Connections 

 

________________________________________________________________________________________ 

Notes: 
 

1. 

Must use NEC Class 2 or Limited Power Source (LPS) and SELV

 

rated power supply. 

If using DC power supply: 

 

Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted (9 to 30 Vdc). 
The power supply can be connected to earth but only through the negative terminal, never through the positive terminal. 

 

If using AC power supply: 

 

Make  sure  the  voltage  applied  is  of  the  value  admitted  (24  Vac).  Do  not  connect  any  of  the  terminals  of  the  AC  power 
supply to earth, and make sure the same power supply is not supplying any other device. 

 

2. 

Modbus  connection.  Only  one  Modbus  connection  type  can  be  used  simultaneously,  Modbus  TCP,  Modbus  RTU  EIA485,  or  Modbus  RTU 
EIA232, this must be configured within LinkBoxMB software. 

 

 

Modbus TCP: Connect the cable coming from the Modbus TCP master device to the connector ETH of IntesisBox, use a crossover 
Ethernet CAT5 cable if connecting directly to the Modbus TCP master device, or a straight Ethernet CAT5 cable if connecting to a 
switch or hub of the LAN of the building. If connecting using the LAN of the building contact the network administrator and make 
sure that TCP/IP traffic and the TCP port used (502 by default) are allowed through all the LAN path. 

 

Modbus  RTU  EIA485:  Connect  the  EIA485  bus  to  the  connector  Modbus  RTU  EIA485  of  IntesisBox.  Respect  the  polarity. 
Remember  the  characteristics  of  the  standard  EIA485  bus:  maximum  distance  of  1200  meters,  maximum  32  device  connected, 
and a 120 ohms terminator resistor in each end of the bus. IntesisBox comes with an internal bus biasing circuit which incorporates 
internal bus terminator resistor, and thus if you connect IntesisBox in one end of the bus then it is not necessary to install additional 
120 ohms resistor in that end. 

 

Modbus RTU EIA232: Connect the serial EIA232 cable coming from the Modbus RTU master device to the Modbus RTU EIA232 
connector of IntesisBox, this is a male DB9 connector (DTE) in which only lines TX, RX and GND are used, see pinout details in 
the user's manual. Respect the maximum distance of 15 meters for this EIA232 line. 

 

3. 

LG  AC  system’s  connection  through  (PMNFP14A0,  PMNFP14A1  or  PHNFP14A0)  EIA485  interface  board  or  Outdoor  Unit  PI485 
connection.  Connect  the  EIA485  bus  of  LG  boards  to  the  connector  LG  PI485  of  IntesisBox.  Respect  the  polarity.  Remember  the 
characteristics  of  the  standard  EIA485  bus:  maximum  bus  distance  of  1200  meters,  maximum  32  devices  in  the  bus,  and  a 
termination resistor of 120 ohms in each end of the bus. IntesisBox incorporates and internal circuit for bus biasing with termination 
resistor incorporated, so if IntesisBox is installed in one of the ends of the bus it is not necessary to connect an additional termination 
resistor in that end. 

 
4. 

Use the software LinkBoxMB to configure IntesisBox. Consult the user's manual for details. 

 

Modbus RTU 

master EIA232 

See Note 2 

 

Modbus RTU 

master EIA485 

See Note 2 

 

Console. 
Standard cable 1.8 m. 
DB9 female - DB9 male. 
Supplied with IntesisBox. 

LinkBoxMB 

Only for configuration 
See Note 4

 

To Power supply 

See Note 1 

 

Modbus TCP 
master 

See Note 2 

PC Console 

 -   + 

 

Ethernet 
Modbus TCP 

 

+   - 

IntesisBox

® 

www.intesisbox.com

 

 

Ethernet 
RJ45

 

 

 

EIA232 

 

EIA485 

 

-  + 

 

Modbus RTU 

 

EIA232 

EIA485 

To LG Interface 
EIA485 

See Note 3 
 

CMN  24Vac 
  
9 - 30Vdc  
Max.125 mA 
24Vac 
Max.127mA 

50-60Hz 

LG PI485 

 