Maintenance 6
Air purging with vacuum pump
/TJUUX[TOZ
2OW[OJYOJK
-GYYOJK
:]U]G_\GR\K
:NXKK]G_\GR\K
5[ZJUUX[TOZ
)RUYK
)RUYK
3GTOLURJ\GR\K
36G
6XKYY[XK
MG[MK
.GTJRK2U
.GTJRK.O
)NGXMKNUYK
)NGXMKNUYK
<GI[[S
V[SV
<GI[[S
V[SV
)USVU[TJSKZKX
2U
.O
Procedure:
1.
Tighten the flare nuts of the indoor and outdoor
units, and confirm that both the 2- and 3-way valves
are closed.
2.
Connect the charge hose with the push pin of Handle
Lo to the gas service port of the 3-way valve.
3.
Connect another charge hose to the vacuum pump.
4.
Fully open the Handle Lo manifold valve.
5.
Using the vacuum pump, evacuate the system for 30
minutes.
a.
Check whether the compound meter indicates
-0.1 MPa (14.5 Psi).
• If the meter does not indicate -0.1 MPa (14.5
Psi) after 30 minutes, continue evacuating for
an additional 20 minutes.
• If the pressure does not achieve -0.1 MPa (14.5
Psi) after 50 minutes, check for leakage.
• If the pressure successfully reaches -0.1 MPa
(14.5 Psi), fully close the Handle Lo valve, then
cease vacuum pump operations.
b.
Wait for 5 minutes then check whether the gauge
needle moves after turning off the vacuum pump.
If the gauge needle moves backward, check
wether there is gas leakage.
6.
Loosen the flare nut of the 3-way valve for 6 or 7
seconds and then tighten the flare nut again.
a.
Confirm the pressure display in the pressure
indicator is slightly higher than the atmospheric
pressure.
b.
Remove the charge hose from the 3-way valve.
7.
Fully open the 2- and 3-way valves and tighten the
cap of the 2- and 3-way valves.
Summary of Contents for U6MRS32-18
Page 1: ...SERVICE MANUAL ENGLISH AIR CONDITIONING SYSTEMS LCAC...
Page 4: ......
Page 5: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Page 11: ...Contents 1 Model Reference 2 2 External Appearance 3 Model Reference...
Page 14: ...Model Reference 4 2 2 Outdoor Unit Outdoor Unit...
Page 18: ...IDU Compact Cassette 4 2 Dimensional Drawings...
Page 20: ...IDU Compact Cassette 6 4 Service Place...
Page 49: ...IDU A6 Duct 8 6 Fan Performance 18K...
Page 50: ...IDU A6 Duct 9 Constant air volume...
Page 68: ...IDU Floor Ceiling 5 4 Service Place 35mm 1 38in 1m 3 28ft 35mm 1 38in 35mm 1 38ch...
Page 93: ...Outdoor Unit 3 Panel Plate B30...
Page 94: ...Outdoor Unit 4 Panel Plate BA30...
Page 95: ...Outdoor Unit 5 Panel Plate CA30...
Page 96: ...Outdoor Unit 6 Panel Plate D30...
Page 97: ...Outdoor Unit 7 Panel Plate E30...
Page 98: ...Outdoor Unit 8 Panel Plate 590...
Page 99: ...Outdoor Unit 9 2 Service Place...
Page 110: ...Wiring Diagrams Outdoor unit wiring diagram 16022000022493...
Page 111: ...Outdoor unit printed circuit board diagram 17122000002718...
Page 280: ...AIR CONDITIONING SYSTEMS LCAC Scan here to download the latest version of this manual...