UNIT INTRODUCTION

This unit is a small packaged gas heat/electric cooling system that
can utilize

the comfort of gas heating packaged along with

efficient electric air conditioning.

Starting or Shutting Off Unit

NOTE

: Your combination heating/cooling unit is equipped with

an automatic direct spark ignition and power combustion blower.

To start unit gas heat:

Refer to Fig. 2 for location of unit front access panel. Refer to Fig.
3 for location of gas valve. Refer to Fig. 4 while proceeding with

the following steps.

1. Set the temperature selector on room thermostat to the low-

est temperature setting and set system switch to HEAT.

2. Close the external manual gas shutoff valve.
3. Turn off the electrical supply to the unit.
4. Remove the control access panel with a 5/16--in. nut driver.

(See Fig. 2.)

Compressor

Access

Panel

Filter Access Panel

For Accessory Filter Rack

Blower

Access

Panel

Control

Access

Panel

A09213

Fig. 2 -- Unit Access Panel

5. Move the selector switch on the internal gas valve to the

OFF position and wait 5 minutes.

6. Move the selector switch on the internal gas valve to the ON

position.

7. Replace the control access panel.
8. Turn on the electrical supply to unit.
9. Open the external manual gas shutoff valve.

10. Set the temperature selector on room thermostat slightly

above room temperature to start unit. The induced--draft

combustion air fan will start. Main gas valve will open and
main burners should ignite within 5 seconds. If the burner
does not light within 5 seconds, the ignition module will go

into a Retry Mode after a period of approximately 22
seconds (following the 5--second ignition period). If the

burners do not light within 15 minutes of the initial call for
heat, there is a lockout.

11. Set the temperature selector on room thermostat to desired

setting.

FIRE AND EXPLOSION HAZARD

Failure to follow this warning could result in personal

injury, death, and/or property damage.
1. If the main burners fail to light, or the blower fails to

start, shut down gas heating section and call your dealer for

service.

2. Never attempt to manually light the main burners on unit

with a match, lighter, or any other flame. If the electric

sparking device fails to light the main burners, refer to the

following shutdown procedures, then call your dealer as

soon as possible.

!

WARNING

Burners

Gas Valve

Flue Hood

A09043

Fig. 3 -- Gas Heating/Electric Cooling Unit with Access Panel

Removed

T

o shut off unit gas heat:

FIRE,

EXPLOSION,

ELECTRICAL

SHOCK

HAZARD

Failure to follow this warning could result in personal

injury, death, and/or property damage.
Do not turn off the electrical power to unit without first

turning off the gas supply.

!

WARNING

NOTE

: If the unit is being shut down because of a malfunction,

call your dealer as soon as possible.

Should overheating occur or the gas supply fail to shut off, shut

off the external manual gas valve to the unit before shutting off

the electrical supply. Do not use this unit if any part has been under
water. Immediately call a qualified service technician to inspect the

unit and to replace any part of the control system and any gas

control which has been under water.
Refer to Fig. 5 while proceeding with the following steps.

1. Set the temperature selector on room thermostat to lowest

temperature setting and set system SWITCH to OFF.

2. Close the external manual shutoff valve.
3. Turn off the electrical power supply to the unit.
4. Remove the control access panel. (See Fig. 2.)
5. Move the selector switch on the internal gas valve to the

OFF position.

6. Replace the control access panel.

Summary of Contents for PGD3 Series

Page 1: ...f model _____________________________________________ _____________________________________________ _____________________________________________ INSTALLATION INFORMATION Date Installed_______________...

Page 2: ...Only trained and qualified personnel should install repair or service this equipment WARNING FIRE EXPLOSION HAZARD Failure to follow this warning could result in personal injury death and or property...

Page 3: ...rs do not light within 15 minutes of the initial call for heat there is a lockout 11 Set the temperature selector on room thermostat to desired setting FIRE AND EXPLOSION HAZARD Failure to follow this...

Page 4: ...e With the SYSTEM control set to COOL your unit will run in cooling mode until the indoor temperature is lowered to the level you have selected On extremely hot days your unit will run for longer peri...

Page 5: ...301 Specifications are subject to change without notice 55 STEP 1 STEP 2 CL O S E STEP 3 OFF ON MAIN STEP 4 STEP 7 OFF ON MAIN STEP 8 STEP 5 72 STEP 10 STEP 6 STEP 9 O P E N A07662 Fig 4 To Start Unit...

Page 6: ...ject to change without notice 55 STEP 1 STEP 2 CL O S E STEP 3 OFF ON MAIN STEP 4 STEP 6 STEP 5 A07663 Fig 5 To Shut off Unit Gas Heat 90 STEP 1 STEP 2 CL O S E 72 STEP 4 5 OFF ON MAIN STEP 3 A09194 F...

Page 7: ...5 mm 48 090 115 130 1 each 24 x 14 x 1 610 x 356 x 25 mm 24 x 16 x 1 610 x 406 x 25 mm 60 090 115 130 1 each 24 x 16 x 1 610 x 406 x 25 mm 24 x 18 x 1 610 x 457 x 25 mm Units with bent indoor coil To...

Page 8: ...for any required service Electrical Controls and Wiring Electrical controls are difficult to check without proper instrumentation If there are any discrepancies in the operating cycle contact your lo...

Page 9: ...r connection 11 Inspection for leaks in the refrigerant circuit Pressure check to determine appropriate refrigerant charge 12 Operational check of the unit to determine working conditions Repair or ad...

Page 10: ...10 50902340301 Specifications are subject to change without notice Copyright 2016 International Comfort Products Lewisburg TN 37091 USA Replaces 50902340300...

Reviews: