Additional  installation  material,  such  as  rails  or  panels
and also junction boxes, are not included in the standard
scope of delivery (see 

Installation accessories [

}

Page 3]

)

and must be ordered additionally.

8

Connection

 WARNING

The heater is only designed for non hazardous
areas.

INTERTEC-Hess GmbH accepts no liability for improper
use.

 INFO

The device may only be connected up and secured by a
trained person, taking into account the "rated voltage"
and "rated current" specified on the nameplate.

Where  operating  voltage  =  measured  voltage  (rated
voltage),  then  the  heater  is  at  its  rated  output.  Mains
voltage fluctuations up to 10 % are then permissible.

Each  heater  with  integrated  TS  thermostat  must  be
preceded  by  a  10  A  fuse  or  a  motor  protection  switch
with short-circuit and thermal quick release (set to 10 A)
as  short-circuit  protection.  When  using  a  heater  without
integrated  thermostat,  the  fuse  protection  can  be
selected  according  to  the  cross-section  of  the  supply
cable.

In  a  TT  or  TN  system,  a  residual  current  device  (RCD)
must  be  used  where  the  measured  triggering  residual
current  does  not  exceed  100  mA.  Residual  current
devices with a measured triggering residual current of 30
mA  are  preferable.  In  an  IT  system,  an  insulation
monitoring  device  needs  to  be  used  which  switches  off
the  supply  as  soon  as  the  insulation  resistance  is  no
greater than 50 Ω per Volt of the rated voltage.

ATTENTION:
Never remove the
adapter/ cable gland!

Illustration 2: 

Example heater with KLE connection

 CAUTION

NOTICE: Do not remove adapter/ cable
connection to connect up the heater!

This would cause irreversible damage to the heater.

The illustration may deviate from the heater.

1

2

3

4

5

6

7

8

9

10

11

12

13

L
N

PE

NTC

RS 485

F1

TC DIGITAL

CP...THERM...HI

external sensor 

br=brown bl=blue ye/gn=yellow/green bk=black gr=grey

bl  br  gn/ye 

gr  bk 

+

A

B
Ground 

Illustration 3: 

Smart Heater HI System with TC

9

Commissioning

If the heater is installed in accordance with the notes in
the 

Installation  [

}

Page  4]

  section  and 

Connection  [

}

Page  5]

 

sections, 

then 

the 

radiator 

may 

be

commissioned.

 CAUTION

Sufficient heat dissipation must be ensured.

Unauthorized covers must be removed as otherwise
there is the risk of the heater overheating.

The heating circuit is permanently disconnected by a
temperature melt fuse which can't be reset if these
installation instructions are not adhered to.