8  Setting the Address 

An address must be set for identification. 

Address setting for the connection to a terminal controller or an access manager:

 

It is common practice to assign the first slave terminal on each RS485 BUS to address 1, the second to 
address 2, and so on. 

Address setting for the connection to a master terminal:

 

It is common practice to assign the first slave terminal to address 2, the second to address 3, and so on. 

Before making the settings, check the BUS address section of the higher-ranking device, such as, e.g., a 
master terminal. You can do so by using a remote program, e.g. Telnet, and entering the OC command "cfg". 
Furthermore, please check if the address of the terminal already exists on this BUS. It is not allowed to 
assign identical addresses to one RS485 BUS. 

 

 

 

Switch off the power supply prior to changing an address. 

Switch: 

Address 1 (A) 

OFF 

OFF 

OFF 

OFF (not required if connected to a master terminal) 

Address 2 (B) 

ON 

OFF 

OFF 

OFF 

Address 3 (C) 

OFF 

ON 

OFF 

OFF (as shown in the figure above) 

Address 4 (D) 

ON 

ON 

OFF 

OFF 

Address 5 (E) 

OFF 

OFF 

ON 

OFF 

Address 6 (F) 

ON 

OFF 

ON 

OFF 

Address 7 (G) 

OFF 

ON 

ON 

OFF 

Address 8 (H) 

ON 

ON 

ON 

OFF 

 

 

Summary of Contents for IF-800/W02

Page 1: ...l mounting Please check the completeness and condition of the shipment upon receipt 2 Function Slave terminals of series IF 800 W02 are used for 1 controlling the access of people who identify themsel...

Page 2: ...sfer problems must be examined on a case by case basis Where necessary a shielded cable must be used for the corresponding devices 5 How to Proceed During Installation The following installation proce...

Page 3: ...aid in empty conduit 100 m 4 x 2 x 0 6 mm 2 Control line for electric actuator No specifications 2 x 2 x 0 6 mm 3 Cable to door sensor handle contact or opening push button 100 m 2 x 2 x 0 6 mm 4 RS48...

Page 4: ...ID readers When the device is mounted on a metal surface the reading distance is reduced Close housing The housing cover 3 is first placed over the reader electronics during initial operation To close...

Page 5: ...gs check the BUS address section of the higher ranking device such as e g a master terminal You can do so by using a remote program e g Telnet and entering the OC command cfg Furthermore please check...

Page 6: ...r master terminal please refer to the installation and wiring instructions included in the delivery of the respective device 1 IF 800 W02 6 Example Door monitoring connection 2 I O controller board 7...

Page 7: ...Protection Protection category III Degree of protection Reader IP65 encapsulated electronics I O board IP 00 General Data Ambient temperature 25 C to 55 C Humidity Max 95 non condensing Product safety...

Reviews: