Optidrive VTC – User Guide
www.invertek.co.uk
17
6.2.
Parameter Group 2 - Extended parameters
Par.
Description
Range
Units
Default
Explanation
P2-01
Digital input function
select
0 to 23
-
0
Defines the function of the digital inputs
depending on the control mode setting in P-12.
See section 7 Analog and Digital Input
Configurations for more information.
P2-02
Preset Speed 2
-P1-01 to P1-01
Hz
0.0
Sets jog / preset speed 2
P2-03
Preset Speed 3
-P1-01 to P1-01
Hz
0.0
Sets jog / preset speed 3
P2-04
Preset Speed 4
-P1-01 to P1-01
Hz
0.0
Sets jog / preset speed 4
P2-05
Preset Speed 5
-P1-01 to P1-01
Hz
0.0
Sets jog /preset speed 5
P2-06
Preset Speed 6
-P1-01 to P1-01
Hz
0.0
Sets jog / preset speed 6
P2-07
Preset speed 7
-P1-01 to P1-01
Hz
0.0
Sets jog / preset speed 7
P2-08
Preset speed 8
-P1-01 to P1-01
Hz
0.0
Sets jog / preset speed 8
P2-09
Skip frequency
P1-02 to P1-01
Hz
0.0
Centre point of skip frequency band set up in
conjunction with P2-10
P2-10
Skip frequency band
0 to P1-01
Hz
0.0
Width of skip frequency band centred on
frequency set in P2-09
P2-11
Analog output /
Digital Output 1
Function select
Digital output mode
0 : Drive enabled
1 : Drive healthy
2 : Motor at target speed
3 : Motor Speed > 0
4 : Motor speed >= limit
5 : Motor current >= limit
6 : 2
nd
Analog Input >= limit
Analog Output Mode
7 : Motor speed
8 : Motor Current
9 : Motor power
7
Digital Output Mode. Logic 1 = +24V DC
0 : Logic 1 when the drive is enabled (Running)
1: Logic 1 When no Fault condition exists on the
drive
2 : Logic 1 when the motor speed matches the
setpoint speed
3 : Logic 1 when the motor runs above zero
speed
Options 4 to 6 : the Digital output is enabled
using the level set in P2-12h and P2-12L
Analog Output Mode
7 : Motor Speed, 0 to 10V = 0 to P-01
8 : Motor Current, 0 to 10V = 0 to 200% of P1-
08
9 : Motor power, 0 to 10V = 0 to 150% of drive
rated power
10 :
P2-12h
Digital Output Control
High Limit
0.0 to 200.0
%
100.0
With P2-11 = 4 to 6, Digital Output 1 is set to
Logic 1 (+24V DC) when the value set in P2-12h
is exceeded, and returns to Logic 0 (0V) when
the selected value reduces below the limit set
in P2-12L
P2-12L
Digital Output Control
Low Limit
0.0 to P2-12h
%
100.0
P2-13
User Relay Output
Function Select
0 : Drive enabled
1 : Drive healthy
2 : Motor at target speed
3 : Motor Speed >0
4 : Motor speed >= limit
5 : Motor current >= limit
6 : 2
nd
Analog Input >= limit
1
Selects the function assigned to the relay
output.
0 : Logic 1 when the drive is enabled (Running)
1 : Logic 1 When no Fault condition exists on
the drive
2 : Logic 1 when the motor speed matches the
setpoint speed
3 : Logic 1 when the motor runs above zero
speed
Options 4 to 6 : the Digital output is enabled
using the level set in P2-14h and P2-14L
P2-14h
Relay Output Control
High Limit
0.0 to 200.0
%
100.0
With P2-13 = 4 to 6, the User Relay Output is
set to Logic 1 (+24V DC) when the value set in
P2-14h is exceeded, and returns to Logic 0 (0V)
when the selected value reduces below the
limit set in P2-12L
P2-14L
Relay Output Control
Low Limit
0.0 to P2-14h
%
100.0
P2-15
Relay Output Mode
0 : Normally Open
1 : Normally Closed
-
0
Inverts the operating status of the User Relay
0 : Logic 1 = Relay Contacts Closed
1 : Logic 1 = Relay Contacts Open
The drive must be powered for the contacts to
close
P2-16
Standby Mode Wake Up
Speed
0.0 to 100.0
%
0.0
Drive will wake from Standby Mode if the
setpoint exceeds this value