background image

 

                                                      53‐01118‐100 Rev B  06/09/2020 

Page 2 

USER’S

 

GUIDE

 

 
 
 
 

Diagnostics 

 
If the Battery Guard® 1000 is fails to operate as intended, locate the device. The Battery Guard® 1000 provides a 
diagnostic LED on the module that indicates several failure modes. 
 

 

(Diagnostic LED located in the lower right corner) 

 
1 Blink – Failed to disconnect 
2 Blinks – Failed to reconnect 
3 Blinks – Below minimum disconnect voltage. 
 
This information can be very useful when trying to troubleshoot the Battery Guard® 1000. In the event that 
there is an issue and the operator needs to bypass the disconnect. Remove the System load wire from the 
Battery Guard 1000 terminal and move it to the same side as the positive battery feed. 
 

WARNING: Before performing this task, disconnect all sources of power. Unplug the coach and turn off the 
generator. Disconnect the battery(s) negative (‐) terminal. 

 Operating Parameters 

 

The table below defines the operating parameters used by the Battery Guard® 1000. The device comes with two 
sets of preconfigured parameters, one for chassis disconnects and one for coach disconnects. Depending on 
what mode the device is in, the parameters may vary. 
 

Parameter 

Chassis Battery 

Coach Battery 

Low Voltage Disconnect Threshold 

12.1 Volts 

10.5 Volts 

Isolation Delay 

5 Minutes 

3 Minutes 

Minimum Disconnect Threshold 

9.0 Volts 

Charging Voltage Threshold 

13.3 Volts 

Reconnect Delay 

1 Minute 

State Change Delay 

5 Seconds 

 
 
Refer to the 53‐01118‐200 Installation Guide on how to switch between configurations.  

 