Wiring Terminal Description

11

5.2   Indoor Unit Wiring

Power Supply 

When the power cable is parallel to the signal wire, make sure 

that they are enclosed in respective conduits and are kept a

reasonable wire spacing. (Distance between power cables: 

less than 10A-300mm; less than 50A-500mm)

The three-core shielded cable is used as the signal cables of 

the IDUs and ODU, and the shield layer must be grounded as 

required.

The display box and build-out resistor are IDU accessories. 

The remote controller, centralized controller and wired 

controller are optional accessories. If necessary, contact the 

local distributor for purchase. (Note: The BP3 series IDUs 

provide standard remote controllers.)

CAUTION

Table 5-2

Fig. 5-3

Fig. 5-4

Circuit Breaker (A)

16

Refer to Table 5-3 for wire size 

Indoor 

Unit 

Power

Phase

Voltage and Frequency 

1-Phase

220-240V~  50/60Hz

Indoor Unit /Outdoor Unit Signal 

Wire (mm

2

) (Weak electric signal)

3-core shielded wire

3X0.75

Only the dedicated meter of Intensity can be used on the unit.

For the wiring method of the meter, please consult Intensity’s 

professional service personnel.

CAUTION

Capacity (kBtu/h)

7~56

Power Wiring Size

       

X    Y    E    P

   

Q

   

E

Communication 

of IDUs

Centralized 

controller  

IDU

IDU

IDU

IDU

ODU

P Q E

P Q E

P Q E

Build-out resistor

Remote 

controller

Wired controller

P Q E

P Q E X Y E

Please use the shielded wire, and the shield layer must be grounded.

Note: The wired controller and centralized controller in the dashed box are optional 

accessories. If necessary, please contact the local distributor for purchase.

Suspend

Centralized 

controller

X Y E

Only the last IDU 

requires adding the 

build-out resistor at 

P and Q.

Nominal cross-sectional area (mm

2

 ) 

 

  

>3  

   >6 

 >10 
 >16 

 >25 

 >32 

 >50 

and 
and 
and 
and 
and 
and 
and 

3

  

  

10 

16 

25 

32 

50 

63 

 

0.75 

1.5
2.5

  6 

  10 

and 
and 
and 
and 
and 
and 
and 


1.5 
2.5
4

10
16

0.5   and 

0.75

Flexible cords

Cable for fixed wiring

4

10

to

1.5

4

to

1

2.5

to

1

2.5

to

1

2.5

to

2.5

6

to

6

16

to

10

25

to

 Rated current 

of appliance(A) 

Safety device requirements

2. Maximum allowable voltage range variation between phases is  

    2%.

3. Select circuit breaker that having a contact separation in all poles 

not less than 3 mm providing full disconnection

where MFA is 

used to select the current circuit breakers and residual current 

operation breakers:

1. Select the wire diameters( minimum value) individually for each

unit based on the table 5-1 and table 5-3

 where the MCA in 

table 5-1 means Rated current in table 5-3. In case the MCA  

exceeds 40A, the wire diameters should be selected according 

to the table 5-3 is 6 to 16.

Table 5-3

Running

Timer Defrosting E-heat

Later

High

Running

Timer Defrosting E-heat

Running

Timer Defrosting E-heat

Running

Timer Defrosting E-heat

Later

High

Later

High

Later

High

Summary of Contents for BlackSeries DIVERSE MDV-V28W/DHN1(At)

Page 1: ...DHN1 At MDVC V42W DHN1 At MDVC V48W DHN1 At MDVC V56W DHN1 At MDV V28W DHN1 At MDV V36W DHN1 At MDV V42W DHN1 At MDV V48W DHN1 At MDV V56W DHN1 At DIVERSE Thank you very much for purchasing our air c...

Page 2: ...ce RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule The power cord type designation is H05RN R H07RN F or above Ask an authorized dealer or qu...

Page 3: ...mp Do not use refrigerant charged in the outdoor unit for air purge The refrigerant for air purge is not contained in the outdoor unit Electrical cabling Be sure to fix the power cables and indoor out...

Page 4: ...ficient ventilation place Near a private power station or high Frequency equipment The insulation of the metal parts of the building and the air conditioner should comply with the regulation of Nation...

Page 5: ...units refer to Fig 3 7 Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind refer to Fig 3 7 Since the gravity center of the unit is not a...

Page 6: ...hile connect to the connecting pipes outside and then piping and wiring through this Pay attention to the piping the fat connecting pipe should out from the largest hole otherwise the pipes will be ru...

Page 7: ...able 4 4 the air liquid side of L2 is 15 9 9 5 N1 28 N3 28 N5 28 N6 22 N2 28 N4 28 A B D E C a b c e f d L1 L2 L5 L3 L4 The straight distance between copper pipe turning and the contiguous branch pipe...

Page 8: ...should not longer than 15m Indoor unit branch pipe The main pipes of indoor unit and the indoor unit branch pipe components The downstream inner units of the main pipe L2 are N1 N2 and its total capa...

Page 9: ...h 20m 36 42kBtu h 20m 48 56kBtu h Drop HEIGHT between indoor unit and outdoor unit The first connect method Indoor Unit The First Line Branch Pipe Outdoor unit a A L2 L1 B C D E L3 L4 L5 b c d e f Fig...

Page 10: ...er enters the pipes After the above vacuum drying of two hours use nitrogen to increase the pressure to 0 05 MPa vacuum breaking and use a vacuum pump to decrease the pressure to lower than 100 7kPa o...

Page 11: ...u h Hz Voltage Min V Max V MCA TOCA MFA MSC RLA kW FLA 220 240V 1Ph 50 60Hz Power Supply Compressor OFM Power Source PQE PQE PQE L N P Q E X Y E Outdoor power supply Indoors Power supply ODU IDU IDU I...

Page 12: ...ntroller Wired controller P Q E P Q E X Y E Please use the shielded wire and the shield layer must be grounded Note The wired controller and centralized controller in the dashed box are optional acces...

Page 13: ...Wire controller The reserved wire control function is indicated in broken line table users can purchase the wire controller when necessary In broken line table users can purchase the wire controller...

Page 14: ...ustomers in details Please press constraint cool button to carry out refrigerant recycling process Keep the low pressure above 0 2MPa other wise compressor may be burnt out Fig 7 1 NOTE 7 1 Important...

Reviews: