FIGURE 6

Unit Leveling Tolerances

FIGURE 7

Slab Mounting Detail

CONFIGURING HORIZONTAL UNITS FOR DOWNFLOW

(VERTICAL) DISCHARGE

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing or servicing system, turn off the power

supply to the unit and install lockout tag. There may be

more than one disconnect switch.

!

WARNING

1. Open all electrical disconnects before starting any

service work.

2. Remove horizontal duct covers to access bottom return

and supply knock out panels.

3. Use a screwdriver and hammer to remove the panels in

the bottom of the unit base.

NOTE

: These panels are held in place with tabs similar to

an electrical knockout.

4. Reinstall the horizontal duct covers (Fig. 10) to block off

the horizontal air openings.

NOTE

: Avoid abrupt duct size increases and reductions.

Abrupt change in duct size adversely affects air

performance.

Step 6—Connect Condensate Drain
NOTE

: When installing condensate drain connection be

sure to comply with local codes and restrictions.
This unit disposes of condensate water through a 3/4 in.

NPT fitting which exits through the base on the compressor

end of the unit.

Condensate water can be drained directly onto the roof in

rooftop installations (where permitted) or onto a gravel

apron in ground level installations. Install a field--supplied

condensate trap at end of condensate connection to ensure

proper drainage. Make sure that the outlet of the trap is at

least 1 in. (25 mm) lower than the drain--pan condensate

connection to prevent the pan from overflowing. Prime the

trap with water.When using a gravel apron, make sure it

slopes away from the unit.
If the installation requires draining the condensate water

away from the unit, install a field--supplied 2--in. (51mm)

trap at the condensate connection to ensure proper

drainage. Condensate trap is available as an accessory or

is field--supplied. Make sure that the outlet of the trap is at

least 1 in. (25 mm) lower than the unit drain--pan

condensate connection to prevent the pan from

overflowing. Connect a drain trough using a minimum of

field--supplied 3/4--in. (19 mm) PVC or field--supplied

3/4--in. (19 mm) copper pipe at outlet end of the 2--in. (51

mm) trap. (See Fig. 11) Do not undersize the tube. Pitch the

drain trough downward at a slope of at least 1 in. (25 mm)

every 10 ft (3 m) of horizontal run. Be sure to check the drain

trough for leaks. Prime the trap at the beginning of the

cooling season start--up.

Step 7—Install Electrical Connections

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
The unit cabinet must have an uninterrupted, unbroken

electrical ground. This ground may consist of an

electrical wire connected to the unit ground screw in the

control compartment, or conduit approved for electrical

ground when installed in accordance with NEC,

ANSI/NFPA

American

National

Standards

Institute/National Fire Protection Association (latest

edition) (in Canada, Canadian Electrical Code CSA

C22.1) and local electrical codes.

!

WARNING

UNIT COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in damage to the

unit being installed.

1.

Make all electrical connections in accordance with

NEC ANSI/NFPA (latest edition) and local electrical

codes governing such wiring. In Canada, all

electrical connections must be in accordance with

CSA standard C22.1 Canadian Electrical Code Part

1 and applicable local codes. Refer to unit wiring

diagram.

2.

Use only copper conductor for connections between

field--supplied electrical disconnect switch and unit.

DO NOT USE ALUMINUM WIRE.

3.

Be sure that high--voltage power to unit is within

operating voltage range indicated on unit rating

plate.

4.

Do not damage internal components when drilling

through any panel to mount electrical hardware,

conduit, etc.

!

CAUTION

Summary of Contents for PHN524

Page 1: ...heaters Installation 10 Sequence of Operation 11 PRE START UP 14 START UP 14 Checking Cooling Heating Control Operation 14 Check for Refrigerant Leaks 14 Start Up Adjustments 15 Checking Adjusting Refrigerant Charge 15 Indoor Airflow Airflow Adjustments 15 Continuous Fan Operation 16 Defrost Control 17 Quiet Shift 17 Defrost 17 MAINTENANCE 17 Air Filter 18 Indoor Blower and Motor 18 Outdoor Coil I...

Page 2: ...ning could result in personal injury or death Before installing or servicing system turn off power supply to the unit and install lockout tag There may be more than one disconnect switch Turn off accessory heater power switch if applicable WARNING INTRODUCTION This packaged heat pump unit is fully self contained and designed for outdoor installation see Fig 1 See Fig 3 and 4 for unit dimensions Al...

Page 3: ...e Unit Rigging and handling of this equipment can be hazardous for many reasons due to the installation location roofs elevated structures etc Only trained qualified crane operators and ground support staff should handle and install this equipment When working with this equipment observe precautions in the literature on tags stickers and labels attached to the equipment and any other safety precau...

Page 4: ...p of brackets down approximately 30 degrees from the corner posts 2 Attach straps of equal length to the rigging brackets at opposite ends of the unit Be sure straps are rated to hold the weight of the unit See Fig 2 3 Attach a clevis of sufficient strength in the middle of the straps Adjust the clevis location to ensure unit is lifted level with the ground 4 After unit is securely in place detach...

Page 5: ...5 FIGURE 3 PHN524 DIMENSIONS ...

Page 6: ...6 FIGURE 4 PHN536 60 DIMENSIONS ...

Page 7: ...r rack installed in the return air side of the unit Recommended sizes for filters are shown in Table 1 2 Avoid abrupt duct size increases and reductions Abrupt change in duct size adversely affects air performance IMPORTANT Use flexible transitions between ductwork and unit to prevent transmission of vibration Use suitable gaskets to ensure weather tight and airtight seal When electric heat is ins...

Page 8: ...opening B X C Insulate d deck pan Short Support CTyp G E F G D E FIGURE 5 Roof Curb Dimensiona F Model PHN5 MODEL NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 24 NPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126 45 15 16 1167 NPRFCURB007A00 14 356 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126 45 15 16 1167 36 60 NPRFCURB008A00 8 203 16 3 16 411 17 3...

Page 9: ...ion to ensure proper drainage Condensate trap is available as an accessory or is field supplied Make sure that the outlet of the trap is at least 1 in 25 mm lower than the unit drain pan condensate connection to prevent the pan from overflowing Connect a drain trough using a minimum of field supplied 3 4 in 19 mm PVC or field supplied 3 4 in 19 mm copper pipe at outlet end of the 2 in 51 mm trap S...

Page 10: ...ove black wire from transformer 3 16 in terminal marked 230 to terminal marked 208 This retaps transformer to primary voltage of 208 vac WARNING CONTROL VOLTAGE CONNECTIONS NOTE Do not use any type of power stealing thermostat Unit control problems may result Use no 18 American Wire Gage AWG color coded insulated 35 C minimum wires to make the controlvoltage connections between the thermostat and ...

Page 11: ... UNIT SIZE PHN524 PHN536 PHN548 PHN560 NOMINAL CAPACITY ton 2 3 4 5 OPERATING WEIGHT lb kg 405 184 464 210 492 223 535 256 COMPRESSOR TYPE TWO STAGE SCROLL COMPRESSOR Refrigerant R 410A Quantity lb Quantity kg 10 3 4 67 9 7 3 99 15 5 7 03 16 0 7 3 EXPANSION DEVICE HEATING FIXED ORIFICE ORIFICE OD in Left 0 042 0 035 0 038 0 046 ORIFICE OD in Right N A 0 035 0 046 0 046 EXPANSION DEVICE COOLING TXV...

Page 12: ...12 FIGURE 9 Typical Installation FIGURE 10 PHN5 With Duct Covers On FIGURE 11 Condensate Drain 1 25 mm MIN 2 51 mm MIN TRAP OUTLET Duct Covers ...

Page 13: ...13 FIGURE 12 PHN524 60 208 230 1 60 Wiring Diagram ...

Page 14: ... are filled with water to ensure proper drainage d Make sure that all tools and miscellaneous loose parts have been removed 5 Each unit system has two 2 Schrader type ports one low side Schrader fitting located on the suction line and one high side Schrader fitting located on the compressor discharge line Be sure that caps on the ports are tight START UP Step 1 CHECK COOLING AND HEATING OPERATION ...

Page 15: ...ion low side pressure psig for reference only 5 Using Cooling Charging Charts compare outdoor air temperature F C db with the discharge line pressure psig to determine desired system operating liquid line temperature See Fig 18 6 Compare actual liquid line temperature with desired liquid line temperature Using a tolerance of 2 F 1 1 C add refrigerant if actual temperature is more than 2 F 1 1 C hi...

Page 16: ...is the same as high stage cooling fan speed Continuous Fan Operation The continuous fan operates at the same fan speed as low stage cooling fan operation FIGURE 13 Typical Heat Pump Operation Cooling Mode COMPRESSOR ACCUMULATOR OUTDOOR COIL INDOOR COIL LCS LEGEND HPS High Pressure Switch LCS Loss of Charge Switch Accurater Metering Device Arrow indicates direction of flow Metering Position Bypass ...

Page 17: ...FF position a normal and complete defrost cycle will be observed If defrost thermostat is in open position and speedup pins are shorted with a flat head screw driver for 5 sec and released a short defrost cycle will be observed actual length is dependent upon the selected Quiet Shift position When Quiet Shift switch is in ON position the length of defrost is 1 minute 30 sec compressor off period f...

Page 18: ... SHOCK HAZARD Failure to follow this warning could result in personal injury or death Disconnect and tag electrical power to the unit before cleaning the blower motor and wheel WARNING To clean the blower motor and wheel 1 Remove and disassemble blower assembly as follows a Remove unit access panel b Disconnect 5 pin plug and 4 pin plug from indoor blower motor c On all units remove blower assembl...

Page 19: ...coil pressure drop to obtain external static pressure available for ducting Table 5 PHN5 Wet Coil Pressure Drop in W C UNIT SIZE STANDARD CFM S C F M 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 024 0 06 0 07 0 08 0 09 0 1 030 0 12 0 15 0 19 0 23 0 27 036 0 07 0 11 0 18 0 26 0 35 042 0 04 0 07 0 1 0 15 0 21 048 0 11 0 14 0 17 0 22 0 28 060 0 1 0 17 0 23 0 31 0 36 Table 6 ...

Page 20: ...oils with a mild detergent and water solution Rinse coils with clear water using a garden hose Be careful not to splash water on motors insulation wiring or air filter s For best results spray condenser coil fins from inside to outside the unit On units with an outer and inner condenser coil be sure to clean between the coils Be sure to flush all dirt and debris from the unit base Inspect the drai...

Page 21: ...r tightness Tighten all screw connections If any discolored or burned connections are noticed disassemble the connection clean all the parts restrip the wire end and reassemble the connection properly and securely After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are ...

Page 22: ...be caused by a dirty outdoor coil failed fan motor or outdoor air recirculation To check switch 1 Turn off all power to unit 2 Disconnect leads on switch 3 Apply ohm meter leads across switch You should have continuity on a good switch Step 11 Copeland Scroll Compressor R 410A Refrigerant The compressor used in this product is specifically designed to operate with R 410A refrigerant and cannot be ...

Page 23: ...er from the system Heat from unsweating will release moisture and contaminants from drier into system R 410A Refrigerant Charging Refer to unit information plate and charging chart Some R 410A refrigerant cylinders contain a dip tube to allow liquid refrigerant to flow from cylinder in upright position For cylinders equipped with a dip tube charge R 410A units with cylinder in upright position and...

Page 24: ...r driers with rated working pressures less than 600 psig S Do not leave R 410A suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all filter driers and service valves with wet cloth when braz...

Page 25: ...citor Replace Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Low refrigerant charge Locate leak repair and recharge Mechanical damage in compressor Replace compressor Air in system Recover refrigerant evacuate system ...

Page 26: ...OUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE ___________DB RETURN AIR TEMPERATURE ___________DB ___________WB COOLING SUPPLY AIR ___________DB ___________WB HEAT PUMP SUPPLY AIR ___________ GAS HEAT ...