background image

Figure 7. Mounted sensor 

Door

Door frame

Magnet

Sensor

 

8.  Insert the sensor battery observing correct polarity (

Figure 

3

). 

9.  Attach the sensor cover to the base. 

External contact wiring 

Use the following specifications for the external contact: 

• Maximum 

wire 

length: 26 ft. (8 m). 

• 

Wire: Stranded, 22-gauge (0.7112 mm). 

• 

Switches: Hermetically sealed external switches (sealed 
reed switches) that supply a minimum 250 ms open or 
close on alarm. 

Note:

 Do not connect more than five external contacts to a 

door/window sensor. 

You can wire the sensor terminal blocks with leads from an 
external contact (

Figure 8

). The door/window sensor provides 

alarm and tamper indication. Wire the external contact with one 
end-of-line (EOL) resistor in series with the external contact. 

Caution: 

You must install the EOL resistor at the external 

detection device for proper supervision. For UL listed 

installations, the EOL resistor must be UL listed, manufactured 

by Edwards part number EOL-4k7L, and rated 4.7Kohm. 

This gives the following readings for each configuration: 

Normally closed

 

Zero ohm/short = Tamper 
4.7 Kohm = Normal 
Open = Alarm 

Normally open

 

Zero ohm/short = Tamper 
4.7 Kohm = Alarm 
Open = Normal 

Figure 8

 shows external contact wiring (normally closed and 

normally open). For UL listed installations, use only UL listed 
accessories/contacts. 

Figure 8. External contact wiring 

Door/Window

Contacts

EOL resistor

     Sensor

  4.7 Kohm

 

Sensor test 

The sensor test verifies proper communication between the 
sensor and the panel/receiver. To test the sensor, refer to the 
specific panel/receiver documentation and do the following: 

1.  Put the panel/receiver into sensor test mode. 

2.  Open the door/window the sensor is protecting. The 

sensor transmits a signal. 

3.  Listen for siren beeps to determine the appropriate 

response. 

4.  Exit sensor test mode. 

Battery replacement 

Note

: Battery replacement should be done by trained 

personnel only. 

When the system indicates low sensor battery, replace it 
immediately. Use the recommended replacement batteries 
(see 

Specifications

). 

To replace the batteries: 

1.  Remove the sensor cover. 

2.  Remove the battery. Follow local laws for battery disposal. 

3.  Insert the replacement battery, observing correct polarity 

(

Figure 3

). 

4.  Perform a sensor test with the panel. See 

Sensor test

Caution: 

The battery used in this device may present a fire or 

chemical burn hazard if improperly handled. Do not recharge, 

disassemble, heat above 100°C (212°F), or dispose of in fire. 

Use only batteries listed in the 

Specifications

 section. Use of 

another battery may present a risk of fire or explosion. 

Troubleshooting 

This information is provided to help you diagnose and solve 
various problems that may arise while configuring or using the 
door/window sensor. 

Power up / battery 

If the unit does not power up properly: 

• 

Make sure the battery is fully seated within the battery 
bucket and the polarity is correct. 

• 

Check the battery voltage  (3.0 VDC nominal). 

RF communication 

If the control panel does not respond: 

• 

Use the 60-401 RF Sniffer to make sure the transmitter is 
sending messages for activation. 

• 

Move or rotate the sensor position. 

319.5 Crystal MaxLife Door/Window Sensor Installation Instructions  

Summary of Contents for 319.5

Page 1: ...to moisture or where the operating temperature range will exceed the specified range If possible mount directly to a stud If a stud is not available use plastic anchors Avoid mounting the sensor in areas with a large quantity of metal or electrical wiring Only one input can be used at any given time You must mount the magnet within 3 8 in 0 95 cm of the sensor Mount sensors with screws not double ...

Page 2: ...nsor verify the sensor mounting location provides good RF panel communication To verify 1 Put the panel receiver into sensor test mode 2 Take the sensor to the mounting location 3 Hold the magnet next to the alignment mark on the sensor Figure 5 and then pull the magnet away from the sensor Figure 5 Alignment marks Sensor end view Sensor side view Magnet Alignment marks 4 Listen for siren beeps to...

Page 3: ...anel receiver To test the sensor refer to the specific panel receiver documentation and do the following 1 Put the panel receiver into sensor test mode 2 Open the door window the sensor is protecting The sensor transmits a signal 3 Listen for siren beeps to determine the appropriate response 4 Exit sensor test mode Battery replacement Note Battery replacement should be done by trained personnel on...

Page 4: ...thium Required batteries Duracell DL 123A Energizer EL123 Sanyo CR123A Estimated battery life 5 to 10 years at 20 C 68 F depending on the number of activations per day Magnet gap 3 8 in max Supervisory interval 64 minutes End of line resistor 4 7 Kohm Typical RF output power 0 25mW EIRP Operating temperature 32 to 120 F 0 to 49 C Storage temperature 30 to 140 F 34 to 60 C Relative humidity 0 to 85...

Reviews: