Managing the module using MODBUS TCP
MODBUS TCP protocol is listening on port 502.
The module supports following functions of MODBUS protocol:
- 0x01 Read Coils,
- 0x03 Read Holding Register,
- 0x05 Write Single Coil,
- 0x06 Write Single Register,
- 0x0F Write Multiple Coils,
- 0x10 Write Multiple Registers.
The registers description is shown in tables below.
MODBUS TCP - Coils
Register
Name
Mode:
R-read
W-write
Description
1000
On1
R
Over Temperature
1002
SensError
R
Sensor error (0-ok, 1-error)
MODBUS TCP - Holding Registers
Register
Name
Mode:
R- read
W-write
Description
4000
ThermostatL
R/W
Thermostat low setting
4001
ThermostatH
R/W
Thermostat high setting
4002
Alarm mode
R/W
1-
OFF
(disabled)
2-
Lower
(lower than)
3-
Higher
(higher than)
4-
Lower & Higher
(lower and higher)
4004
Temperature x10
R
Temperature x 10 (ie. 10,5st.C to 105)
4005
Temperature Int
R
Integral part of temperature
4006
Temperature Frac
R
Decimal part of temperature
4007
MAC 0
R
MAC Address
4008
MAC 1
R
MAC Address
4009
MAC 2
R
MAC Address
4010
MAC 3
R
MAC Address
4011
MAC 4
R
MAC Address
4012
MAC 5
R
MAC Address
4013
StoreConfig
W
Entering 144 will save to configuration to
EEPROM
User manuald NANO TEMP