Figure 2. Installing the circuit board 

ON

ON

1   2   3   4   5   6   7   8

1 2 3 4 5 6 7 8

Antenna shrouds

600-1029 enclosure

Top latches

Bottom latch

2 mm power jack

Terminal block

OEM transceiver 

LEDs

Daughter board

 

4.  Connect DC power to the OEM transceiver module using    

2 mm power jacks (center positive) or connect flyleads to 

the terminal block as labeled on the board. 

LED operation 

Table 1

 shows the LED indications for the OEM transceiver 

module 

Table 1: OEM transceiver module LED indications 

Indication Green 

LED 

Red 

LED 

Powered up 

On 

Off 

Communication with daughter board 

On 

Flashing 

Valid packet received 

One flash off 

Off or flashing

Troubleshooting 

The following table gives troubleshooting suggestions for the 

OEM transceiver module. 

Table 2: OEM transceiver module troubleshooting 

Problem Action 

OEM transceiver module’s green 
and red LEDs are off 

1. Check that the transformer 
is plugged in. 

2. Check the transformer to 
module wiring. 

OEM receiver module’s green LED 
is on and the red LED is off 

Check the daughter board 
mounting. 

Specifications 

Model  

600-1046-95 

Frequency 319.5 

MHz 

Compatibility 

All 319.5 MHz sensors and 319.5 MHz 
receivers 

Current required (without daughter board) 

Typical 45mA 

Maximum 100mA 

Voltage 

8 to 15 VDC 

Wireless range 

1,000 feet (305 m) open air 

Operating temperature 

32 to 120°F (0 to 49°C) 

Storage temperature 

-30 to 140°F (-34 to 60°C) 

Maximum relative 
humidity 

90% noncondensing 

Dimensions 

3.2 x 4.6 x 0.6 inches (8.1 x 11.7 x 1.5 cm) 

Features 

Antenna tamper, jam detect, wall tamper, 
cover tamper 

Optional items: 

Enclosure 600-1029 

USB daughter board 

59-873 

Repeater daughter 
board 

600-1031 

Stand-off 40-262 

Regulatory information 

Manufacturer 

UTC Fire & Security Americas Corporation, Inc.
1275 Red Fox Rd., Arden Hills, MN 55112-6943, 
USA 

FCC compliance 

This device complies with FCC Rules Part 15. 
Operation is subject to the following two 
conditions: 
1. This device may not cause harmful 
interference. 
2. This device must accept any interference that 
may be received, including interference that may 
cause undesired operation. 
Changes or modifications not expressly approved 
by UTC Fire & Security can void the user’s 
authority to operate the equipment. 
FCC ID: B4Z-903-TCVR 
IC: 867A-903-TCVR 

California code 

This product cannot be sold in the state of 
California if used to receive fire signals (per 
section 208-g, Chapter 1.5 Construction Materials 
and Equipment Listings, Title 19, California Code 
of Regulations 
(http://osfm.fire.ca.gov/pdf/fireengineering/bml/t-
19.pdf)). 

Contact information 

For contact information, see www.utcfireandsecurity.com or 

www.interlogix.com. 

For technical support, toll-free: 888.437.3287 in the US 

including Alaska, Hawaii, Puerto Rico, and Canada. Outside 

the tool-free area, contact your dealer. 

Copyright © 2011 Interlogix, a UTC Fire & Security Company. 

All rights reserved. 

2  

OEM Transceiver Module with Crystal Transmitter Installation Instructions 

Reviews: