NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

FRONT OF FIREPLACE

REAR BURNER

FRONT BURNER

VENTURI TUBE ARM

VENTURI TUBE ARM

AIR SHUTTER

ADJUSTMENT LEVER

FIREBOX SUBFLOOR

NOTE: REMOVE FRONT BURNER FIRST,

THEN REAR BURNER.

The  natural to LP/propane gas conversion
kit is supplied with the fireplace. The kit
contains all the necessary components
needed to complete the conversion process,
including labeling that must be affixed to
ensure safe operation.

Figure 55

GAS CONVERSION KITS

In Canada:
THE CONVERSION SHALL BE CARRIED OUT
IN ACCORDANCE WITH THE REQUIREMENTS
OF THE PROVINCIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE WITH
THE REQUIREMENTS OF THE CAN1-B149.1
AND .2 INSTALLATION CODE.

LA CONVERSION DEVRA ÊTRE EFFECTUÉE
CONFORMÉMENT AUX RECOMMANDATIONS
DES AUTORITÉS PROVINCIALES AYANT
JURIDICTION ET CONFORMÉMENT AUX
EXIGENCES DU CODE D'INSTALLATION CAN1-
B149.1 ET.2.

WARNING:  THIS CONVERSION KIT SHALL BE
INSTALLED BY A QUALIFIED SERVICE AGENCY IN
ACCORDANCE WITH THE MANUFACTURER'S IN-
STRUCTIONS AND ALL APPLICABLE CODES AND
REQUIREMENTS OF THE AUTHORIZED AGENCY
HAVING JURISDICTION.  IF THE INFORMATION IN
THESE INSTRUCTIONS IS NOT FOLLOWED EX-
ACTLY, A FIRE, EXPLOSION OR PRODUCTION OF
CARBON MONOXIDE MAY RESULT CAUSING
PROPERTY DAMAGE, PERSONAL INJURY OR LOSS
OF LIFE.  THE INSTALLATION IS NOT PROPER AND
COMPLETE UNTIL THE OPERATION OF THE CON-
VERTED APPLIANCE IS CHECKED AS SPECIFIED IN
THE OWNER INSTRUCTIONS SUPPLIED WITH THE
KIT. THE QUALIFIED SERVICE AGENCY PERFORM-
ING THIS INSTALLATION ASSUMES RESPONSI-
BILITY FOR THIS CONVERSION.

AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION
SERA INSTALLÉ PAR UNE AGENCE QUALIFIÉE DE SERVICE
CONFORMÉMENT AUX INSTRUCTIONS DU FABRICANT ET
TOUTES EXIGENCES ET CODES APPLICABLES DE
L'AUTORISÉS AVOIR LA JURIDICTION.  SI L'INFORMATION
DANS CETTE INSTRUCTION N'EST PAS SUIVIE
EXACTEMENT, UN FEU, EXPLOSION OU PRODUCTION DE
PROTOXYDE DE CARBONE PEUT RÉSULTER LE DOMMAGES
CAUSER DE PROPRIÉTÉ, PERTE OU BLESSURE
PERSONNELLE DE VIE.  L'AGENCE QUALIFIÉE DE SERVICE
EST ESPONSABLE DE L'INSTALLATION PROPRE DE CET
ÉQUIPMENT.  L'INSTALLATION N'EST PAS PROPRE ET
COMPLÉTE JUSQU'À L'OPÉRATION DE L'APPAREIL
CONVERTI EST CHÉQUE SUIVANT LES CRITÈRES ÉTABLIS
DANS LES INSTRUCTIONS DE PROPRIÉTAIRE
PROVISIONNÉES AVEC L'ÉQUIPEMENT.

Millivolt Appliances

Step 4.

  Refer to 

Figure 56 on page 27 

and the

instructions provided with the kit.  Using a Torx
T20, remove and discard the three pressure
regulator mounting screws.  Remove the pres-
sure regulator, spring, poppet, diaphragm and
bushing.  

Discard all removed components

.

Ensure the rubber gasket installed on the back
of the replacement pressure regulator is prop-
erly positioned and install the new pressure
regulator using the new screws supplied with
the kit.  Tighten screws to 25 In. lb. torque.

The following steps detail the conversion
procedure:

Step 1.

 Turn off the gas supply to the appliance.

a.

Open the control compartment access panel,

by actuating the spring-loaded magnetic
catches securing the panel, gently depress-
ing the outer top corners of the panel until
the catches "pop" the panel free and allowing
it to swing out and down to open.

b.

Locate the two (2) latches at the top of the

control compartment. To disengage the two
latches from the bottom vee-flange of the
glass enclosure panel, reach for the handles
located towards the back of the latches and
pull the handles down toward the front of the
unit.

c.

Swing the bottom of the door out and raise

it slightly to lift the top flange of the door
frame away from the appliance.

Step 2.

 Carefully remove the log set. 

Exercise

care as not to break the log set

.

Step 3.

 Referring to 

Figure 55 

 remove the

front burner and then the rear burner.

f i r e - p a r t s . c o m

Summary of Contents for Millivolt DMPFNM-2

Page 1: ...lez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service dos incendies L installationetse...

Page 2: ...These vented gas fireplace heaters are sealed combustion air circulating gas fireplaces de signed for residential applications These ap pliances must be installed with the Secure Vent and or Secure F...

Page 3: ...s of the local authorities having jurisdiction and in the USA the latest edition of the National Fuel Gas Code ANSI Z223 1 or in Canada the latest edition of the CAN1 B149 1 and 2 codes WARNING FAILUR...

Page 4: ...ion When the unit is installed with one side flush with a wall the wall on the other side of the unit must not extend beyond the front edge of the unit In addition whentheunitisinstalledinthemiddle of...

Page 5: ...Circuit Wiring Step 5 page 21 Make connection to gas supply Step 6 page 22 Install the log set ver miculite and ceramic fiber chunks Step 7 page 22 Checkout appliance op eration Step 8 page 22 Instal...

Page 6: ...cm minimum H not be installed above a gas service meter regulator assembly within 3 feet 91 4 cm horizontally from the center line of the gas service regulator I clearance to gas service regulator ve...

Page 7: ...LBOWS inches millimeters 7 178 5Z 130 12Z 308 6Z v 159 A Minimum Framing Stud Size is 2x4 41Z x 1054 43B 1108 This dimension can be reduced to 41 inches 1041 mm This results in 0 in 0 mm clearance bet...

Page 8: ...stalled vent seal cap and vent cover plate see Figures 13 and 14 on page 9 in each flue outlet The vent seal cap is not shown in this figure DMPFNM 2 Peninsula 12 305 10 254 TOP VIEW 40Z 1019 3Z x 89...

Page 9: ...being used from inside the firebox loosen the two screws in the keyhole slots of the cover plate and remove the remaining two cover plate securing screws Re move and discard the cover plate Reinstall...

Page 10: ...9 0 0 1 5 5 2 3 5 2 1 7 2 0 0 0 0 7 7 0 3 3 5 7 2 1 0 0 0 7 8 6 3 3 8 2 0 1 0 0 7 8 5 4 3 5 7 8 2 0 0 0 0 1 0 0 1 5 9 4 3 5 2 1 9 2 1 0 0 0 1 0 1 1 2 7 3 1 3 0 0 0 0 8 8 5 6 7 3 5 7 3 1 3 1 0 0 0 8 9...

Page 11: ...See Fig ure 21 for pitched roofs or flat roofs with flat ceilings or Figure 22 for pitched roofs with cathedral ceilings FIGURE 22 Note Trim Thimble Extension To Desired Length And Pitch At The Roof...

Page 12: ...e Support the vertical portion of the venting system every 8 feet 2 4m above the fireplace vent outlet One method of support is by utiliz ing field provided support straps conventional plumber s tape...

Page 13: ...hen using Secure Flex use Firestop Spacer SF4 5BF Figure 30 Rear Vent ONE 90 DEGREE ELBOW Figure 29 Top Vent STRAIGHT Figure 31 Top Vent TWO 90 DEGREE ELBOWS VERTICAL VENT FIGURES TABLES Note Secure V...

Page 14: ...M V m u m i x a M H H H 1 m u m i x a M t e e f m t e e f m t e e f m 1 5 0 3 0 2 0 1 6 0 5 2 5 1 2 0 1 6 0 4 2 2 1 0 1 1 3 3 4 1 9 0 6 6 8 1 5 1 5 6 4 4 2 2 1 8 8 4 2 0 2 2 6 V V 1 H H 1 x a M m 4 2...

Page 15: ...an opening 10 x 10 267 mm x 267 mm inside dimensions about this center refer to Figure 18 on page 11 G Support the vertical run sections See section E on page 12 H Change vent direction At transition...

Page 16: ...ng as described in Step B Assemble the vent system to point where the terminus of the last section is within 7 in 191 mm to 11 in 298 mm inboard of the exterior surface to which the SV4 5 HTS terminat...

Page 17: ...lex use Firestop Spacer SF4 5HF E L B A T F w o b l e e e r g e d 0 9 e n 0 V x a M m 4 1 9 0 t e e f 3 H Figure 38 Rear Vent NO ELBOWS Figure 39 Top Vent ONE 90 DEGREE ELBOW ELBOW CONNECTION AT APPLI...

Page 18: ...l Firestop Spacer SV4 5HF Ceiling Firestop Spacer SV4 5BF Note When using Secure Flex use Firestop Spacer SF4 5BF V H H1 Wall Firestop Spacer SV4 5HF Wall Firestop Spacer SV4 5HF When using Secure Fle...

Page 19: ...0 3 0 5 2 5 1 2 0 1 6 0 0 1 1 3 3 4 1 9 0 5 1 5 6 4 4 2 2 1 0 2 2 6 H H 1 x a M m 2 6 t e e f 0 2 V V 1 H H 1 x a M m 4 2 1 t e e f 0 4 V H2 H1 H Wall Firestop Spacer SV4 5HF When using Secure Flex u...

Page 20: ...r clock wise running the dimples down and along the incline channels until they seat at the end of the channels B Install the Outer Flex Pipe 1 Installthelargegearclamplooselyaround the outer flexible...

Page 21: ...x Reducer Gas Valve Gas Flex Line Connector Figure 49 Figure 48 GAS CONNECTION Turn on gas supply and test for gas leaks using a soapy water solution Never use an open flame to check for leaks A Mix a...

Page 22: ...instruction labels at tached to the gas control valve To access the label see the procedure on the previous page described for accessing the gas control valve When first lighting the appliance it wil...

Page 23: ...e and sooting Proper flame appearance is a matter of taste Generally most people prefer the warm glow of a yellow to orange flame Appliances operated with air shutter openings that are too large will...

Page 24: ...nter the room It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground level d e t s i L t n e V e r u c e S s l e d...

Page 25: ...3 t f 2 1 1 0 L 7 8 K R H F S x e l F h t i w t i K r e s i R l e k r o n S d n a x e l F f o n o i t c e s a r e t p a d A s p m a l C r a e G 1 8 K 0 1 P M F S e r u t a r e p m e T i H k c a l B c...

Page 26: ...S SAVOIRLAJURIDICTION SIL INFORMATION DANS CETTE INSTRUCTION N EST PAS SUIVIE EXACTEMENT UN FEU EXPLOSION OU PRODUCTION DE PROTOXYDEDECARBONEPEUTR SULTERLEDOMMAGES CAUSER DE PROPRI T PERTE OU BLESSURE...

Page 27: ...Step 5 Attach manometer to the manifold side pressure test fitting and verify manifold pressurereads10 0incheswatercolumn 2 49 kPa for propane gas Step 6 Refer to Figure 57 and remove the pilot hood a...

Page 28: ...2002 The manufacturer reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local dist...

Reviews: