![background image](http://html1.mh-extra.com/html/interlogix/ats1745/ats1745_installation-and-setup-manual_2077117018.webp)
10
ATS1745 Advisor Master IP Bus adaptor installation & Setup Guide
Preliminary, not for sales
Figure 6: Wiring details for DB9 connector
Note:
During firmware update, the Advisor Master IP Bus system does not carry
communications between the Advisor Master panel and remote Bus devices.
To update ATS1745 firmware:
1. View the module’s Web interface (Figure 8 on page 12) and note the
currently-loaded firmware version.
2. Remove power to the module.
3. Move SW4 (Figure 4, item 7, on page 2) to the ON position.
4. Connect power to the module.
5. Connect the module’s RS-232 port (Figure 4, item 2, on page 2) to the
computer’s COM port.
6. Start HyperTerminal and open a connection to the Comm port with 115200
bits per second, 8-N-1. HyperTerminal should say "waiting for upgrade .... "
with a few CCCC on screen.
7. Select Send File from the Transfer menu. Select IK Xmodem as the Protocol
and then browse to select the supplied firmware file.
8. Click Send. HyperTerminal opens a Send File window and indicates status.
When finished, HyperTerminal closes the Send File window and indicates
Upgrade Completed.
9. Remove power to the module.
10. Move SW4 (Figure 4, item 2, on page 2) to the OFF position.
11. Connect power to the module.
12. View the module’s Web interface (Figure 8 on page 12) and note the
currently-loaded firmware version. It should display the updated version
number.
CONCEPT
Summary of Contents for ATS1745
Page 26: ...C O N C E P T ...