ATS1745 Advisor Master IP Bus adaptor installation & Setup Guide
17
Preliminary, not for sales
Problems logging in
If you can see the login window for a particular IP address, but cannot log in with a
known good user name and password, a different user may have been logged in
less than 20 minutes previously and ended the session without logging out. If so,
you will need to wait up to 20 minutes before you can log in. See “Logging out” on
page 11.
If you cannot see the login window for a particular IP address, you may need to
perform a “hard” refresh of the Web browser. This bypasses any cached versions of
the window and displays the current window being served by the ATS1745 module.
To hard refresh the Web browser, simultaneously press the Ctrl and F5 keys.
If you still cannot see the login window, close and restart the Web browser. If
unsuccessful, see “Problems viewing ATS1745 Web pages” on page 16.
Resetting the ATS1745 module
ATS1745 modules are shipped with the following default settings:
IP address 192.168.20.100 for an SLM or 192.168.20.105 for an ELM
(determined by the setting of SW1)
Gateway 0.0.0.0
Netmask 255.255.255.0
Port 3002
User name “admin” with password “password”
You may need to reset an ATS1745 module to its default settings for
troubleshooting purposes or if you cannot log in to the Web interface due to an
incorrect password. Resetting the module erases all programming (including the
assigned IP address) and creates one user name “admin” and password
“password”.
To reset the ATS1745 module:
1. Place a link on the CFG pins (Figure 4 on page 9, item 3).
2. Remove power and then repower the module.
3. Remove the link on the CFG pins.
CONCEPT