For stand-alone installations, the unit may be surface

mounted inside an indoor enclosure which is

available from Intermatic Incorporated    

. or your

wholesaler.

PANEL MOUNTING—MIL 12E

Cut a square hole 2

5

/

8

” x 2

5

/

8

” (66mm x 66mm) in the

front of the panel. Insert the time switch through the

opening. With screwdriver press down and turn

outer screws (A) until flanges are in position to fasten

the unit in front panel, then release. Insert plugs into

holes as per illustration (B).

Use

1

/

4

” quick connects and make connections in

accordance with the wiring diagram shown and

applicable code requirements.

WIRING

1. Disconnect the power.
2. Wire according to the proper voltage marked on

the unit. Wiring to incorrect voltage will void the

warranty.

3. Connect wiring according to the wiring diagram.

The terminals on the MIL 72A sub-base will

accommodate 10 to 24 AWG wire.

PROGRAMMING

The weekly program dial shows the seven days of

the week and AM/PM imprints for each day. The 24-

hour dial has quarter-hour divisions and AM/PM

indications.
The time switch is set by pushing the captive

trippers to the outer ring position for the entire period

that the load is to be turned ON, i.e., fifteen minutes

for each tripper on the 24-hour dial and 2 hours for

each tripper on the 7-day dial. When the tripper is

pushed to the inside, the switch is in the OFF

position.

SETTING TIME

TO SET THE CURRENT TIME (AND DAY OF

WEEK ON 7 DAY UNITS), TURN THE

MINUTE HAND CLOCKWISE. DO NOT SET

THE TIME BY ROTATING “OUTER” DIAL.

Turn the minute hand clockwise until the day of the

week (7-day timer) and the time of day on the outer

dial is aligned with the triangle marker on the inner

dial (two o'clock position).
Example for 7-day program dial Monday 10:30 AM.

Turn the minute hand clockwise until Monday 10:30

AM is aligned with the triangle on the inner dial. The

hour and minute hand will show exactly 10:30.
Example for 24-hour program dial 10:30 AM. Turn

the minute hand clockwise until 10:30 AM is aligned

with the triangle on the inner dial. The hour and the

minute dial will show exactly 10:30.

MANUAL OVERRIDE

All MIL 72 units are available with an optional 3-way

manual override (type designation “H”).

B

A

3-way manual
override switch

Off position with trippers
pushed in (trippers pushed out
will close contacts 3 and 4 and
turn load on)

I = permanent ON

= automatic

0 = permanent OFF

A

B

Terminal Connections

Indoor Enclosure

158--00539

INTERMATIC INCORPORATED

Spring Grove, IL 60081-9698

www.intermatic.com