intensity BlackSeries DIVERSE MDV-V28W/DHN1(At) Installation Manual Download Page 10

Make  sure  there  is  no  any dirt  or  water before connecting 

the piping to the outdoor units. 
Wash the piping with high pressure nitrogen, never use 

refrigerant of outdoor unit.

4.7   Remove Dirt or Water in the Piping

4.8   Airtight Test

Air tightness test – nitrogen must be used. (See the figure on

 the right for the location of the maintenance access).

Increase the pressure from the liquid pipe and gas pipe to 4.0 

MPa at the same time (not exceeding 4.0 MPa). If the pressure 

does not drop in 24 hours, the test is passed.

When the pressure drops, check the leakage position (after 

you make sure that there is no leakage, discharge the nitrogen).

CAUTION

Never use oxygen, combustible gas, or poisonous gas in the air 

tightness test.

To prevent damage to the equipment, the pressure must not be 

held for too long.

9

4.9   Air Purge with Vacuum Pump

4.10   Refrigerant Amount to be Added

Use a vacuum pump that can evacuate the pipe to the pressure 

of less than -100.7 kPa (5 Torr, -755 mmHg). When the pump is 

stopped, do not let the pump oil fow back into the refrigerant 

pipe.

The liquid and gas pipes should be evacuated with a vacuum 

pump for more than two hours to the pressure of less than 

-100.7kPa. Then, place the pipes with the pressure of less than 

-100.7 kPa for more than one hour, and check whether the 

reading of the vacuum gauge rises. (If the reading rises, there is 

residual water or gas leakage in the system. The leakage must 

be checked and solved and the test should be performed again.)

Water may enter into pipes in the following conditions: the 

installation is carried out in rainy seasons and the installation 

period is long; the pipes are condensed inside; rainwater enters 

the pipes.

After the above vacuum drying of two hours, use nitrogen to 

increase the pressure to 0.05 MPa (vacuum breaking), and use 

a vacuum pump to decrease the pressure to lower than -100.7kPa 

or below and hold the pressure for one hour (vacuum drying).

Calculate the amount of the R410A refrigerant to be added based 

on the diameter and length of the liquid pipes of the ODU and IDUs.

NOTE

Additional refrigerant volume of divergent pipe is 0.1kg 

per item (Consider the liquid side of divergent pipe only)

CAUTION

Use a vacuum pump to perform the vacuuming process. Do not 

use refrigerant gas to discharge air.

Use a vacuum pump that can vacuumize the pipe to the pressure 

of less than -100.7 kPa (5 Torr, -755 mmHg). When the pump is 

stopped, do not let the pump oil flow back into the refrigerant 

pipe.

In order to prevent the entry of impurities, the R410A special tool 

must be used to ensure the compression strength. Use a filling

hose with a top rod to connect to the maintenance access of 

the check valve or the refrigerant filling port.

Liquid Side Piping 

      Diameter

Refrigerant to be Added 

     Permitted Piping

Φ9.5

Φ12.7

Φ15.9

0.054kg

0.110kg

0.170kg

Φ6.4

0.022kg

Table 4-12

When the outdoor unit connects 1 indoor unit:

The second Connect method

Indoor unit

a

N

1

3

N

N

5

N

6

N

2

N

4

Outdoor unit

A

B

D

E

C

b

c

e

f

d

1

L

2

L

5

L

3

L

4

L

Drop HEIGHT

 between indoor unit and outdoor unit

Maximum pipe equivalent length

Pipe length(From the nearest branch

 pipe equivalent length

(From the first line branch pipe) 

Maximum pipe equivalent length 

Indoor Unit to Indoor Unit Drop Heigh

t

The First Line Branch Pipe

Fig.4-8

 (If the pressure cannot be decreased to lower than -100.7 kPa after 

two-hour vacuuming, repeat the vacuum breaking and vacuum 

process.) After that, place the vacuum pipes for one hour, and 

then check whether the reading of the vacuum gauge rises.

Summary of Contents for BlackSeries DIVERSE MDV-V28W/DHN1(At)

Page 1: ...DHN1 At MDVC V42W DHN1 At MDVC V48W DHN1 At MDVC V56W DHN1 At MDV V28W DHN1 At MDV V36W DHN1 At MDV V42W DHN1 At MDV V48W DHN1 At MDV V56W DHN1 At DIVERSE Thank you very much for purchasing our air c...

Page 2: ...ce RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule The power cord type designation is H05RN R H07RN F or above Ask an authorized dealer or qu...

Page 3: ...mp Do not use refrigerant charged in the outdoor unit for air purge The refrigerant for air purge is not contained in the outdoor unit Electrical cabling Be sure to fix the power cables and indoor out...

Page 4: ...ficient ventilation place Near a private power station or high Frequency equipment The insulation of the metal parts of the building and the air conditioner should comply with the regulation of Nation...

Page 5: ...units refer to Fig 3 7 Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind refer to Fig 3 7 Since the gravity center of the unit is not a...

Page 6: ...hile connect to the connecting pipes outside and then piping and wiring through this Pay attention to the piping the fat connecting pipe should out from the largest hole otherwise the pipes will be ru...

Page 7: ...able 4 4 the air liquid side of L2 is 15 9 9 5 N1 28 N3 28 N5 28 N6 22 N2 28 N4 28 A B D E C a b c e f d L1 L2 L5 L3 L4 The straight distance between copper pipe turning and the contiguous branch pipe...

Page 8: ...should not longer than 15m Indoor unit branch pipe The main pipes of indoor unit and the indoor unit branch pipe components The downstream inner units of the main pipe L2 are N1 N2 and its total capa...

Page 9: ...h 20m 36 42kBtu h 20m 48 56kBtu h Drop HEIGHT between indoor unit and outdoor unit The first connect method Indoor Unit The First Line Branch Pipe Outdoor unit a A L2 L1 B C D E L3 L4 L5 b c d e f Fig...

Page 10: ...er enters the pipes After the above vacuum drying of two hours use nitrogen to increase the pressure to 0 05 MPa vacuum breaking and use a vacuum pump to decrease the pressure to lower than 100 7kPa o...

Page 11: ...u h Hz Voltage Min V Max V MCA TOCA MFA MSC RLA kW FLA 220 240V 1Ph 50 60Hz Power Supply Compressor OFM Power Source PQE PQE PQE L N P Q E X Y E Outdoor power supply Indoors Power supply ODU IDU IDU I...

Page 12: ...ntroller Wired controller P Q E P Q E X Y E Please use the shielded wire and the shield layer must be grounded Note The wired controller and centralized controller in the dashed box are optional acces...

Page 13: ...Wire controller The reserved wire control function is indicated in broken line table users can purchase the wire controller when necessary In broken line table users can purchase the wire controller...

Page 14: ...ustomers in details Please press constraint cool button to carry out refrigerant recycling process Keep the low pressure above 0 2MPa other wise compressor may be burnt out Fig 7 1 NOTE 7 1 Important...

Reviews: