49
11.1 Indoor Unit Error Display
Operation
lamp
Timer
lamp
Display LED STATUS
☆
1 time
X
E0
Indoor unit EEPROM parameter error
☆
2 times
X
E1
Indoor / outdoor units communication error
☆
4 times
X
E3
Indoor fan speed has been out of control
☆
5 times
X
E4
Indoor room temperature sensor T1 open circuit
or short circuit
☆
6 times
X
E5
Evaporator coil temperature sensor T2 open
circuit or short circuit
☆
9 times
X
E7
Indoor PCB /Display board communication error
☆
7 times
X
EC
Refrigerant leakage detection
☆
1 times
O
F0
Overload current protection
☆
2 times
O
F1
Outdoor ambient temperature sensor T4 open
circuit or short circuit
☆
3 times
O
F2
Condenser coil temperature sensor T3 open
circuit or short circuit
☆
4 times
O
F3
Compressor discharge temperature sensor T5
open circuit or short circuit
☆
5 times
O
F4
Outdoor unit EEPROM parameter error
☆
6 times
O
F5
Outdoor fan speed has been out of control
☆
1 times
☆
P0
IPM malfunction or IGBT over-strong current
protection
☆
2 times
☆
P1
Over voltage or over low voltage protection
☆
3 times
☆
P2
High temperature protection of IPM module
☆
5 times
☆
P4
Inverter compressor drive error
O
(
light
)
X
(
off
)
☆(
flash
)
Summary of Contents for P8MVI32-09WiFi
Page 2: ......
Page 14: ...12 For P8MVI32 09WiFi For P8MVI32 09WiFi P8MVO32 09 P8MVI32 12WiFi P8MVO32 12...
Page 15: ...13 For P8MVI32 18WiFi P8MVO32 18 For P8MVI32 24WiFi P8MVO32 24...
Page 19: ...17 For P8MVO32 24...
Page 35: ...33 8 2 Outdoor Unit P8MVO32 09 P8MVO32 12 P8MVO32 18 P8MVO32 24...
Page 70: ...68...
Page 71: ......