background image

  

 

 

 

 

 

 

© HMS Industrial Networks S.L.U - All rights reserved                

This information is subject to change without notice

 

 

  URL          https://www.intesis.com  

 
 

    Rev.1.6 

                2 / 2

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Enclosure 

Plastic, type PC (UL 94 V-0) 
Net dimensions (d

x

w

x

h): 90x88x56 mm  

Recommended space for installation (d

x

w

x

h): 130x100x100mm 

Color: Light Grey. RAL 7035 

 

Battery 

Size: Coin 20mm x 3.2mm 
Capacity: 3V / 225mAh 
Type: Manganese Dioxide Lithium 

Mounting 

Wall. 
DIN rail EN60715 TH35. 

 

Console 
Port 

Mini Type-B USB 2.0 compliant 
1500VDC isolation 

Terminal Wiring 

(for power supply and 
 low-voltage signals) 

Per terminal: solid wires or stranded wires (twisted or with 
ferrule) 

1 core: 0.5mm

2

… 2.5mm

2

 

2 cores: 0.5mm

2

… 1.5mm

2

 

3 cores: not permitted 

If cables are more than 3.05 meters long, Class 2 cable is required.

 

 

USB port 

Type-A USB 2.0 compliant 
Only for USB flash storage device  

(USB pen drive) 

Power consumption limited to 150mA  

(HDD connection not allowed) 

Power 

1 x Plug-in screw terminal block (3 poles) 

Positive, Negative, Earth 
24VDC +/-10% 

 

Push Button 

Button A: Check the user manual 
Button B: Check the user manual 

Operation 
Temperature 

0°C to +60°C 

Ethernet 

1 x Ethernet 10/100 Mbps RJ45 
2 x Ethernet LED: port link and activity 

 

Operational 
Humidity 

5 to 95%, no condensation 

Port A 

1 x MBUS Plug-in screw terminal block orange (2 poles) 

1500VDC isolation from other ports 
Voltage rating: 36VDC / 210mA 

1 x Plug-in screw terminal block green (2 poles) 

Reserved for future use 

 

Protection  

IP20 (IEC60529) 

LED 
Indicators 

10 x Onboard LED indicators 

2 x Error (red)/ Power LEDs 
2 x Ethernet Link/Speed 
2 x Port A TX/RX 

2 x Port B TX/RX 

1 x Button A indicator 
1 x Button B indicator 

Switch A  

(SWA)

 

1 x DIP-Switch for PORT A configuration: 

Reserved for future use 

 

PORT B 

1 x Serial EIA232 (SUB-D9 male connector) 

Reserved for future use 

1 x Serial EIA485 Plug-in screw terminal block (3 poles) 

A, B, SGND (Reference ground or shield) 
1500VDC isolation from other ports 

(except PORT B: EIA232)

  

 

 

 

Switch B  

(SWB)

 

1 x DIP-Switch for serial EIA485 configuration: 

Position 1:  

ON:

 

120 Ω termination active 

Off:

 

120 Ω termination inactive 

Position 2-3: 

ON:

 Polarization active 

Off:

 Polarization inactive

 

 

 

 

CONNECTIONS 

ELECTRICAL & MECHANICAL FEATURES 

Power Supply 
Must use NEC Class 2 or Limited Power Source (LPS) and SELV

 

rated power supply. Respect polarity 

applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted (check table 
below).  The  power  supply  can  be  connected  to  earth  but  only  through  the  negative  terminal,  never 
through the positive terminal. 
 
Ethernet / BACnet IP (UDP) / Console (UDP & TCP) 
Connect the cable coming from the IP network to the connector ETH of the gateway. Use an Ethernet 
CAT5 cable. If communicating through the LAN of the building, contact the network administrator and 
make sure traffic on the port used is allowed through all the LAN path (check the gateway user manual 
for more information). With factory settings, after powering up the gateway, DHCP will be enabled for 30 
seconds. After that time, if no IP is provided by a DHCP server, the default IP 192.168.100.246 will be 
set. 
 
PortA / MBUS 
Connect the MBUS bus to connectors A3 (+) and A4 (-) of gateway

’s PortA. The Intesis gateway provides 

36VDC M-Bus voltage to the bus. 
 
PortB / BACnet MSTP 
Connect the EIA485 bus to connectors B1 (-), B2 (+) and B3 (SNGD) of 

gateway’s PortB. Respect the 

polarity.  
 
Remember  the  characteristics  of  the  standard  EIA485  bus:  maximum  distance  of  1200  meters, 
maximum 32 devices connected to the bus, and in each end of the bus it must be a termination resistor 
of 120 

Ω. The gateway has an internal bus biasing circuit that incorporates the termination resistor. If 

you install the gateway in one of the ends of the bus, then do not install an additional termination resistor 
in that end. 
 
Console Port
 
Connect a mini-type B USB cable from your computer to the gateway to allow communication between 
the Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check 
the user manual for more information. 
 
USB 
Connect a USB storage device (not a HDD) if required. Check the user manual for more information. 

Power Supply 

MBUS 

Ethernet 
BACnet IP 

USB  
storage 

BACnet MSTP 
EIA485 

Console 
Port 

100 mm (h) 

100 mm (w) 

130 mm (d) 

This marking on the product, accessories, packaging or literature (manual) indicates that the product contains electronic 
parts and they must be properly disposed of by following the instructions a

https://intesis.com/weee-regulation

  

 