2 / 4
This information is subject to change without prior notice
email:
web:
www.intesisbox.com
phone: +34 938047134
Enclosure
Plastic, type PC (UL 94 V-0)
Net dimensions (d
x
w
x
h): 90x88x56 mm
Recommended space for installation (d
x
w
x
h): 130x100x100mm
Color: Light Grey. RAL 7035
Battery
Size: Coin 20mm x 3.2mm
Capacity: 3V / 225mAh
Type: Manganese Dioxide Lithium
Mounting
Wall.
DIN rail EN60715 TH35.
Console
Port
Mini Type-B USB 2.0 compliant
1500VDC isolation
Terminal Wiring
(for power supply and
low-voltage signals)
Per terminal: solid wires or stranded wires (twisted or with
ferrule)
1 core: 0.5mm
2
… 2.5mm
2
2 cores: 0.5mm
2
… 1.5mm
2
3 cores: not permitted
USB port
Type-A USB 2.0 compliant
Only for USB flash storage device (USB pen
drive)
Power consumption limited to 150mA (HDD
connection not allowed)
Power
1 x Plug-in screw terminal block (3 poles)
Positive, Negative, Earth
24VDC
Push Button
Button A: Check the user manual
Button B: Check the user manual
Operation
Temperature
0°C to +60°C
Ethernet
1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
Operational
Humidity
5 to 95%, no condensation
Port A
1 x DALI port (Plug-in screw terminal block orange 2 poles)
1500VDC isolation from other ports
DALI power consumption: 240mA
Voltage rating: 16VDC
1 x Plug-in screw terminal block green (2 poles)
Reserved for future use
Protection
IP20 (IEC60529)
LED
Indicators
10 x On board LED indicators
2 x Error (red) / Power LED
2 x Ethernet Link / Speed
2 x Port A TX/RX
2 x Port B TX/RX
1 x Button A indicator
1 x Button B indicator
Switch A
(SWA)
1 x DIP-Switch for PORT A configuration:
Reserved for future use
PORT B
1 x Serial EIA232 (SUB-D9 male connector)
Modbus RTU
1500VDC isolation from other ports
(except PORT B: EIA485)
1 x Serial EIA485 (Plug-in screw terminal block 3 poles)
A, B, SGND (Reference ground or shield)
1500VDC isolation from other ports
(except PORT B: EIA485)
Switch B
(SWB)
1 x DIP-Switch for serial EIA485 configuration:
Position 1:
ON:
120 Ω termination active
Off:
120 Ω termination inactive
Position 2-3:
ON:
Polarization active
Off:
Polarization inactive
CONNECTIONS
ELECTRICAL & MECHANICAL FEATURES
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV
rated power supply.
If using DC power supply:
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range
admitted (check table below). The power supply can be connected to earth but only through the
negative terminal, never through the positive terminal.
If using AC power supply:
Make sure the voltage applied is of the value admitted (24 Vac). Do not connect any of the terminals
of the AC power supply to earth, and make sure the same power supply is not supplying any other
device.
Ethernet / Modbus TCP / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the gateway. Use an Ethernet
CAT5 cable. If communicating through the LAN of the building, contact the network administrator and
make sure traffic on the port used is allowed through all the LAN path (check the gateway user manual
for more information). DHCP is enabled by default. When disabled, default IP is 192.168.100.246.
PortA / DALI
Connect the DALI bus to connectors A4 (+), A3 (-) of
gateway’s PortA. IntesisBox provides 16VDC (+/-
2%) DALI voltage to the bus.
PortB / Modbus RTU
Connect the EIA485 bus to connectors B1 (-), B2 (+) and B3 (SNGD) of
gateway’s PortB. Respect the
polarity. Remember the characteristics of the standard EIA485 bus: maximum distance of 1200 meters,
maximum 32 devices connected to the bus, and in each end of the bus it must be a termination resistor
of 120
Ω. The gateway has an internal bus biasing circuit that incorporates the termination resistor. If
you install the gateway in one of the ends of the bus, then do not install an additional termination resistor
in that end.
Connect the serial cable EIA232 coming from the external serial device to the EIA232 connector of
gateway’s PortB. This is a DB9 male (DTE) connector in which only the lines TX, RX and GND are used.
Details of the pinout can be seen in the user's manual. Respect the maximum distance of 15 meters.
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow communication between
the Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check
the user manual for more information.
USB
Connect a USB storage device (not a HDD) if required. Check the user manual for more information.
Port B
USB
EIA 232
B1 B2 B3
SW B
SW A Ethernet Port
Port A
A1 A2
A3 A4
Power
zzzzz
Run / Error
Eth.
Link/Spd
PortA
TX/RX
PortB
TX/RX
Button A
Button B
Console
- +
www.intesisbox.com
Power Supply
DALI
Ethernet
Modbus TCP
USB
storage
Modbus RTU
EIA232
Modbus RTU
EIA485
Console
Port
100 mm (h)
100 mm (w)
130 mm (d)