background image

440 04 4311 08

Specifications are subject to change without notice.

2

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service,

maintenance, or use can cause explosion, fire, electrical shock,

or other conditions which may cause death, personal injury, or

property damage. Consult a qualified installer, service agency,

or your distributor or branch for information or assistance. The

qualified installer or agency must use factory

authorized kits or

accessories when modifying this product. Refer to the individual

instructions packaged with the kits or accessories when

installing.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Use quenching cloth for brazing operations.

Have fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions included in

literature and  attached to the unit. Consult local building codes,

the current editions of the National Fuel Gas Code (NFCG)

NFPA 54/ANSI Z223.1, and the National Electrical Code (NEC)

NFPA 70.
In Canada refer to the current editions of the National standards

of Canada CAN/CSA

B149.1 and .2 Natural Gas and Propane

Installation Codes, and Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety

alert symbol

. When you see this symbol on the unit and in instructions or

manuals, be alert to the potential for personal injury.

Understand these signal words; DANGER, WARNING, and

CAUTION. These words are used with the safety

alert symbol.

DANGER identifies the most serious hazards which 

will 

result in

severe personal injury or death. WARNING signifies hazards

which 

could 

result in personal injury or death. CAUTION is used

to identify unsafe practices which 

may 

result in minor personal

injury or product and property damage. NOTE is used to

highlight suggestions which 

will

 result in enhanced installation,

reliability, or operation.

!

WARNING

PERSONAL INJURY, AND/OR PROPERTY

DAMAGE HAZARD

Failure to carefully read and follow this warning could

result in equipment malfunction, property damage,

personal injury and/or death.

Installation or repairs made by unqualified persons could

result in equipment malfunction, property damage,

personal injury and/or death.

The information contained in this manual is intended for

use by a qualified service technician familiar with safety

procedures and equipped with proper tools and test

instruments.

Installation must conform with local building codes and

with the Natural Fuel Gas Code (NFCG) NFPA 54/ANSI

Z223.1, and National standards of Canada

CAN/CSA

B149.1 and .2 Natural Gas and Propane

Installation Codes.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could cause personal

injury or death.
Before performing service or maintenance operations

on unit, always turn off main power switch to unit and

install lockout tag. Unit may have more than one power

switch.

!

WARNING

CARBON MONOXIDE POISONING AND FIRE

HAZARD

Failure to follow safety warnings could result in personal

injury, death, and/or property damage.
This furnace is not designed for use in mobile homes,

trailers or recreational vehicles.

!

CAUTION

CUT HAZARD

Failure to follow this caution may result in damage

personal injury.
Sheet metal parts may have sharp edges or burrs. Use

care and wear appropriate protective clothing, safety

glasses and gloves when handling parts and servicing

furnaces.

Summary of Contents for F9MXE0401410A

Page 1: ...uct labels The signal word WARNING is used throughout this manual in the following manner Safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury TABLE OF CONTENTS START UP ADJUSTMENT AND SAFETY CHECK 4 PRIME CONDENSATE TRAP WITH WATER 4 PURGE GAS LINES 4 ADJUST TEMPERATURE RISE 10 ADJUST BLOWER OFF DELAY HEAT MODE 11 AD...

Page 2: ...death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation WARNING PERSONAL INJURY AND OR PROPERTY DAMAGE HAZARD Failure to carefully read and follow this w...

Page 3: ...stream of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Check in box the Blower OFF Delay Jumper Heating Position for Fan Time OFF Setting 1 and 2 2 and 3 3 and 4 5 and 6 90 120 150 180 Calculated Input BTU Rate See Checks and Adjustments Section Heating Check Measured Line Pressure During Heat Measured Manifold Pressure Heat Temperature of Supply Air Heat T...

Page 4: ... switch CAUTION Before operating furnace check flame rollout manual reset switch for continuity If necessary press button to reset switch EAC 1 115vac terminal is energized whenever blower operates HUM 24vac terminal is only energized the draft inducer is energized in heating Prime Condensate Trap with Water CARBON MONOXIDE POISONING HAZARD Failure to follow these warnings could result in personal...

Page 5: ...T M PERCENT OF DERATE DERATE MULTIPLIER FACTOR 0 2000 0 610 0 1 00 2001 3000 610 914 4 6 0 95 3001 4000 914 1219 6 8 0 93 4001 5000 1219 1524 8 10 0 91 5001 6000 1524 1829 10 12 0 89 6001 7000 1829 2134 12 14 0 87 7001 8000 2134 2438 14 16 0 85 8001 9000 2438 2743 16 18 0 83 9001 10 000 2743 3048 18 20 0 81 Derate multiplier factors are based on midpoint altitude for altitude range NOTE For Canadi...

Page 6: ...ove regulator adjustment cap from gas valve pressure regulator See Figure 3 and turn adjusting screw 3 16 or smaller flat tipped screwdriver counterclockwise out to decrease input rate or clockwise in to increase input rate NOTICE DO NOT set low heat manifold pressure less than 2 8 in w c 697 Pa or more than 3 8 in w c 947 Pa for natural gas If required manifold pressure is outside this range chan...

Page 7: ...4VAC CONNECTIONS EAC TERMINAL 115 VAC 1 0 AMP MAX COOL SPARE2 SPARE1 COM BLUE 115 VAC L2 NEUTRAL CONNECTIONS 24 V THERMOSTAT TERMINALS HUMIDIFIER TERMINAL 24 VAC 0 5 AMP MAX 3 AMP FUSE LED OPERATION DIAGNOSTIC LIGHT 24VAC RED BLOWER SPEED SELECTION TERMINALS BL 1 XFMR Y1 DHUM HEAT OFF DELAY 120 180 90 150 ÏÏ ÏÏ ÏÏ ÏÏ ÏÏ ÏÏ ÏÏ NEUTRAL L2 115 VAC L1 CONNECTIONS L1 IND P2 HOT SURFACE IGNITOR HSI INDU...

Page 8: ...0 300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120 240 600 80 45 90 225 31 116 232 581 82 44 88 220 32 113 225 563 84 43 86 214 33 109 218 545 86 42 84 209 34 106 212 529 88 41 82 ...

Page 9: ... 3 42 3 4 42 3 5 42 3 6 3001 800 43 3 8 42 3 2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3 1 44 3 2 44 3 3 44 3 4 750 42 3 3 42 3 4 42 3 5 42 3 6 4001 775 43 3 7 43 3 8 42 3 3 42 3 4 1220 800 43 3 5 43 3 6 43 3 7 43 3 8 825 44 3 8 43 3 4 43 3 5 43...

Page 10: ...n may result in S Overheating the heat exchangers or condensing flue gases in heat exchanger areas not designed for condensate S Shortened furnace life S Component damage Temperature rise must be within limits specified on furnace rating plate Recommended operation is at midpoint of rise range or slightly above CAUTION Jumper R to W to check gas heat temperature rise Do not exceed temperature rise...

Page 11: ...ected to thermostat sub base terminals R and W The thermostat anticipator should NOT be in the circuit while measuring current 1 Remove thermostat from sub base or from wall 2 Connect an amp meter across the R and W sub base terminals or R and W wires at wall 3 Record amp draw across terminals when furnace is in low heat and after blower starts 4 Set heat anticipator on thermostat per thermostat i...

Page 12: ...OTTOM or TWO SIDES 4 5 Gray 2290 2225 2155 2090 2015 1930 1845 1750 1640 1515 Yellow 1810 1760 1725 1685 1640 1600 1555 1520 1480 1415 Blue 1385 1340 1285 1240 1200 1140 1090 1050 995 950 Orange 1560 1520 1475 1430 1385 1335 1295 1240 1200 1150 Red 1055 985 910 860 795 750 680 615 565 495 1002120 BOTTOM or TWO SIDES 4 5 Gray 2340 2295 2250 2195 2110 2030 1935 1835 1725 1605 Yellow 1950 1900 1855 1...

Page 13: ... to follow this caution may result in environmental pollution Remove and recycle all components or materials i e oil refrigerant control board etc before unit final disposal CAUTION ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death or property damage Before installing modifying or servicing system main electrical disconnect switch mus...

Page 14: ...ooting Status codes can be viewed at the indicator in blower door The green furnace control LED is either ON heartbeat off or a code composed of 1 or 2 digits The first digit is the number of short flashes the second digit is the number of long flashes Figure 7 Heating and Cooling Application Wiring Diagram with Single Stage Thermostat 115 V FIELD SUPPLIED DISCONNECT AUXILIARY J BOX 24 V TERMINAL ...

Page 15: ...ing thermostat setting below room temperature 7 Verify that furnace restarts by raising thermostat setting above room temperature Care and Maintenance FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury death and or property damage Never store flammable or combustible materials on near or in contact with the furnace such as 1 Spray or aerosol cans rags brooms du...

Page 16: ...lectrical supply to furnace 2 Remove filter cabinet door 3 Slide filter out of cabinet 4 If equipped with permanent washable filter clean filter by spraying cold tap water through filter in opposite direction of airflow Rinse filter and let dry Oiling or coating of the filter is not recommended 5 If equipped with factory specified disposable media filter replace only with a factory specified media...

Page 17: ...rientation and cutoff plate location to ensure proper reassembly d Remove screws securing cutoff plate and remove cutoff plate from housing e Remove bolts holding motor mounts to blower housing and slide motor and mounts out of housing f Remove blower wheel from housing g Clean wheel per instructions on degreaser cleaner Do not get degreaser in motor 8 Reassemble motor and blower wheel by reversin...

Page 18: ...forming any maintenance or service Follow the operating instructions on the label attached to the furnace WARNING Refer to Figure 9 1 Disconnect power at external disconnect fuse or circuit breaker 2 Turn off gas at external shut off or gas meter 3 Remove control door and set aside 4 Turn electric switch on gas valve to OFF 5 Disconnect the gas pipe from gas valve and remove pipe from the furnace ...

Page 19: ...rature Only check resistance when the igniter is at room temperature a Using an ohm meter check resistance across both igniter leads in connector b Cold reading should be between 40 ohms and 70 ohms 5 Remove igniter assembly a Using a 1 4 in driver remove the two screws securing the igniter mounting bracket to the burner assembly See Figure 9 b Carefully withdraw the igniter and bracket assembly t...

Page 20: ...ric switch on gas valve and at external shut off or meter 10 Turn power on at external disconnect fuse or circuit breaker 11 Run the furnace through two complete heating cycles to check for proper operation 12 Install control door when complete Checking Heat Pad Operation If Applicable In applications where the ambient temperature around the furnace is 32_F 0_C or lower freeze protection measures ...

Page 21: ...erty or product damage CAUTION Since the furnace uses a condensing heat exchanger some water will accumulate in the unit as a result of the heat transfer process Therefore once it has been operated it cannot be turned off and left off for an extended period of time when temperatures will reach 32_F 0_C or lower unless winterized Follow these procedures to winterize your furnace UNIT COMPONENT DAMA...

Page 22: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MXE Specifications subject to change without notice 22 440 04 4311 08 Figure 14 Service Label 338312 2 Rev F ...

Page 23: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MXE Specifications subject to change without notice 440 04 4311 08 23 Figure 15 Wiring Diagram 338312 2 Rev F ...

Page 24: ... Sequence Gas valve and humidifier will not be turned on Inducer motor will start and remain on until the end of the blower test then off The following components are on for 10 15 seconds each individually hot surface igniter blower speeds FAN if present HEAT COOL Was there a previous status code Go to section below for the flashed status code Does the control respond to W Y1 Y Y2 and G 24V thermo...

Page 25: ...wer start the component test Does the igniter glow orange white by the end of the 15 second warm up period Unplug igniter harness from control and repeat component test Check for 115V between connector P2 HSI and NEUTRAL L2 on the control Was 115V present for the 15 second period Check connections and retry If current is near typical value 4 0 6 0μA DC nominal and burners will not stay on replace ...

Page 26: ...ate the inducer motor IDM until flame is no longer proved e Blower On Delay If the burner flame is proven the blower motor is energized on HEAT speed 25 seconds after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC 1 AMP is energized and remains energized as long as the blower motor BLWM is energized f Heat Off Delay When the thermostat is satisfied the R to W ...

Page 27: ... When the R to G circuit is opened the blower motor BLWM will continue operating for an additional 5 seconds if no other function requires blower motor BLWM operation 5 Heat pump See Figure 17 Figure 23 for thermostat connections When installed with a heat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles When the R to W ...

Page 28: ...4 4311 08 Figure 17 ECM Single Stage Furnace with Single Stage Air Conditioner NOTE 9 Figure 18 ECM Single Stage Furnace with Two Stage Air Conditioner NOTE 9 Figure 19 ECM Single Stage Furnace with Two Stage Heat Pump Dual Fuel NOTE 9 Figure 20 ECM Single Stage Furnace with Single Stage Heat Pump Dual Fuel NOTE 9 ...

Page 29: ...ment Installation Instructions for additional information and setup procedure 2 Outdoor Air Temperature Sensor must be attached in all dual fuel application 3 Refer to ICP thermostat Installation Instructions for additional information and setup procedure 4 When using a Humidity Sensing Thermostat set DEHUMIDIFY OPTIONS to H DE ENRGZD FOR DEHUM 5 HUM 24VAC terminal is 24 VAC and is energized when ...

Page 30: ...lector box Condensate trap Condensate trap elbow Gaskets WARNING FIRE EXPLOSION ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in dangerous operation personal injury death or property damage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions...

Page 31: ...riable Speed X ECM S Single stage T Two stage FEATURE B Base AFUE Efficiency E Extra AFUE Efficiency C Communicating D Dual Certified 2 pipe or 1 pipe R 2 pipe only S Single stage T Two stage N Standard L Low Nox FEATURE 040 40 000 BTU hr 060 60 000 BTU hr 080 80 000 BTU hr 100 100 000 BTU hr 120 120 000 BTU hr INPUT HEAT 14 14 3 16 17 17 1 2 21 21 24 24 1 2 CABINET WIDTH 10 1000 CFM max 14 1400 C...

Reviews: