INSTALLATION INSTRUCTIONS
Gas Furnace: (F/G)9MVE
440 01 4401 02
53
Specifications subject to change without notice.
Table 14
MAXIMUM EQUIVALENT VENT LENGTH
- Feet (Meters)
Note:
Maximum Equivalent Vent Length (MEVL) does NOT include elbows or terminations
−
DEDUCTIONS FROM MEVL to determine allowable vent length for each application.
Unit Size
40,000
Outlet choke
required under
10 ft. TEVL
60,000
80,000
100,000
120,000
140,000
Altitude (feet)
Pipe Dia. (in)
1 ½
2
2 ½
1 ½
2
2 ½
3
1 ½
2
2 ½
3
4
2
2 ½
3
4
2 ½
3
4
2 ½
3
4
02000
40
155
185
20
100
175
200
15
50
130
175 200
20
80
175 200
10
75 185
5
65 155
20013000
35
150
175
95
165
185
10
45
125
165 185
15
75
165 185
70 175
N/A
60
140
30014000
30
135
160
15
90
155
175
115
155 175
155
175
5
65 165
120
40014500
25
130
155
85
150
170
40
110
150 165
10
70
170
N/A
60
160
50 110
45015000
125
145
80
165
145 160
65
150 165
45 100
50016000
20
120
130
75
140
155
35
100
135 150
140 155
155
35
80
60017000
15
110
120
10
70
130
145
N/A
30
90
125 140
60
135 145
50 140
30
65
70018000
10
100
110
65
120
135
120 125
N/A
55
125 135
45 130
25
45
80019000
90
95
5
60
115
125
25
80
110 115
50
115 125
40 120
15
30
900110000
5
80
85
N/A
55
105
115
20
75
100 105
45
100 115
30 115
10
15
Unit Size
40,000
Outlet choke
required under 10
ft. TEVL
60,000
80,000
100,000
120,000
140,000*
Altitude (meters)
Pipe Dia.
(mm)
38
51
64
38
51
64
76
38
51
64
76
102
51
64
76
102
64
76
102
64
76
102
0610
11
57
57
6.5
31
54
61
3
16
40
54
61
6
25
54
61
3
23
57
1.5
21
48
611914
10
53
53
29
51
57
2
15
38
51
57
5
23
51
57
21
54
N/A
18
42
9151219
9
49
49
5
27
48
54
36
48
53
48
54
1.5
20
51
36
12201370
8
47
47
26
46
52
13
34
46
51
3
22
52
N/A
19
50
16
33
13711524
45
45
24
51
45
50
21
46
51
14
31
15251829
6
41
41
22
43
47
11
31
42
46
43
48
48
11
25
18302134
5
37
37
3
25
40
44
N/A
10
27
39
42
19
41
45
16
43
9
20
21352438
3.5
33
34
20
37
42
36
39
N/A
18
38
42
14
40
7
15
24392743
30
30
1.5
19
35
38
8
26
34
36
15
36
39
13
38
5
10
27443048
1.5
26
26
N/A
17
33
36
7
24
31
33
14
34
36
12
35
3.5
5
*
Not all families have these models
Table 15
DEDUCTIONS FROM MAXIMUM EQUIVALENT VENT LENGTH
- Feet (Meters)
Pipe Diameter (in):
11/2
2
21/2
3
4
Mitered 90º Elbow
8
(2.4)
8
(2.4)
8
(2.4)
8
(2.4)
8
(2.4)
Medium Radius 90º Elbow
5
(1.5)
5
(1.5)
5
(1.5)
5
(1.5)
5
(1.5)
Long Radius 90º Elbow
3
(0.9)
3
(0.9)
3
(0.9)
3
(0.9)
3
(0.9)
Mitered 45º Elbow
4
(1.2)
4
(1.2)
4
(1.2)
4
(1.2)
4
(1.2)
Medium Radius 45º Elbow
2.5
(0.8)
2.5
(0.8)
2.5
(0.8)
2.5
(0.8)
2.5
(0.8)
Long Radius 45º Elbow
1.5
(0.5)
1.5
(0.5)
1.5
(0.5)
1.5
(0.5)
1.5
(0.5)
Tee
16
(4.9)
16
(4.9)
16
(4.9)
16
(4.9)
16
(4.9)
Concentric Vent Termination
NA
0
(0.0)
NA
0
(0.0)
NA
Standard Vent Termination
0
(0.0)
0
(0.0)
0
(0.0)
0
(0.0)
0
(0.0)
Figure 64
Elbows Configurations
LONG
MEDIUM
MITERED
L11F082
Figure 65
Vent Terminal Configurations
L11F083
CONCENTRIC
A13110
STANDARD 2
−
IN.,
3
−
IN. OR OPTIONAL
4
−
IN. TERMINATION
NOTES:
1. Use only the smallest diameter pipe possible for venting. Over
−
sizing may cause flame disturbance or excessive vent terminal
icing or freeze
−
up.
2. NA = Not allowed. Pressure switch will not close, or flame disturbance may result.
3. Total equivalent vent lengths under 10 ft. for 40k BTUH furnaces from 0 to 2000 ft (0 to 610m) above sea level require use of
an inducer outlet choke. Failure to use an outlet choke may result in flame disturbance or flame sense lock
−
out.
4. Not all furnace families include 140,000 BTUH input models.
5. Vent sizing for Canadian installation over 4500 ft. (1370 m) above sea level are subject to acceptance by local authorities having
jurisdiction.
6. Size both the combustion air and vent pipe independently, then use the larger size for both pipes.
7. Assume two 45
°
degree elbows equal one 90
°
degree elbow. Wide radius elbows are desirable and may be required in some
cases.
8. Elbow and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow
count.
9. The minimum pipe length is 5 (1.5) linear feet (meters) for all applications.
10. Use 3
−
in (76 mm) diameter vent termination kit for installations requiring a 4
−
in (102 mm) diameter pipe.