International comfort products PAN324 Installation Instructions Manual Download Page 9

9

NOTE

: The design and installation of the duct system must

be in accordance with the standards of the NFPA for

installation of nonresidence--type air conditioning and

ventilating systems, NFPA 90A or residence--type, NFPA

90B; and/or local codes and ordinances.

FIGURE 7

Supply and Return Duct Opening

SUPPLY

DUCT

OPENING

RETURN

DUCT

OPENING

VENT HOOD

SHIPPING

LOCATION

FIGURE 8

Vertical Duct Cover Removed

DUCT COVERS REMOVED

Adhere to the following criteria when selecting, sizing, and

installing the duct system:

1. Units are shipped for horizontal duct installation (by

removing duct covers).

2. Select and size ductwork, supply--air registers, and

return--air grilles according to American Society of

Heating, Refrigeration and Air Conditioning Engineers

(ASHRAE) recommendations.

3. Use flexible transition between rigid ductwork and unit

to prevent transmission of vibration. The transition may

be screwed or bolted to duct flanges. Use suitable

gaskets to ensure weather--tight and airtight seal.

4. All units must have field--supplied filters or accessory

filter rack installed in the return--air side of the unit.

Recommended sizes for filters are shown in Table 1.

5. Size all ductwork for maximum required airflow (either

heating or cooling) for unit being installed. Avoid abrupt

duct size increases or decreases or performance may

be affected.

6. Adequately insulate and weatherproof all ductwork

located outdoors. Insulate ducts passing through

unconditioned space, and use vapor barrier in

accordance with latest issue of Sheet Metal and Air

Conditioning

Contractors

National

Association

(SMACNA) and Air Conditioning Contractors of

America (ACCA) minimum installation standards for

heating and air conditioning systems. Secure all ducts

to building structure.

7. Flash, weatherproof, and vibration isolate all openings

in building structure in accordance with local codes and

good building practices.

Step 8—Install Electrical Connections

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
The unit cabinet must have an uninterrupted, unbroken

electrical ground. This ground may consist of an

electrical wire connected to the unit ground screw in the

control compartment, or conduit approved for electrical

ground when installed in accordance with NEC,

ANSI/NFPA

American

National

Standards

Institute/National Fire Protection Association (latest

edition) (in Canada, Canadian Electrical Code CSA

C22.1) and local electrical codes.

!

WARNING

UNIT COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in damage to the

unit being installed.
1. Make all electrical connections in accordance with

NEC ANSI/NFPA (latest edition) and local electrical

codes governing such wiring. In Canada, all

electrical connections must be in accordance with

CSA standard C22.1 Canadian Electrical Code Part

1 and applicable local codes. Refer to unit wiring

diagram.

2. Use only copper conductor for connections between

field--supplied electrical disconnect switch and unit.

DO NOT USE ALUMINUM WIRE.

3. Be sure that high--voltage power to unit is within

operating voltage range indicated on unit rating

plate.

4. Do not damage internal components when drilling

through any panel to mount electrical hardware,

conduit, etc.

!

CAUTION

HIGH--VOLTAGE CONNECTIONS

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before making any wiring changes,

make sure

the gas

supply is switched off first.

Then

switch off the power

supply to the unit and install lockout tag.

!

WARNING

Summary of Contents for PAN324

Page 1: ...ner Weights 7 Connect Condensate Drain 8 Install Duct Connections 8 Install Electrical Connections 9 10 PRE START UP 11 START UP 11 Check for Refrigerant Leaks 11 Start Up Adjustments 11 Wiring Diagra...

Page 2: ...Before installing or servicing system turn off power supply to the unit and install lockout tag There may be more than one disconnect switch Turn off accessory heater power switch if applicable WARNI...

Page 3: ...tal applications unit is provided with flanges on the horizontal openings All ductwork should be secured to the flanges Insulate and weatherproof all external ductwork joints and roof openings with co...

Page 4: ...Failure to follow this warning could result in personal injury death or property damage Rigging bracket MUST be under the rain lip to provide adequate lifting WARNING PROPERTY DAMAGE HAZARD Failure to...

Page 5: ...355 6 BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS...

Page 6: ...BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OT...

Page 7: ...00 1000 1200 1400 1600 1750 FIGURE 5 Unit Corner Weight lbs and Rigging 1 2 4 3 Rigging Brackets are factory installed on 3 phase units only Single phase units require accessory kit NPLIFTBK003A10 COR...

Page 8: ...sistant material connector between ductwork and unit discharge connection If flexible duct is used insert a sheet metal sleeve inside duct Heat resistant duct connector or sheet metal sleeve must exte...

Page 9: ...tandards for heating and air conditioning systems Secure all ducts to building structure 7 Flash weatherproof and vibration isolate all openings in building structure in accordance with local codes an...

Page 10: ...can Wire Gage AWG color coded insulated 35 C minimum wires to make the controlvoltage connections between the thermostat and the unit If the thermostat is located more than 100 ft 30 5 m from the unit...

Page 11: ...and handling carefully straighten fins with a fin comb 4 Verify the following conditions a Make sure that condenser fan blade is correctly positioned in fan orifice Top 1 3 of condenser fan blade sho...

Page 12: ...12 FIGURE 11 PAN324 60 Wiring Diagram...

Page 13: ...C lower than required suction tube temperature NOTE If the problem causing the inaccurate readings is a refrigerant leak refer to Check for Refrigerant Leaks section INDOOR AIRFLOW AND AIRFLOW ADJUST...

Page 14: ...l for cooling from the room thermostat Table 4 Cooling Charging Chart Table 5 PAN3 Wet Coil Pressure Drop in wc UNIT SIZE STANDARD CFM S C F M 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 17...

Page 15: ...095 2026 1962 1887 1817 1748 1679 1583 1439 High Watts 1012 993 981 963 948 927 904 886 846 CFM 2184 2109 2036 1963 1886 1812 1729 1647 1496 Air delivery values are without air filter and are for dry...

Page 16: ...ot to disturb balance weights clips on blower wheel vanes c Remove caked on dirt from wheel and housing with a brush Remove lint and or dirt accumulations from wheel and housing with vacuum cleaner us...

Page 17: ...ollow this warning could result in property damage personal injury or death System under pressure Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all servi...

Page 18: ...ctive run start capacitor overload or start relay Determine cause and replace Faulty outdoor fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor o...

Page 19: ...R AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE __...

Reviews: