background image

  

2 / 4

 

This information is subject to change without prior notice

 

email: 

[email protected]

  

web: 

www.intesisbox.com 

 

phone: +34 938047134

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 

 

 

Enclosure 

Plastic, type PC (UL 94 V-0) 
Net dimensions (d

x

w

x

h): 90x88x56 mm  

Recommended space for installation (d

x

w

x

h): 130x100x100mm 

Color: Light Grey. RAL 7035 

 

Battery 

Size: Coin 20mm x 3.2mm 
Capacity: 3V / 225mAh 
Type: Manganese Dioxide Lithium 

Mounting 

Wall. 
DIN rail EN60715 TH35. 

 

Console 
Port 

Mini Type-B USB 2.0 compliant 
1500VDC isolation 

Terminal Wiring 

(for power supply and 
 low-voltage signals) 

Per terminal: solid wires or stranded wires (twisted or with 
ferrule) 

1 core: 0.5mm

2

… 2.5mm

2

 

2 cores: 0.5mm

2

… 1.5mm

2

 

3 cores: not permitted 

 

USB port 

Type-A USB 2.0 compliant 
Only for USB flash storage device (USB pen 
drive) 
Power consumption limited to 150mA (HDD 
connection not allowed) 

Power 

1 x Plug-in screw terminal block (3 poles) 

Positive, Negative, Earth 
24VDC 

 

Push Button 

Button A: Check the user manual 
Button B: Check the user manual 

Operation 
Temperature 

0°C to +60°C 

Ethernet 

1 x Ethernet 10/100 Mbps RJ45 
2 x Ethernet LED: port link and activity 

 

Operational 
Humidity 

5 to 95%, no condensation 

Port A 

1 x DALI port (Plug-in screw terminal block orange 2 poles) 

1500VDC isolation from other ports 
DALI power consumption: 240mA 
Voltage rating: 16VDC 

1 x Plug-in screw terminal block green (2 poles) 

Reserved for future use 

 

Protection  

IP20 (IEC60529) 

LED 
Indicators 

10 x On board LED indicators 

2 x Error (red) / Power LED 
2 x Ethernet Link / Speed 
2 x Port A TX/RX 

2 x Port B TX/RX 

1 x Button A indicator 
1 x Button B indicator 

Switch A  

(SWA)

 

1 x DIP-Switch for PORT A configuration: 

Reserved for future use 

 

PORT B 

1 x Serial EIA232 (SUB-D9 male connector) 

Modbus RTU 
1500VDC isolation from other ports 
(except PORT B: EIA485) 

1 x Serial EIA485 (Plug-in screw terminal block 3 poles) 

A, B, SGND (Reference ground or shield) 
1500VDC isolation from other ports 
(except PORT B: EIA485)  

 

 

 

Switch B  

(SWB)

 

1 x DIP-Switch for serial EIA485 configuration: 

Position 1:  

ON:

 

120 Ω termination active 

Off:

 

120 Ω termination inactive 

Position 2-3: 

ON:

 Polarization active 

Off:

 Polarization inactive

 

 

 

 

CONNECTIONS 

ELECTRICAL & MECHANICAL FEATURES 

Power Supply 
Must use NEC Class 2 or Limited Power Source (LPS) and SELV

 

rated power supply. 

 

If using DC power supply: 
Respect polarity applied of  terminals (+) and (-). Be sure the voltage applied  is within the range 
admitted (check table below). The power supply can be connected to earth but only through the 
negative terminal, never through the positive terminal. 

 

If using AC power supply: 
Make sure the voltage applied is of the value admitted (24 Vac). Do not connect any of the terminals 
of the AC power supply to earth, and make sure the same power supply is not supplying any other 
device. 

 

Ethernet / Modbus TCP / Console (UDP & TCP) 
Connect the cable coming from the IP network to the connector ETH of the gateway. Use an Ethernet 
CAT5 cable. If communicating through the LAN of the building, contact the network administrator and 
make sure traffic on the port used is allowed through all the LAN path (check the gateway user manual 
for more information). DHCP is enabled by default. When disabled, default IP is 192.168.100.246. 

 

PortA / DALI 
Connect the DALI bus to connectors A4 (+), A3 (-) of 

gateway’s PortA. IntesisBox provides 16VDC (+/-

2%) DALI voltage to the bus. 
 

 

PortB / Modbus RTU 
Connect the EIA485 bus to connectors B1 (-), B2 (+) and B3 (SNGD) of 

gateway’s PortB. Respect the 

polarity. Remember the characteristics of the standard EIA485 bus: maximum distance of 1200 meters, 
maximum 32 devices connected to the bus, and in each end of the bus it must be a termination resistor 
of 120 

Ω. The gateway has an internal bus biasing circuit that incorporates the termination resistor. If 

you install the gateway in one of the ends of the bus, then do not install an additional termination resistor 
in that end. 

 

Connect  the  serial  cable  EIA232  coming  from  the  external  serial  device  to  the  EIA232  connector  of 
gateway’s PortB. This is a DB9 male (DTE) connector in which only the lines TX, RX and GND are used. 
Details of the pinout can be seen in the user's manual. Respect the maximum distance of 15 meters. 

 

Console Port 
Connect a mini-type B USB cable from your computer to the gateway to allow communication between 
the Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check 
the user manual for more information. 

 

USB 
Connect a USB storage device (not a HDD) if required. Check the user manual for more information. 

Port B

USB

EIA 232

B1  B2  B3

SW B

SW A Ethernet Port

Port A

A1   A2

A3   A4

Power

zzzzz

Run / Error 

Eth.

Link/Spd

 

PortA 

TX/RX

 

PortB 

TX/RX

Button A 
 
Button B 
 
Console

 -            +

www.intesisbox.com 

Power Supply 

DALI 

Ethernet 
Modbus TCP 

USB  
storage 

Modbus RTU 
EIA232 

Modbus RTU 
EIA485 

Console 
Port 

100 mm (h) 

100 mm (w) 

130 mm (d) 