International comfort products CXH5 Installation Instructions Manual Download Page 8

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pump

8

428 01 5106 00

F. SERVICE VALVES

Service valves are closed and plugged from the factory.

Outdoor units are shipped with a refrigerant charge

sealed in the unit. Leave the service valves closed until all

other refrigerant system work is complete or the charge

will be lost. Leave the plugs in place until line set tubing is

ready to be inserted.
Heat pumps require a piston metering device in the liquid

service valve for proper heating operation. Piston is

shipped in the piston body of the liquid service valve,

temporarily held in place with a plastic cap. Do not remove

the plastic cap until line set tubing is ready to be installed.
Refer to Figure 7 and follow these steps for piston

installation:

1. Remove plastic cap holding piston in piston body of

liquid service valve.

2. Check that piston size (stamped on side of piston)

matches with number listed on unit rating plate.

Return piston to piston body of liquid service valve

(either direction).

3. Find plastic bag taped to unit containing copper

adapter tube, brass nut, and plastic washer.

4. Install plastic washer in the seat inside piston body.
5. Fit brass nut onto adapter tube and install tube

onto liquid service valve. Tighten nut finger tight,

then wrench additional 

½

 turn only. Over tightening

may damage the plastic washer.

Service valve bodies are brass and suction tube stub is

copper.

Figure 7

Liquid Service Valve with Heating

Piston and Adapter Tube

PISTON BODY

LIQUID SERVICE VALVE

PISTON

PLASTIC WASHER

ADAPTER TUBE

BRASS NUT

Vapor Service Valve

VALVE CORE

SERVICE VALVE

G. BRAZING CONNECTIONS

NOTE:

For Liquid Service Valve 

 Braze lineset to adapter tube

BEFORE bolting adapter to valve.  This helps prevent

overheating and damage to plastic washer or o

ring.

For Vapor Service Valve 

 remove valve core from

schrader port on Service Valve BEFORE brazing.  This

helps prevent overheating and damage to valve seals

(refer to Figure 7). Replace valve core when brazing is

completed.

!

WARNING

FIRE HAZARD
Failure to remove refrigerant and oil charge before

brazing could result in personal injury, death, and/

or property damage.
Refrigerant and oil mixture could ignite and burn

as it escapes and contacts brazing torch. Make

sure the refrigerant charge is properly removed

from both the high and low sides of the system be-

fore brazing any component or lines.

Clean line set tube ends with emery cloth or steel brush.

Remove any grit or debris.
Insert line set tube ends into service valve tube stubs.
Apply heat absorbing paste or heat sink product between

service valve and joint. Wrap service valves with a heat

sinking material such as a wet cloth.
Braze joints using a Sil

Fos or Phos

copper alloy.

!

CAUTION

PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product

damage.
Braze with Sil

Fos or Phos

copper alloy on cop-

per

to

copper joints and wrap a wet cloth around

rear of fitting to prevent damage to TXV.

Summary of Contents for CXH5

Page 1: ...gnal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Saf...

Page 2: ...kes vents or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit Loc...

Page 3: ...6 152mm 24 610mm Service Wall Wall Wall 6 152mm 6 152mm Post Wall Wall 18 457mm 18 457mm 18 457mm 18 152mm 6 152mm 6 152mm 6 152mm 18 457mm 18 457mm 18 457mm 18 457mm 24 610mm Service 24 610mm Servic...

Page 4: ...se levels are required Supporting structure or platform for the unit must be level If installation is on a flat roof locate unit minimum 6 inches 152mm above roof level Place the unit over one or more...

Page 5: ...ng operation Heat pumps also use an outdoor piston for heating operation refer to section F Check piston size shipped with indoor unit to see if it matches required indoor piston size shown on outdoor...

Page 6: ...ne in the field use dehydrated or dry sealed deoxidized copper refrigeration tubing Do not use copper water pipe Do not remove rubber plugs or caps from copper tubing until connections are ready to be...

Page 7: ...OOR WALL INDOOR WALL LIQUID TUBE SUCTION TUBE INSULATION CAULK HANGER STRAP AROUND SUCTION TUBE ONLY JOIST 1 25mm MIN THROUGH THE WALL SUSPENSION CAUTION UNIT OPERATION HAZARD Failure to follow this c...

Page 8: ...and suction tube stub is copper Figure 7 Liquid Service Valve with Heating Piston and Adapter Tube PISTON BODY LIQUID SERVICE VALVE PISTON PLASTIC WASHER ADAPTER TUBE BRASS NUT Vapor Service Valve VA...

Page 9: ...free of air and water Watch the vacuum gauge as the system is pulling down The response of the gauge is an indicator of the condition of the system refer to Figure 8 With no leaks in the system allow...

Page 10: ...the main remote electrical disconnect device There may be more than one disconnect device Supply voltage must be 208 230 volts 197 volt minimum to 253 volts maximum 60 Hz single phase Outdoor units ar...

Page 11: ...ALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W 3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2 C Y O R W 2 SUBBASE THE...

Page 12: ...the defrost thermostat itself will not be observed Skip to 3 2 Use a volt meter to confirm there is no voltage across the DFT leads 24 volts across the SFT terminals indicates an OPEN defrost thermos...

Page 13: ...Defrost Control Board R8 OF1 K1 O1 R21 C2 R6 H9C1 C US R14 R13 D13 R7 C4 C10 JW2 JW1 D3 C16 C7 R28 D6 JW3 C13 R4 R1 R2 R3 R11 R5 R26 D1 D2 D10 A29 R9 D4 C19 C9 C1 OF2 CEBD430524 01A 5501A P2 1 Y T1 C...

Page 14: ...e below Unit is factory charged for 15 feet 4 6m of lineset Adjust charge by adding or removing 0 6 oz ft 17 g mm of 3 8 liquid line above or below 15 feet 4 6 m respectively For standard refrigerant...

Page 15: ...easure suction pressure by attaching an accurate gage to suction valve service port 3 Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to suction line at...

Page 16: ...4 16 18 20 20 20 75 3 11 13 16 18 18 19 82 6 8 12 15 16 17 85 4 7 11 14 15 16 90 4 8 12 14 15 95 6 10 12 14 100 4 8 11 12 105 3 6 9 11 110 5 7 10 115 3 6 8 Optimum performance point 82 F 28 C outdoor...

Page 17: ...84 29 82 28 80 27 308 92 33 90 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88 31 345 100 38 98 37 96 3...

Page 18: ...V F E S A4X24 A 5 3 FVM FCM 4X24 3 5 3 3 FXM4X24 A 5 3 FEM4X24 A 3 3 FS M U 4P24 A TXV 5 3 ED 4X30 EA 4X30 14 17 A 3 EN 4X30 3 3 EHD4X30A 3 3 FEM4 P X 30 A TXV 3 FSA4X30 A 3 FEA4X30 A 3 FXM4X30 A 3 5...

Page 19: ...e 17 Additional Subcooling Tables 15 SEER 13 14 SEER Subcooling Delta from Rating Plate Value Subcooling Delta from Rating Plate Value OUTDOOR UNIT TONNAGE OUTDOOR UNIT TONNAGE EN 4X60 24 3 EHD4X60A 3...

Page 20: ...ROUBLESHOOTING Some models are factory equipped with the Comfort Alertt Diagnostics device in the control box refer to Figure 18 Comfort Alert provides around the clock monitoring for common electrica...

Page 21: ...a tion 4 If low pressure switch present go to Flash Code 1 informa tion Yellow ALERT Flash Code 4 Locked Rotor 1 Run capacitor has failed 2 Low line voltage contact utility if voltage at disconnect is...

Page 22: ...igerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a suction l...

Reviews: