Oil traps
CAUTION
•
If the indoor unit is installed higher than the
outdoor unit:
An oil trap should be installed every 10m
(32.8ft) of vertical suction line riser.
(See Fig. 7.2)
-If oil flows back into the outdoor unit’s
compressor, this might cause liquid
compression or deterioration of oil return.
Oil traps in the rising gas piping can prevent
this.
CAUTION
Fig. 7.2
The indoor unit is installed higher than the
outdoor unit
If the outdoor unit is installed higher than the
indoor unit:
-It is recommended that vertical suction risers
not be upsized. Proper oil return to the
compressor should be maintained with suction
gas velocity. If velocities drop below7.62m/s
(1500fpm (feet per minute)), oil return will be
decreased. An oil trap should be installed every
6m(20ft) of vertical suction line riser.
(See Fig. 7.3)
Fig. 7.3
The outdoor unit is installed higher than the
indoor unit
Summary of Contents for U4MRS-12B
Page 31: ...Page 31...
Page 32: ...2 Indoor Unit Installation 07 1 04 08 09 13 14 14 2 05 3 07 6 15 4 07 5 12...
Page 33: ...3 07 MC MC L N 18 20 27 28 22 23 o 25 7 18 9 27 10 29 8 20...
Page 35: ...5 2 1 2 3 4 12 5...
Page 36: ...6 L N 1 2 3 4 5 MC MC 6 7 3 9 27 29 22 19 15 17...
Page 37: ...7 4 4 1 1 9 000btu h 18 000btu h 1m 3 2 1m 3 2...
Page 41: ...11 125mm 4 92 160mm 6 3 18 60 4 1 5 6 1 2 3 1 2 3 2 3 4 11 4 12 4 15 4 16 4 13...
Page 42: ...12 5 1 2 M10 5 1 5 2 1 1 60cm 23 6 5 1 5 2 5 3...
Page 48: ...18 7 2 7 3 10 32 8 7 2 7 62m s 1500 fpm 6m 20ft 7 3...
Page 53: ...23 7 10 7 11 90 3 10cm 3 9 6 7 8 9...
Page 54: ...24 CONFIRM 3 6 ON on 4 5 1 2 FAN ONLY 2 o 3 FAN ONLY H L 4 COPY AF booster HRV 3...
Page 59: ...29 1 2 3 COOL 4 d 5 6 2 000ml COOL 10...
Page 60: ...30...
Page 61: ...31...
Page 91: ...Pagina 31...