROTECTOR LAID ON JOIST
INVICTA
ELTON INSTALLATION AND USER MANUAL