1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00911-000 Rev. B 072619
www.Intellitec.com
Intellitec
INSTALLATION AND SERVICE MANUAL
P
L
OWER INE 2004
Energy Management System
TM
PLACEMENT
REMOTE PANEL
continued)
The 12 VDC voltage connections are made through the 8 pin Mate-N-Lok plug on the low voltage side of the
Control Module. The connections are as follows:
1
+ 12 Volts
2
Ground
3
Relay 3 Normally Open
4
Relay 3 Common
5
Relay 3 Normally Closed
6
Relay 4 Common
7
Relay 4 Normally Closed
8
Gen. Set Run +12 VDC Input
The +12 volts should be supplied from a source fused at 5 Amps minimum and capable of delivering up to 1 Amp of
AVERAGE current. Protecting this connection with a higher rated fuse is acceptable since the EMS is internally
protected with 5 Amp fuse. The low voltage wires are brought into the box through the large hole in the lower left-
hand corner of the back of the box.
The Relay 3 connections are typically made to the low voltage compressor control wires of the air conditioners. The
normally closed contacts are wired in "series" with the compressor control lead. This means that the compressor
control wire is cut and the two ends are wired to the Common and the Normally Closed contacts of Relay 3. In this
way, the EMS can interrupt the operation of the compressor, just as the thermostat does.
The Relay 4 connections
are typically made to the thermostat wires of the air conditioners. The normally closed contacts are wired in "series"
with the thermostat. This means that the thermostat wire is cut and the two ends are wired to the Common and the
Normally Closed contacts of Relay 4. In this way, the EMS can interrupt the operation of the fan, just as the
thermostat does.
Select a convenient location for the panel, where it can be easily viewed by the owner. Cut a hole in the panel
for the panel as shown.
Pin
Function
6