background image

277 V

240 V

208 V

120 V

COM

IGN-02

X3

LAMP

X1

X3

COM

CAP

CP150MH (Metal Halide)

Figure 3

277 V

240 V

208 V

120 V

COM

IGN-01

X3

LAMP

X1

X2

COM

CAP

CP150HPS (High Pressure Sodium)

Figure 5

LIMITED 1 YEAR WARRANTY

If within one (1) year from the date of purchase, this product fails due to a defect in material or workmanship, Intermatic Incorporated will repair or replace it, at its sole option, 

free of charge. This warranty is extended to the original purchaser only and is not transferable. This warranty does not apply to: (a) damage to units caused by accident, 

dropping or abuse in handling, acts of God or any negligent use; (b) units which have been subject to unauthorized repair, opened, taken apart or otherwise modified; 

(c) units not used in accordance with instructions; (d) damages exceeding the cost of the product; (e) sealed lamps and/or lamp bulbs; (f) the finish on any portion of the 

product, such as surface and/or weathering, as this is considered normal wear and tear; (g) transit damage, initial installation costs, removal costs, or reinstallation costs.

INTERMATIC  INCORPORATED  WILL  NOT  BE  LIABLE  FOR  INCIDENTAL  OR  CONSEQUENTIAL  DAMAGES.  SOME  STATES  DO  NOT  ALLOW  THE  EXCLUSION 

OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU. THIS WARRANTY 

IS IN LIEU OF ALL OTHER EXPRESS OR IMPLIED WARRANTIES. ALL IMPLIED WARRANTIES, INCLUDING THE WARRANTY OF MERCHANTABILITY AND THE 

WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY MODIFIED TO EXIST ONLY AS CONTAINED IN THIS LIMITED WARRANTY, AND SHALL 

BE OF THE SAME DURATION AS THE WARRANTY PERIOD STATED ABOVE. SOME STATES DO NOT ALLOW LIMITATIONS ON THE DURATION OF AN IMPLIED 

WARRANTY, SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU.

This warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased, or (b) mailing the product, along with proof of pur-

chase, postage prepaid to the authorized service center listed below. This warranty is made by: Intermatic Incorporated/After Sales Service/7777 Winn Rd., Spring Grove, 

Illinois 60081-9698/815-675-7000  http://www.intermatic.com  Please be sure to wrap the product securely to avoid shipping damage. 

158HL13186

THESE INSTRUCTIONS DO NOT COVER ALL VARIATIONS IN EQUIPMENT, NOR DO THEY PROVIDE FOR ALL SITUATIONS 

RELATED TO FIXTURE INSTALLATION, OPERATION OR MAINTENANCE. FOR FURTHER INFORMATION CONTACT YOUR 

DISTRIBUTOR OR INTERMATIC INCORPORATED - SPRING GROVE, ILLINOIS 60081 (815) 675-7000   www.intermatic.com

CP150MHT (Metal Halide w/tri-tap)

Figure 4

CP150HPST (High Pressure Sodium w/tri-tap)

Figure 6

COM

IGN-01

X3

LAMP

X1

X2

COM

CAP

347 V

277 V

120 V

CAP

LAMP

COM

IGN-02

X3

LAMP

X1

X2

COM

CAP

347 V

277 V

120 V

CAP

LAMP

MOUNTING & WIRING (continued)

Feed the matching voltage fixture wire, fixture wire marked 
“COM”, and green fixture grounding wire out of the fixture.
Confirm  all  unused  voltage  fixture  wires  are  appropriately 
capped within fixture body.
Using  provided  twist  on  or  other  approved  connectors, 
connect the fixture wires to the supply wires.

Connect  the  selected  voltage  fixture  wire  to  the  Black 

(hot) supply wire.

Connect  the  White  fixture  wire  marked  “COM”  to  the 

White (neutral) supply wire.

Connect  the  Green  (fixture  ground)  wire  to  the  supply 

grounding wire.

Install  fixture  over  mounting.  Fixture  should  be  mounted 
horizontal. (See Figure 2)
Install reflector and secure with (3) screws.
Screw lamp into lampholder until finger-tight.
Install,  and  secure  lens  cover  with  (4)  screws  making 
sure  that  the  gasket  is  properly  seated.  To  weatherproof 
fixture,  seal  all  holes  in  housing  (mounting  conduit,  plugs, 
photocontrols, etc.) with silicone sealant. 

Alternate wiring:

 If desired connections may be made inside 

fixture using supply wire rating minimum 125°.

5.

6.

7.

a.

b.

c.

8.

9.
10.
11.

To operate, restore power to the circuit and switch light on.

    

CAUTION

  (Metal Halide Lamps Only) 

Do not use lamp beyond manufactures rated life to reduce 
chance of lamp rupture.Turn lamp off at least once for 15 
minutes per week to reduce chance of lamp rupture.

LAMP REPLACEMENT

    

CAUTION

 

Use lamp of correct type and wattage as specified on fixture.

1.  Turn off power at circuit breaker or fuse box. Allow fixture and 

lamp to cool.

2.  Loosen (4) screws and swing hinged fixture lens door open. 

Remove old lamp and replace with new lamp of correct type 
and  wattage.  Screw  lamp  into  socket  in  lampholder  until 
finger-tight.

3.  Close  and  secure  lens  door,  making  sure  that  gasket  is 

properly seated, free of debris, and compressed to seal out 
moisture.

4.  Turn power back on.
5.  Properly dispose of lamp per manufacturer’s 

recommendations.

12.