background image

440 04 6001 00

3

Specifications  subject to change without notice.

START

UP, ADJUSTMENT, AND SAFETY

CHECK

NOTICE

IMPORTANT INSTALLATION AND START

UP

PROCEDURES

Failure to follow this procedure may result in a nuisance

smoke or odor complaint.
The manifold pressure, gas rate by meter clocking,

temperature rise and operation must be checked after

installation. Minor smoke and odor may be present

temporarily after start

up from the manufacturing process.

Some occupants are more sensitive to this minor smoke and

odor. It is recommended that doors and windows be open

during the first heat cycle.

General

1. Furnace must have a 115-v power supply properly

connected and grounded.

NOTE

:  Proper polarity must be maintained for 115-v wiring.

Control status indicator light flashes rapidly and furnace
does not operate if polarity is incorrect or if the furnace is not
grounded.

2. Thermostat wire connections at terminals R, W, G,

and Y must be made at 24-v terminal block on

furnace control.

3. Natural gas service pressure must not exceed 0.5

psig (14- in. w.c., 1125 Pa), but must be no less than

0.16 psig (4.5-in. w.c., 350 Pa).

4. Blower door must be in place to complete 115-v elec-

trical circuit and supply power to the furnace

components.

UNIT OPERATION HAZARD

Failure to follow this caution may result in intermittent

unit operation or performance satisfaction.
These furnaces are equipped with a manual reset limit

switch in burner assembly.  This switch opens and

shuts off power to the gas valve if an overheat

condition (flame rollout) occurs in the burner

assembly/enclosure.  Correct inadequate

combustion

air supply, improper gas pressure setting,

improper burner or gas orifice positioning, or improper

venting condition before resetting switch.  DO NOT

jumper this switch.

CAUTION

!

Before operating furnace, check flame rollout manual reset

switch for continuity. If necessary, press button to reset

switch.
EAC-1 (115vac) terminal is energized whenever blower

operates. HUM (24vac) terminal is only energized when the

low pressure switch (LPS) is closed on a call for heat.

Prime Condensate Trap with Water

CARBON MONOXIDE POISONING HAZARD

Failure to follow these warnings could result in personal

injury or death.
Failure to use a properly configured trap or NOT

water-priming trap before operating furnace may allow

positive pressure vent gases to enter the structure

through drain tube. Vent gases contain carbon

monoxide which is tasteless and odorless.

!

WARNING

1. Remove upper and middle collector box drain plugs

opposite of the condensate trap.   (See Figure 10.)

2. Connect field-supplied 5/8-in. (16 mm) ID tube with at-

tached funnel (see Figure 10) to upper collector box

drain connection.

3. Pour one quart (liter) of water into funnel/tube. Water

should run through collector box, overfill condensate

trap, and flow into open field drain.

4. Remove funnel; replace collector box drain plug.
5. Connect field-supplied 5/8-in. (16 mm) ID tube to

middle collector box drain port.

6. Pour one quart (liter) of water into funnel/tube. Water

should run through collector box, overfill condensate

trap, and flow into open field drain.

7. Remove funnel and tube from collector box and

replace collector box drain plug.

Purge Gas Lines

If not previously done, purge the lines after all connections

have been made and check for leaks.

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal

injury, death, and/or property damage.
Never purge a gas line into a combustion chamber.

Never test for gas leaks with an open flame. Use a

commercially available soap solution made

specifically for the detection of leaks to check all

connections.  A fire or explosion may result causing

property damage, personal injury or loss of life.

!

WARNING

Adjustments

FIRE HAZARD

Failure to follow this warning could result in personal

injury, death and/or property damage.
DO NOT bottom out gas valve regulator adjusting

screw. This can result in unregulated manifold

pressure and result in excess overfire and heat

exchanger failures.

!

WARNING

Summary of Contents for R9MSB0601716B

Page 1: ...in the following manner CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and or pictures or product labels The signal word WARNING is used throughout this man...

Page 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Page 3: ...115vac terminal is energized whenever blower operates HUM 24vac terminal is only energized when the low pressure switch LPS is closed on a call for heat Prime Condensate Trap with Water CARBON MONOXID...

Page 4: ...ions to match the required orifice to the manifold pressure to the heat content and specific gravity of the gas To do this 1 Obtain average yearly gas heat value at installed altitude from local gas s...

Page 5: ...hould be clear blue almost transparent See Figure 12 i Remove jumper R to W j Reinstall manifold pressure tap plug from gas valve 2 Verify natural gas input rate by clocking meter NOTE Contact your HV...

Page 6: ...exchangers or condensing flue gases in heat exchanger areas not designed for condensate S Shortened furnace life S Component damage Temperature rise must be within limits specified on furnace rating p...

Page 7: ...nals when furnace is in low heat and after blower starts 4 Set heat anticipator on thermostat per thermostat instructions and install on sub base or wall 5 Install blower access door Electronic thermo...

Page 8: ...743 3048 18 20 0 81 Derate multiplier factors are based on midpoint altitude for altitude range ON OFF Switch Regulator Seal Cap Regulator Adjustment Regulator Seal Cap under Cap 1 2 NPT Outlet 1 8 NP...

Page 9: ...290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 9...

Page 10: ...10 440 04 6001 00 Specifications subject to change without notice 338309 201 Rev E A11602 Figure 5 Service Label Information...

Page 11: ...2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3...

Page 12: ...5 1075 1015 950 885 Red 3 2 5 394 1030 1025 1030 1010 985 940 905 855 805 735 0801716B SIDE BOTTOM Black 4 0 389 1650 1620 1640 1605 1555 1495 1425 1345 1255 1165 Yellow 3 5 381 1420 1425 1400 1370 13...

Page 13: ...switch is 0 73 in W C The maximum make point of the switch is 0 83 in W C ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death There may be more than one el...

Page 14: ...ND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE BLOWER DOOR SWITCH WHT BLK WHT BLK NOTES Connect Y term...

Page 15: ...e sure that it operates properly with the room thermostat Check all modes including Heat Cool and Fan 7 Check operation of accessories per manufacturer s instructions 8 Review Owner s Manual with owne...

Page 16: ...8 Turn on electrical supply to furnace Blower Motor and Wheel Maintenance To ensure long life economy and high efficiency clean accumulated dirt and grease from blower wheel and motor annually The in...

Page 17: ...aning Burners and Flame Sensor The following items must be performed by a qualified service technician If the burners develop an accumulation of light dirt or dust they may be cleaned by using the fol...

Page 18: ...burner assembly without striking the igniter on surrounding parts c Inspect igniter for signs of damage or failure d If replacement is required remove the screw that secures the igniter on igniter bra...

Page 19: ...supply circuit is on Cleaning Heat Exchangers The following items must be performed by a qualified service technician Primary Heat Exchangers If the heat exchangers get an accumulation of light dirt o...

Page 20: ...ed Follow these procedures to winterize your furnace UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the furnace and other property damage Do not use ethylene glyco...

Page 21: ...ner Manifold A11461 Figure 12 Burner Flame SET SCREW MOTOR WHEEL HUB MOTOR SHAFT FLAT SCREW MOTOR ARM GROMMET SCREW LOCATION BLO HSG ASSY BRACKET BRACKET ENGAGEMENT SEE DETAIL A CAPACITOR OR POWER CHO...

Page 22: ...22 440 04 6001 00 Specifications subject to change without notice FLAME SENSOR BELOW BURNER FLAME ROLLOUT SWITCH BRACKET IGNITER IGNITER BURNER SUPT ASSY BURNER ASSY A11403 Figure 14 Burner Assembly...

Page 23: ...y If the burner flame is proven the blower motor is energized on HEAT speed 25 sec after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC 1 is energized and remains...

Page 24: ...flash the status code of the previous fault or status code 11 1 short and 1 long flash if there was no previous fault After the control repeats the code 4 times the control will go through a brief com...

Page 25: ...control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check t...

Page 26: ...26 440 04 6001 00 Specifications subject to change without notice 339236 2 Rev A Figure 16 Wiring Diagram...

Page 27: ...can cause personal injury property damage or death Consult a qualified installer service agency or your local gas supplier for information or assistance The qualified installer or service agency must...

Reviews: