Testing the reader

1. Power up the reader. Verify the power-on self 

test LED/beep sequence:
- green LED flashes; two short beeps
- yellow LED flashes; three short beeps
- red LED flashes
- yellow LED flashes

2. Verify the yellow LED is on continuously 

indicating the reader is ready. 

3. Present a badge that has been properly 

enrolled in the system. Verify the green LED 
lights and a short beep is heard. 

Removing the cover

To remove the cover, squeeze the sides of the top 
cover and pull to release the cover.

Specifications

The voltage specification for this reader is 5-16 
VDC, although 12 VDC or greater is recommended 
for better performance and cable run distances.
The recommended cable gauge is 18-gauge to 22-
gauge. Check with the cable supplier to determine 
the best choice for the application and installation 
distance.

FCC compliance

The FCC requires the following statement: This 
reader uses radio frequency energy, has been 
tested, and complies with the limits of FCC testing. 
Changes, modifications, or disregard of proper 
installation and instructions not expressly approved 
by UTC Fire & Security are strictly prohibited by the 
FCC and could void the user’s authority to operate 
the equipment.

Ordering information 

Note

: Each part number includes all three colors of the 

cover plates (black, charcoal, gray).

© 25JUL13, United Technologies Corporation 

Interlogix is part of UTC Climate, Controls & Security, a 
unit of United Technologies Corporation. All rights 
reserved. 

The TruPortal product name and logo are trademarks of 
United Technologies. Other trade names used in this 
document may be trademarks or registered trademarks 
of the manufacturers or vendors of the respective 
products.

Document number: 460950002C - July 2013

Colors

Black, Charcoal, Gray

Power supply

Linear DC recommended

Power usage

50 mA @ 12 VDC

Voltage range

5 - 16 VDC

Temperature 
range

a

a. -25

°

F to 125

°

F (32

°

C to 52

°

C)

-31°F to 149°F 
(-35°C to 65°C)

Cable distance to 
panel

b

b. 500 ft. (152.4 m) max. 22 AWG @ 12 VDC 

200 ft. (60.96 m) max. 22 AWG @ 5 VDC

Read Range

c

(Distances may 
vary depending on 
environment.)

c. Vicinity: up to 3.0" (7.62 cm)

- Mifare: 
  up to 1.0" (2.54 cm) 
  Ultralight cards not supported
- Vicinity: up to 3.5" (8.89 cm)

Wiegand output

- Mifare 4002 (40-bit)
- Vicinity 5502 (55-bit)

Regulatory 
approvals and 
standards

UL 294, CE, and FCC (part 15)

ISO Standards

Mifare ISO 14443A
Vicinity ISO 15693

UL evaluation for UL Listed Installations:

Cable Distance 
Max. @ 12 VDC

AWG

200 ft. (60.96 m) 

22

300 ft. (91.44 m) 

20

500 ft. (152.4 m) 

18

Product

Part numbers

T-200 
(3 covers, 18" / 45.7 cm pigtail wire)

TP-RDR-200a

T-200 
(3 covers, 84" / 214 cm pigtail wire)

TP-RDR-200b