IDIGITAL — 24-Hour Digital Time Switch

MODEL DT104

Clear Mem

Clear Entry

BATTERY

MODE

RESET

ENTER

NEXT

+

ON/

OFF

ON/

OFF

-

DT104

SAFETY SECTION

 WARNING

Risk of Fire or Electrical Shock

•  Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
•  Installation and/or wiring must be in accordance with national and local electrical code requirements.
•  This enclosure does not provide grounding between conduit connections. When metallic conduit is used, you must also install grounding type bushings and jumper wire.
•  Use #14-#12 AWG wires, rated at least 75°C (167°F)-COPPER conductors ONLY.
•  If the power disconnect point is out of sight, lock it in the OFF position and tag it to prevent unexpected application power.
•  Make sure there is no wire insulation under the terminal plate on the time switch connector. Firmly tighten terminal screws.
•  Do not remove insulator that is covering terminals.
•  KEEP DOOR CLOSED AT ALL TIMES when not servicing.

NOTICE

•  Do NOT touch circuit board components. Contact can create a static discharge, which can damage the microprocessor.

PRODUCT DESCRIPTION

The Intermatic DT104 Digital 24-Hour Time Switch automatically switches loads to a preset daily schedule with to-the-minute 
accuracy. Use the DT104 as an ON/OFF timer in applications requiring 24-hour load control such as lighting, air conditioning 
systems, pumps, etc. Each load output of the Time Switch can support up to 14 timed ON and 14 timed OFF events per day. 
The program can be overridden by pushing the ON/OFF load override button(s). The DT104 Time Switch is designed to directly 
switch tungsten or ballast loads up to its rating, and inductive or resistive loads up to 20 A at 120, 208, 240 or 277 VAC.

Specifications

Time Switch

•  Input Voltage: 120–277 VAC, 60 Hz
•  Power Consumption: 6.0 W Max.
•  Contact Configuration: 2xSPST or 1xDPST

Switch Ratings

•  20 A Inductive/Resistive, 120/240 VAC
•  20 A Magnetic Ballast, 120-277 VAC
•  1 A Electronic Ballast, 120-277 VAC
•  20 A Resistive, 28 VDC
•  5 A Tungsten: 120/240 VAC
•  1 HP, 120 VAC
•  2 HP, 240 VAC

Set Points (Events)

•  The load output of the Time Switch can support up to 

14 timed ON and 14 timed OFF events per day.

Battery-Powered Clock Operation

•  3 year minimum (uses two AAA industrial-grade  

alkaline nonrechargeable 1.5 V batteries, supplied)

Minimum ON or OFF time

•  1 minute

Maximum ON or OFF time

•  23 hours, 59 minutes

Shipping Weight

•  2.5 lb. (1.1 kg)

Enclosures

•  TYPE 1 indoor metal enclosure

Knockouts

•  Combination 1/2-3/4" size (one on back, one on each 

side, two on bottom)

Wire Size

•  #14-#12 AWG

Summary of Contents for IDIGITAL DT104

Page 1: ...al 24 Hour Time Switch automatically switches loads to a preset daily schedule with to the minute accuracy Use the DT104 as an ON OFF timer in applications requiring 24 hour load control such as lighting air conditioning systems pumps etc Each load output of the Time Switch can support up to 14 timed ON and 14 timed OFF events per day The program can be overridden by pushing the ON OFF load overri...

Page 2: ...e enclosure for the cover to swing open See FIG 3 2 Replace the mechanism in the enclosure Connecting the Wires 1 Lift the left side of the plastic insulator off the retaining post and pivot it up and away to expose the terminal strip See FIG 4 2 Strip the supply and load wires to 1 2 Use 14 12 AWG wires rated at least 75 C 167 F COPPER conductors ONLY 3 Insert wire ends under proper terminals and...

Page 3: ...r to the Time Switch Proceed to the Initial Setup section Note You must reset the Time Switch using this procedure whenever you change the jumpers described in FIG 2 SIM IND PUL or DST To reset the Time Switch press and hold the ENTER button then press the RESET button The screen will flash 12 00 AM and the Time Switch status is Manual Mode Clear Mem Clear Entry BATTERY MODE RESET ENTER NEXT ON OF...

Page 4: ...tton repeatedly to reach the desired menu Then follow the relevant instructions in this sheet LIMITED ONE YEAR WARRANTY This warranty is extended to the original household purchaser only and is not transferable This warranty does not apply to a damage to units caused by accident dropping or abuse in handling acts of God or any negligent use b units which have been subject to unauthorized repair op...

Page 5: ...réglé avec une précision à la minute près Servez vous du modèle DT104 comme d une minuterie d activation désactivation pour les applications qui nécessitent des contrôles de charge pendant 24 h telles que l éclairage les systèmes de climatisation les pompes etc Chaque sortie de charge de la minuterie peut prendre en charge jusqu à 14 cycles d activation et 14 cycles de désactivation par jour Le pr...

Page 6: ...permettre l ouverture du couvercle Voir FIG 3 2 Replacez le mécanisme dans le boîtier Raccordement des fils 1 Levez le côté gauche de l isolant en plastique du support coulissant et faites le pivoter vers le haut pour l écarter afin de pouvoir accéder au bornier Voir FIG 4 2 Dénudez de 12 7 mm 0 5 po les câbles de charge et d alimentation Utilisez des câbles AWG nº 14 nº 12 d une valeur minimale d...

Page 7: ...renseignements brouillés appuyez sur le bouton RESET RÉINITIALISER pour résoudre le problème 3 Mettez sous tension la minuterie Passez à la section Configuration initiale Remarque Vous devez réinitialiser la minuterie en suivant cette procédure à chaque fois que vous changez les cavaliers comme décrit dans FIG 2 SIM IND PUL ou DST Pour réinitialiser la minuterie maintenez enfoncé le bouton ENTER E...

Page 8: ...énements de la minuterie et du circuit à l aide du bouton ON OFF ACTIVER DÉSACTIVER Modification révision des événements programmés Appuyez à plusieurs reprises sur le bouton MODE pour accéder au menu souhaité Suivez ensuite les instructions pertinentes de ce guide GARANTIE LIMITÉE D UN AN Cette garantie couvre uniquement l acheteur initial et n est pas transférable Cette garantie ne s applique pa...

Page 9: ...ntermatic conmuta automáticamente cargas en un programa diario predefinido con precisión de minutos Use el DT104 como un temporizador de encendido apagado en aplicaciones que necesitan 24 horas de control sobre la carga como sistemas de iluminación y aire acondicionado bombas etc Cada salida de carga del interruptor temporizador permite hasta 14 eventos de encendido y 14 eventos de apagado cronome...

Page 10: ...smo en la caja Conectar los cables 1 Levante el lado izquierdo del aislante de plástico del poste de sujeción y gírelo hacia arriba y hacia afuera para exponer la regleta de terminales Consulte FIG 4 2 Pele los cables de alimentación y de carga hasta 1 2 Use cables AWG n º 14 n º 12 con capacidad para por lo menos 75 C 167 F SOLO conductores de COBRE 3 Inserte los extremos del cable debajo de los ...

Page 11: ...n Si la pantalla muestra información desordenada presione el botón RESET REINICIAR para borrarla 3 Aplique energía al interruptor temporizador Continúe a la sección de Ajuste inicial Nota Debe reiniciar el interruptor temporizador usando este procedimiento cuando quiera cambiar los puentes descritos en FIG 2 SIM IND PUL o DST Para restablecer el temporizador mantenga presionado el botón ENTER y lu...

Page 12: ...o el botón ENCENDER APAGAR Editar revisar eventos programados Presione varias veces el botón MODE hasta llegar al menú deseado Luego siga las instrucciones pertinentes en esta hoja GARANTÍA LIMITADA DE UN AÑO Esta garantía se extiende solo al comprador original y no es transferible Esta garantía no se aplica a lo siguiente a daño a las unidades causado por accidente caída o uso indebido en su mani...

Reviews: