2
IDIGITAL — 24-Hour Digital Time Switch
INSTALLATION
Preparing the Time Switch
1. Remove the mechanism from the case by depressing
the catch at the top of the case and pulling out, as
shown in FIG. 1.
2. Set the voltage selector for the desired input voltage.
The Time Switch is shipped with voltage set for 277
VAC.
To operate at 120, 208 or 240 VAC, move the
selector switch to the desired setting as marked
on the circuit board.
See FIG. 2.
3. The timer is shipped with DST (Daylight Saving Time)
enabled. To disable DST, move the jumper from Spare
to DST. See FIG. 2.
4. Decide whether you want to control multiple loads
simultaneously (SIM), independently (IND), or with a
2-second pulse (PUL) (e.g., for use with mechanically
held contactors or bell ringing applications), and make
sure the jumper is positioned accordingly. See location
B in Rear View above and detail at the right. See FIG. 2.
(The unit is shipped with the loads set for IND.)
5. Choose and remove the selected knockout(s) from the
enclosure.
Note:
There are five 1/2
"
to 3/4
"
combination knockouts
available. There are two on the bottom of the
enclosure, one on each side, and one on the rear.
If a 3/4
"
knockout is needed, remove the 1/2
"
knockout first, then the 3/4
"
knockout.
Mounting the Time Switch
1. Mount the enclosure in the desired location using the
three mounting holes provided. Position at eye level if
possible, providing space to the left of the enclosure for
the cover to swing open. See FIG. 3.
2. Replace the mechanism in the enclosure.
Connecting the Wires
1. Lift the left side of the plastic insulator off the retaining
post and pivot it up and away to expose the terminal
strip. See FIG. 4.
2. Strip the supply and load wires to 1/2".
Use #14-#12
AWG wires, rated at least 75°C (167°F)-COPPER
conductors ONLY
.
3. Insert wire ends under proper terminals and tighten
screws to 10.5 lbf-in. See FIG. 5a through FIG. 5d
4. Connect the ground wire to the grounding terminal at
the bottom of the enclosure. See FIG. 4.
5. Replace the plastic insulator on the retaining post.
Note:
If the Time Switch is being powered from a different
circuit than the load, you do not need to install the
jumper wire. If the Time Switch is being powered from
the same circuit as the load, install the jumper wire.
Clear Mem
Clear Entry
BATTERY
MODE
RESET
ENTER
NEXT
+
ON/
OFF
ON/
OFF
-
DT104
FIG. 1
Removing the Mechanism
PU
L
SI
M
IN
D
DS
T
Spare
120V 208V
240V 277V
Back of Timer
Mechanism
FIG. 2
Setting the Voltage, DST, and SIM/IND/PUL
Mounting Hole
FIG. 3
Enclosure Mounting Holes
ON /
OFF
ON /
OFF
Clear Mem
Clear Entry
BATTERY
MODE
RESET
+
–
ENTER
NEXT
Clear Mem
Clear Entry
BATTERY
MODE
RESET
+
–
ENTER
NEXT
ON /
OFF
ON /
OFF
Wire
Terminal
Plastic
Insulator
Ground
Terminal
FIG. 4
Plastic Insulator and Wire Terminals
L2/N
Line 1
1
2
3
4
5
6
Timer Power
ON
OFF
Install jumper only if timer input
and load voltage are the same
120/208/240/277 VAC Input
L2/N
Line 1
1
2
3
4
5
6
Timer Power
Load
1
Load
2
120/208/240/277 VAC Input
L2/N
Line 1
1
2
3
4
5
6
Timer Power
Load
1
Load
2
120/208/240/277 VAC Input
Line 2
Line 2
Line 1
Line 1
1
2
3
4
5
6
Timer Power
Load
Install jumper only if timer input
and load voltage are the same
240 VAC Input
FIG. 5a
DT104 configured for pulse SPST load with jumper set to PUL