Avoid detaching the IADS connection hub either from a control panel, a 
programmable device, or from a PC, when the actual programming or data 
exchange function is in progress 

— it can affect correct and successful operation. 

USB to serial converter mode 

This mode allows to connect ATS control panels, that currently have a 9-pin 
RS232 connector, transparently to a computer (usually a notebook), which are 
mostly equipped only with USB ports. 

The IADS connection hub should be connected via the USB cable to the 
notebook, and via a 9-pin RS232 cable to an ATS control panel.  

Figure 2: USB to serial converter mode 

 

 

Press Mode button on the IADS connection hub, so that the yellow LED is on. 
The IADS connection hub is now in the converter mode. 

After that, it is possible to connect the Titan software to the ATS control panel, to 
manage and configure the panel.  

For further information on programming see appropriate panel programming and 
management manuals, as well as Titan online help system. 

IADS device programming mode 

When using the IADS connection hub in programming mode, use the AdDev 
software from the supplied CD. You can copy the software to the computer hard 
disk, or run it directly from the CD.  

Note: 

To copy the software, copy the application file AdDev102.exe and the 

configuration file AdDev.ini into the same directory. 

No administration privileges are required to copy or run the application.  

  

 

PC 

RS232 

 

ATS panel 

 

USB 

 

IADS connetion 

hub 

Summary of Contents for IADS-PROG

Page 1: ...ned for the following functions It allows to connect computers notebooks desktop PCs etc to ATS control panels creating a bridge between a USB port of the computer and an RS232 connection of the control panel See USB to serial converter mode on page 4 for more details It also allows address programming for addressable detectors or other components for example magnetic contact type MK 46 AD which d...

Page 2: ...connections are described in the corresponding chapter The requirements for running the software are A free USB port One of the following operating systems Windows XP Windows Vista Windows 7 There are no administrator requirements It might be necessary to configure the system or any firewalls security software to allow access to the USB port Please be aware that the first version of Titan supporti...

Page 3: ...onverter mode the green LED means IADS device programming mode The USB plug is used for hooking up the IADS connection hub to the computer via the USB cable which is a part of the package Each time the IADS connection hub has been connected to the USB port of the computer it powers up and performs an internal self test If the internal self test has been successfully performed it automatically swit...

Page 4: ... mode Press Mode button on the IADS connection hub so that the yellow LED is on The IADS connection hub is now in the converter mode After that it is possible to connect the Titan software to the ATS control panel to manage and configure the panel For further information on programming see appropriate panel programming and management manuals as well as Titan online help system IADS device programm...

Page 5: ... exe to run the software Figure 4 AdDev software interface If necessary choose the appropriate language from the Language combo box In the AdDev application choose a correct COM port or search through the COM port list to find the IADS connection hub by pressing Scan Ports During the start up the application will scan all ports and search for the IADS connection hub if connected already State will...

Page 6: ...e problems or behaviour Press Read Device button to read and display the device values in fields Device Name Actual Device Category and Type Press Reset button to reset the application If no device is connected Device Name will show no device and other fields will be blank or 0 If an IADS device is already connected its settings will be displayed accordingly Press Close button to close the AdDev a...

Page 7: ... disclaimers and product safety information please check https firesecurityproducts com policy product warning or scan the QR code Certification European Union directives UTC Fire Security hereby declares that this device is in compliance with the applicable requirements and provisions of the Directive 2014 30 EU and or 2014 35 EU For more information see www utcfireandsecurity com or www interlog...

Page 8: ...8 P N 1070544 EN REV B ISS 11MAR19 ...

Reviews: