ATS1197 Smart Card Reader With Keypad 
Installation Sheet 

EN  DE  IT 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EN: Installation Sheet 

Mounting the unit 

1.  Remove power to the control panel, or 4-door DGP, as 

applicable. 

2.  Remove the two front panel screws at the bottom of the 

RAS (see Figure 1), and then remove the RAS back plate. 
Retain the screws to secure the RAS later. 

3.  Position the RAS back plate (with the tamper spring at the 

top) against the mounting surface to determine the 
locations of mounting holes and for cabling access 
(a reduced card reading range may occur if mounted on a 
metal surface).  

4.  Mount the back plate on a flat surface using four screws 

(the hole nearest the tamper spring must have a screw in 
order for the tamper switch to work correctly). 

5.  Terminate the cable, as required (see wiring details 

below). 

6.  For on-line mode, set the BUS address (DIP switches 1 

through 4). For on-line mode, set the TERM switch (DIP 
switch 5) as required. For off-line mode, the TERM switch 
must be off (up). See DIP switch settings for details. 

7.  Mount the RAS on the back plate by engaging the top, and 

then lowering the RAS to be flat against the back plate. 
The rear tamper switch must be sealed for the system to 

work correctly. Ensure that the back plate tamper spring 
rests on the tamper switch actuator (protruding from the 
resin in the back of the RAS) when the RAS is in position. 

8.  Fix the RAS to the back plate using the two screws 

removed earlier from the bottom of the RAS. 

9.  Apply power to the control panel, or the 4-door DGP. 

10.  For online mode, use an LCD RAS on the BUS (or the 

system management software) to program polling and set 
up the required items for the new RAS. In particular, the 
ATS1197 RAS must be programmed as a non-LCD RAS. 

11.  Check that the ATS1197 is communicating correctly and 

verify that the tamper switch is working properly (i.e. "RAS 
Tamper" is not showing on the LCD RAS).  

WARNING: 

All power should be turned off to the control panel 

before wiring the RAS. 

Location of features 

Figure 1 legend 

(1)  Red/Green dual colour LED 
(2)  Yellow LED 

(3)  Red LED 
(4)  Locking screws 

Connecting control panel to keypad RAS 

Refer to the 

ATS Control Panel Installation Guide

 for 

instructions. 

1

2

3

4

5

6

7

8

9

0

#

(4)

(1)

(2)

(3)

RAS 1

RAS 5

RAS 9

RAS 13

RAS 2

RAS 6

RAS 10

RAS 14

RAS 3

RAS 7

RAS 11

RAS 15

RAS 4

RAS 8

RAS 12

RAS 16

( )

2

( )

1

 

Summary of Contents for ATS1197

Page 1: ...s 7 Mount the RAS on the back plate by engaging the top and then lowering the RAS to be flat against the back plate The rear tamper switch must be sealed for the system to work correctly Ensure that the back plate tamper spring rests on the tamper switch actuator protruding from the resin in the back of the RAS when the RAS is in position 8 Fix the RAS to the back plate using the two screws remove...

Page 2: ...buzzer control Wire open or 5 to 12 V buzzer off absolute maximum is 14 V Wire grounded 0 V buzzer on Brown Application depends on selection of RAS menu option 2 Offline LED control See programming Colour Application Yellow Application depends on selection of RAS menu option 2 Offline LED control see programming When not used for two wire LED control yellow wire may be used for RTE input when onli...

Page 3: ... the bus is faulty usually cabling Tx The red Tx LED flashes to indicate the RAS is replying to polling from the control panel If the Rx LED flashes but the Tx LED does not the RAS is not programmed to be polled in the control panel or is addressed incorrectly Configuring the ATS1197 RAS To configure the RAS 1 Press 19 Enter followed by 3 Enter 2 Type the required RAS address 2 to 16 followed by E...

Page 4: ... and disables the use of reader configuration option cards at the reader If an installer wishes to prevent the modification of the reader setup by configuration card this option should be disabled Menu 10 RTE Egress The RAS is fitted with Request To Exit RTE control yellow wire The open collector output violet wire may be used to control a door relay RTE is only available in online mode There are ...

Page 5: ...marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information see www recyclethis info Contact information www utcfireandsecurity com or www interlogix com For customer support see www i...

Page 6: ...nschluss AUX PWR von einer AME oder einer Nebenmelderversorgung Schwarz 0 V Gleichspannung Grün D0 D Clock kann für D0 Wiegand Daten D RS485 Daten Magnetstreifen Clock verwendet werden Normale Betriebsspannung 0 bis 5 V absolutes Maximum 12 V Weiß D1 D Daten kann für D1 Wiegand Daten D RS485 Daten Magnetstreifendaten verwendet werden Normale Betriebsspannung 0 bis 5 V absolutes Maximum 12 V Das BD...

Page 7: ...n damit die Scharfschaltung des Systems an Die Bereiche müssen unscharfgeschaltet werden damit auf die Optionen im Errichterprogrammiermenü zugegriffen werden kann Fehlerbehebung Allgemeine Störungen Keine LED Anzeige oder Hintergrundbeleuchtung für die Tastatur aktiviert Überprüfen Sie sowohl am BDT als auch am Netzteil die Kabelverbindungen für 13 8 und 0 V Spannungsversorgung Überprüfen Sie den...

Page 8: ...der auf Minus 0 V LED 1 grün ein Ader offen oder an 5 bis 14 V LED 1 aus Gelbe und braune Ader auf Minus 0 V LED 1 leuchtet gelb Nicht zulässig bei Verwendung mit UTC Produkten Bei der 1 Draht LED Steuerung steuert die braune Ader die zweifarbige LED 1 grün rot Ader auf Minus 0 V LED 1 grün ein Ader an 5 bis 15 V LED 1 rot ist aktiv Offen oder Ader an 2 5 V LED 1 aus Menü 3 Anzeige Gültige Karte b...

Page 9: ...erät programmiert wurden Es wird das 4 Byte lange Sicherheitspasswort verwendet Datenübertragung In den folgenden Tabellen werden die Formate aufgelistet die der Kartenleser zum Übertragen von Daten verwendet Die Formate werden durch folgende Faktoren beeinflusst Online oder Offline Modus des Lesers Menü 5 Protokolloptionen Wiegand oder Magnetstreifen Menü 16 Sicherheitsmodus Gesichert oder Ungesi...

Page 10: ...ei cavi Il montaggio del dispositivo su una superficie metallica può comportare una riduzione della portata di lettura 4 Fissare la piastra posteriore su una superficie piana utilizzando quattro viti Per il corretto funzionamento dell interruttore antimanomissione il foro più vicino alla molla antimanomissione deve essere occupato da una vite 5 Terminare il cavo in base alle esigenze vedere più av...

Page 11: ...u 2 della RAS Controllo LED fuori linea Vedere la sezione relativa alla programmazione Giallo L applicazione dipende dalla scelta dell opzione di menu 2 della RAS Controllo LED fuori linea Vedere la sezione relativa alla programmazione Quando non utilizzato per il controllo LED a due cavi il cavo giallo può essere utilizzato per le seguenti applicazioni Ingresso RU quando in linea con l ATS Colleg...

Page 12: ...n lo specifico sistema LED Rx e Tx I LED Rx e Tx visibili sulla scheda dei circuiti quando il coperchio posteriore di plastica viene rimosso semplificano la diagnosi dei guasti Rx Il LED giallo Rx lampeggia per indicare la ricezione dei dati di interrogazione inviati dalla centrale al bus del sistema Se il LED non lampeggia la centrale non è operativa oppure il bus è guasto generalmente si tratta ...

Page 13: ...al minuto per indicare che la RAS è collegata e funziona correttamente Se la protezione antimanomissione dell ATS1197 è attiva il byte di dati non verrà inviato opzione disattivata per impostazione predefinita Menu 8 uscita A C Selezionare una delle opzioni seguenti Relè varco solo modalità in linea l uscita open collector si attiva attiva bassa quando il segnale di varco aperto viene inviato all ...

Page 14: ...iche Tensione di alimentazione Da 8 5 a 14 0 V Corrente massima di funzionamento 110 mA a 13 8 V Corrente normale di funzionamento tutte le aree inserite 40 mA a 13 8 V Uscita open collector terminale OUT 14 V max a 50 mA max Dimensioni L x A x P 140 x 121 x 22 mm Temperatura di esercizio Da 40 a 50 C Umidità relativa 95 senza condensa Informazioni sulle normative Produttore UTC Fire Security Amer...

Reviews: