2 / 2
This information is subject to change without prior notice
IntesisBox
is a registered trademark of Intesis Software S.L.U.
email:
web:
www.intesisbox.com
phone: +34 938047134
Enclosure
Plastic, type PC (UL 94 V-0)
Net dimensions (d
x
w
x
h): 90x88x56 mm
Recommended space for installation (d
x
w
x
h): 130x100x100mm
Color: Light Grey. RAL 7035
Battery
Size: Coin 20mm x 3.2mm
Capacity: 3V / 225mAh
Type: Manganese Dioxide Lithium
Mounting
Wall.
DIN rail EN60715 TH35.
Console Port
Mini Type-B USB 2.0 compliant
1500VDC isolation
Terminal
Wiring
(for power supply
and
low-voltage
signals)
Per terminal: solid wires or stranded wires (twisted or with
ferrule)
1 core: 0.5mm
2
… 2.5mm
2
2 cores: 0.5mm
2
… 1.5mm
2
3 cores: not permitted
If cables are more than 3.05 meters long, Class 2 cable is required.
USB port
Type-A USB 2.0 compliant
Only for USB flash storage device
(USB pen drive)
Power consumption limited to 150mA
(HDD connection not allowed)
Power
1 x Plug-in screw terminal block (3 poles)
9 to 36VDC +/-10%, Max.: 140mA.
24VAC +/-10% 50-60Hz, Max.: 127mA
Recommended: 24VDC
Push Button
Button A: Not used
Button B: Not used
Operation
Temperature
0°C to +60°C
Ethernet
1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
Operational
Humidity
5 to 95%, no condensation
Port A
1 x H-Link Plug-in screw terminal block orange (2 poles)
1500VDC isolation from other ports
1 x Plug-in screw terminal block green (2 poles)
Reserved for future use
Protection
IP20 (IEC60529)
LED
Indicators
10 x Onboard LED indicators
2 x Run (Power)/Error
2 x Ethernet Link/Speed
2 x Port A TX/RX
2 x Port B TX/RX
1 x Button A indicator
1 x Button B indicator
Switch A
(SWA)
1 x DIP-Switch for PORTA configuration:
Reserved for future use (leave OFF, default)
PORT B
1 x Serial EIA232 (SUB-D9 male connector)
Pinout from a DTE device
1500VDC isolation from other ports
(except PORT B: EIA485)
1 x Serial EIA485 Plug-in screw terminal block (3 poles)
A, B, SGND (Reference ground or shield)
1500VDC isolation from other ports
(except PORT B: EIA232)
Switch B
(SWB)
1 x DIP-Switch for serial EIA485 configuration:
Position 1:
ON:
120 Ω termination active
Off:
120 Ω termination inactive (default)
Position 2-3:
ON:
Polarization active
Off:
Polarization inactive (default)
CONNECTIONS
ELECTRICAL & MECHANICAL FEATURES
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV
rated power supply.
If using DC power supply:
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted
(check table below). The power supply can be connected to earth but only through the negative terminal,
never through the positive terminal.
If using AC power supply:
Make sure the voltage applied is of the value admitted (24 Vac). Do not connect any of the terminals of the
AC power supply to earth, and make sure the same power supply is not supplying any other device.
Ethernet / Modbus TCP (TCP) / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the gateway. Use an Ethernet CAT5
cable. If communicating through the LAN of the building, contact the network administrator and make sure traffic
on the port used is allowed through all the LAN path (check the gateway user manual for more information).
Default IP is 192.168.100.246.
PortA / H-Link Hitachi
Connect the H-Link terminals (TB2) of Hitachi Outdoor Unit to the connectors A3 and A4 of gateway’s PortA.
There is no polarity to be respected.
PortB / Modbus RTU
Connect the EIA485 bus to connectors B1 (B+), B2 (A-) and B3 (SNGD) of gateway’s PortB. Respect the polarity.
Remember the characteristics of the standard EIA485 bus: maximum distance of 1200 meters, maximum 32
devices connected to the bus, and in each end of the bus it must be a termination resistor of 120
Ω
. Bus biasing
and termination resistor for EIA485 can be enabled for PortB by means of a dedicated DIP switch – see table
below.
Connect the serial cable EIA232 coming from the external serial device to the EIA232 connector of
gateway’s PortB. This is a DB9 male (DTE) connector in which only the lines TX, RX and GND are used.
Details of the pinout can be seen in the user's manual. Respect the maximum distance of 15 meters.
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow communication between the
Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check the user
manual for more information.
USB
Connect a USB storage device (not a HDD) if required. Check the user manual for more information.
Power Supply
Ethernet
Modbus TCP
USB
storage
Modbus RTU
EIA485
Console
Port
100 mm (h)
100 mm (w)
130 mm (d)
Hitachi
H-Link -
TB2
Modbus RTU
EIA232